Daikin EUWAC8FZW1 Скачать руководство пользователя страница 17

EUWAC5~10FZ

Packaged air-cooled water chillers

4PW14037-1D

Installation and operation manual

14

Symptom 4: One of the following safety devices is activated

Symptom 5: Unit stops soon after operation

Symptom 6: Unit runs continuously and the water temperature remains 
higher, respectively lower than the temperature set on the controller

Symptom 7: Excessive noises and vibrations of the unit

Symptom 8: Water drips out of the unit

Symptom 9: Continuous switching between high and low fanspeed

Symptom 4.1:  Overcurrent relay of compressor

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

Overload of motor.

Reset. If the failure persists, call your 
local Daikin dealer.

RESET

Push the red button on the over-
current relay inside the switch box. 
The controller still needs to be reset.

Symptom 4.2:  Low pressure switch or anti-freeze alarm

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to water heat exchanger 
too low.

Increase the water flow.

Shortage of refrigerant.

Check for leaks and refill refrigerant, 
if necessary.

Unit is working out of its operation 
range.

Check the operation conditions of 
the unit.

Inlet temperature to the water heat 
exchanger is too low.

Increase the inlet water temperature.

Flow switch is not working or no 
water flow.

Check the flow switch and the water 
pump.

RESET

After pressure rise, the low pressure 
switch resets automatically, but the 
controller still needs to be reset.

Symptom 4.3:  High-pressure switch

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Condenser fan does not operate 
properly.

Check that the fans turn freely. Clean 
if necessary.

In case the factory pulley setting has 
been changed, it is possible that the 
used pulley setting with lower airflow 
does not allow optimal working.

Reduce the pulley setting back grad-
ually towards the factory setting until 
the problem is solved.

Dirty or partially blocked condenser.

Remove any obstacle and clean 
condenser coil using brush and 
blower.

Inlet air temperature of the 
condenser is too high.

The air temperature measured at the 
inlet of the condenser should not 
exceed 43°C.

RESET

After pressure decrease, the high 
pressure switch resets automatically, 
but the controller still needs to be 
reset.

Symptom 4.4:  Fan thermal protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Mechanical failure (fan is blocked).

Check that the fan rotates freely.

Air flow in the unit too low or outdoor 
temperature too high.

Clean the air heat exchanger 
properly.

RESET

After temperature decrease, the 
thermal protector is reset 
automatically.

If the protector is activated 
frequently, replace the motor or call 
your local Daikin dealer.

Symptom 4.5:  Reverse phase protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Two phases of the power supply are 
connected in the wrong phase 
position.

Invert two phases of the power 
supply (by licensed electrician).

One phase is not connected 
properly.

Check the connection of all phases.

RESET

After inverting two phases or fixing 
the power supply cables properly, 
the protector is reset automatically, 
but the controller still needs to be 
reset.

Symptom 4.6:  Discharge thermal protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit is working outside the operation 
range.

Check the operation condition of the 
unit.

RESET

After temperature decrease, the 
thermal protector resets 
automatically but the controller still 
needs to be reset.

Symptom 4.7:  Flow switch is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

No water flow.

Check the water pump.

RESET

After finding the cause, the flow 
switch is reset automatically, but the 
controller still needs to be reset.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

One of the safety devices is 
activated. 

Check safety devices (refer to 

"One 

of the following safety devices is 
activated" on page 14

).

Voltage is too low.

Test the voltage in the supply panel 
and, if necessary, in the electrical 
compartment of the unit (voltage 
drop due to supply cables is too 
high).

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The temperature setting on the 
controller is too low.

Check and adjust the temperature 
setting.

The heat production in the water 
circuit is too high.

The cooling capacity of the unit is too 
low. Call your local Daikin dealer.

Water flow is too high.

Recalculate the water flow.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit has not been fixed properly.

Fix the unit as described in the 
chapter “

Installing the unit

”.

The flexible connections between 
the ducting flanges of the unit and 
the ducts are not installed or are 
worn out.

Check the air ducts and fix them 
properly as described in the chapter 

Installing the unit

”, or install flexible 

ducts.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Blocked drain pipe.

Check the drain outlet and clean it, if 
necessary.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

In case the factory pulley setting has 
been changed, it is possible that the 
used pulley setting with lower airflow 
does not allow optimal working.

Reduce the pulley setting back grad-
ually towards the factory setting until 
the problem is solved.

Содержание EUWAC8FZW1

Страница 1: ...INSTALLATION AND OPERATION MANUAL EUWAC5FZW1 EUWAC8FZW1 EUWAC10FZW1 Packaged air cooled water chillers...

Страница 2: ...D E F G H I J K L M N O P Q R EUWAC5FZ mm 243 311 243 1345 343 125 765 71 58 629 108 25 796 605 735 578 600 795 EUWAC8FZ mm 163 800 162 1290 267 98 815 71 60 951 111 25 1125 605 288 975 600 1122 EUWAC...

Страница 3: ...en i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob u...

Страница 4: ...and used for cooling applications only The units are available in 3 standard sizes with nominal cooling capacities ranging from 11 2 to 22 6 kW The EUWAC packaged air cooled water chillers can be comb...

Страница 5: ...dboard box and attached on a wooden pallet At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account...

Страница 6: ...the water circuit 1 Use clean pipes only 2 Hold the pipe end downwards when removing burrs 3 Cover the pipe end when inserting it through a wall so that no dust and dirt enter WATER CHARGE FLOW AND Q...

Страница 7: ...d that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the public sys tem It is the responsibility of the installer or user of the equip me...

Страница 8: ...lter installed behind the condenser removes small particles from the refrigerant to prevent blockage of the expansion valve and tubes Thermostatic expansion valve The liquid refrigerant coming from th...

Страница 9: ...ter becomes too low in order to prevent freezing of the water during operation When the outlet water temperature returns to normal the protector resets automatically but the controller needs to be res...

Страница 10: ...er operation of the drain Pour some water into the drain pan and check whether the water evacuates freely through the drain Water supply Fill the water piping taking into account the minimum water vol...

Страница 11: ...9 Consulting actual operational information on page 9 Resetting alarms on page 9 Resetting warnings on page 10 Switching the EUWAC unit on To switch the EUWAC unit on proceed as follows 1 When the on...

Страница 12: ...er temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of direct parameters without saving the modified parameter The inlet water t...

Страница 13: ...t of direct parameters is accessible by pressing the R key for approximately 5 seconds When scrolling through the list of direct parameters using the A and or Z key the parameters appear in the follow...

Страница 14: ...aying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifications The i...

Страница 15: ...t other user parameters before saving the modifications select another user parameter using the A and or Z key and then repeat from instruction 3 onwards 7 To save the modifications press the E key To...

Страница 16: ...without saving the modifications The inlet water temperature reappears on the display TROUBLESHOOTING This section provides useful information for diagnosing and correct ing certain troubles which may...

Страница 17: ...freely Air flow in the unit too low or outdoor temperature too high Clean the air heat exchanger properly RESET After temperature decrease the thermal protector is reset automatically If the protecto...

Страница 18: ...leak is detected call your local Daikin dealer Check the working pressure of the unit Refer to paragraph Working pressure on page 8 in the chapter Switching the EUWAC unit on 6 Compressor Check on oi...

Страница 19: ...5 10 5 15 20 15 30 25 40 35 50 C 45 5 Hp 8 Hp 10 Hp General specifications IN OUT IN OUT IN OUT Nominal air flow m3 min 70 70 100 100 125 125 long side W mm 763 341 952 802 1102 938 short side P mm 6...

Страница 20: ...ESP External static pressure AF Air flow 1 ESP with pulley closed factory setting 2 ESP with pulley 1 turn open 3 ESP with pulley 2 turns open 4 ESP with pulley 3 turns open 5 ESP with pulley 4 turns...

Страница 21: ...4 4 6 7 16 11 10 12 13 6 7 16 11 10 12 13 2 15 4 5 2 15 3 9 8 1 14 9 8 1 14 5 5 M1C P S4LP 6 P S1HP 7 1 3 9 8 5 4 2 10 10 R3T R4T M11F M11F EUWAC5 EUWAC8 10...

Страница 22: ...4PW14037 1D Copyright Daikin...

Отзывы: