9
|
Electrical installation
Installer reference guide
108
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1C – 2023.07
9.2 Connections to the outdoor unit
Item
Description
Power supply cable
"9.2.1 To connect the electrical wiring to the
108].
Interconnection cable
Drain tube heater cable
Connection for power
saving function (only for V3
models)
Air thermistor cable
"9.2.2 To reposition the air thermistor on the
114].
9.2.1 To connect the electrical wiring to the outdoor unit
1
Open the switch box cover. See
"7.2.2 To open the outdoor unit"
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3
Insert the cables at the back of the unit, and route them through the factory-
mounted cable sleeves into the switch box.
d
c2
b2
c1
b1
a1
a2
a1+a2
Power supply cable (field supply)
b1+b2
Interconnection cable (field supply)
c1+c2
(optional) Drain tube heater cable (field supply)
d
Cable sleeves (factory-mounted)
4
Inside the switch box, connect the wires to the appropriate terminals, and fix
the cables with cable ties. See: