6 Electrical installation
Installation manual
16
ETVH/23E
Daikin Altherma 3 H MT F
4P634880-1C – 2022.08
A
Y1
7
B
A
B
7 9
X2M
A4P
Y1
YC
X1M
a
b
a
Installation of EKRP1HBAA is required.
b
Prewiring between X2M/7+9 and Q1L (= thermal
protector backup heater). Do NOT change.
3
Fix the cable with cable ties to the cable tie mountings.
6.3.7
To connect the space cooling/heating ON/
OFF output
INFORMATION
Cooling is only applicable in case of reversible models.
Wires: (2+1)×0.75 mm²
Maximum load: 0.3 A, 250 V AC
—
1
Open the following (see
"4.2.1 To open the indoor unit"
5]):
1
Top panel
1
2
3
2
User interface panel
3
Upper switch box cover
2
Connect the space cooling/heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.
7 9
YC
Y2
X2M
1
2
3
A4P
1+2
Wires connected to the space
cooling/heating ON/OFF
output
3
Wire between X2M and A4P
A4P
Installation of EKRP1HBAA is
required.
A
Y2
7
B
A
B
7 9
X2M
A4P
Y2
YC
X1M
a
b
a
Installation of EKRP1HBAA is required.
b
Prewiring between X2M/7+9 and Q1L (= thermal
protector backup heater). Do NOT change.
3
Fix the cable with cable ties to the cable tie mountings.
6.3.8
To connect the changeover to external
heat source
INFORMATION
Bivalent is only possible in case of 1 leaving water
temperature zone with:
▪ room thermostat control, OR
▪ external room thermostat control.
Wires: 2×0.75 mm²
Maximum load: 0.3 A, 250 V AC
Minimum load: 20 mA, 5 V DC
[9.C]
Bivalent
1
Open the following (see
"4.2.1 To open the indoor unit"
5]):
1
Top panel
1
2
3
2
User interface panel
3
Upper switch box cover
2
Connect the changeover to external heat source cable to the
appropriate terminals as shown in the illustration below.