5
|
Application guidelines
Installer reference guide
32
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
Power meter types
Single-phase power meter.
5.5 Setting up the power consumption control
You can use the following power consumption controls. For more information
about the corresponding settings, see
#
Power consumption control
1
"5.5.1 Permanent power limitation"
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) with one permanent
setting.
▪
Limitation of power in kW or current in A.
2
"5.5.2 Power limitation activated by digital inputs"
▪
Allows you to limit the power consumption of the entire heat pump
system (sum of indoor unit and backup heater) via 4 digital inputs.
▪
Limitation of power in kW or current in A.
5.5.1 Permanent power limitation
Permanent power limitation is useful to assure a maximum power or current input
of the system. In some countries, legislation limits the maximum power
consumption for space heating and DHW production.
P
i
t
DI
a
b
P
i
Power input
t
Time
DI
Digital input (power limitation level)
a
Power limitation active
b
Actual power input
Setup and configuration
▪
No additional equipment needed.
▪
Set the power consumption control settings in [A.6.3.1] via the user interface (for
the description of all settings, see
96]):
-
Select full time limitation mode
-
Select the type of limitation (power in kW or current in A)
-
Set the desired power limitation level
NOTICE
Set a minimum power consumption of ±3.6 kW to guarantee:
▪
Defrost operation. Otherwise, if defrosting is interrupted several times, the heat
exchanger will freeze up.
▪
Space heating and DHW production by allowing the backup heater step 1.
Содержание ERLA03DAV3
Страница 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Страница 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Страница 189: ......
Страница 190: ......
Страница 191: ......
Страница 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...