9

 | 

Electrical installation

Installer reference guide

113

ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01

Wire type

Installation method

Single-core wire

c b

c

a

a

A

AA´

a

 Curled single-core wire

b

 Screw

c

 Flat washer

Stranded conductor wire
with round crimp-style
terminal

c b

b

a

c

a

B

B

a

 Terminal

b

 Screw

c

 Flat washer

 Allowed

 NOT allowed

Tightening torques

Outdoor unit:

Item

Tightening torque (N•m)

M4 (X1M)

1.2~1.5

M4 (earth)

Indoor unit:

Item

Tightening torque (N•m)

M4 (X1M)

1.2

M4 (X12M, X15M)

0.88 ±10%

Indoor unit – BUH option:

Item

Tightening torque (N•m)

M4 (X6M) *3V, *6V

2.45 ±10%

M4 (X6M) *9W

1.2

9.1.3 About electrical compliance

Only for the backup heater of the indoor unit

See 

"9.3.3 To connect the backup heater power supply"

 [

4

 124].

9.1.4 About preferential kWh rate power supply

Electricity  companies  throughout  the  world  work  hard  to  provide  reliable  electric
service  at  competitive  prices  and  are  often  authorised  to  bill  clients  at  benefit
rates.  E.g.  time-of-use  rates,  seasonal  rates,  Wärmepumpentarif  in  Germany  and
Austria, ...

Содержание ERGA06EAV3H

Страница 1: ...V3H ERGA08EAV3H ERGA04EAV3A ERGA06EAV3A ERGA08EAV3A ERGA04EAV37 EHSH04P30EF EHSHB04P30EF EHSH08P30EF EHSHB08P30EF EHSH08P50EF EHSHB08P50EF EHSX04P30EF EHSXB04P30EF EHSX04P50EF EHSXB04P50EF EHSX08P30EF...

Страница 2: ...5 3 3 Possible options for the indoor unit 29 6 Application guidelines 33 6 1 Overview Application guidelines 33 6 2 Setting up the space heating cooling system 34 6 2 1 Single room 35 6 2 2 Multiple...

Страница 3: ...erant piping 90 8 2 3 Guidelines when connecting the refrigerant piping 90 8 2 4 Pipe bending guidelines 91 8 2 5 To flare the pipe end 91 8 2 6 To braze the pipe end 92 8 2 7 Using the stop valve and...

Страница 4: ...46 11 1 1 To access the most used commands 147 11 1 2 To connect the PC cable to the switch box 149 11 2 Configuration wizard 149 11 3 Possible screens 151 11 3 1 Possible screens Overview 151 11 3 2...

Страница 5: ...ise cavitation 257 15 3 7 Symptom The pressure relief valve opens 258 15 3 8 Symptom The water pressure relief valve leaks 258 15 3 9 Symptom The space is NOT sufficiently heated at low outdoor temper...

Страница 6: ...n manual Outdoor unit Installation instructions Format Paper in the box of the outdoor unit Installation manual Indoor unit Installation instructions Format Paper in the box of the indoor unit Install...

Страница 7: ...nal Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication required Online tools In addition to the documentation set some o...

Страница 8: ...result in death or serious injury WARNING FLAMMABLE MATERIAL CAUTION Indicates a situation that could result in minor or moderate injury NOTICE Indicates a situation that could result in equipment or...

Страница 9: ...formation on how to prepare for an installation Piping installation What to do and know to install the piping of the system including information on how to prepare for an installation Electrical insta...

Страница 10: ...efrigerant WARNING Improper installation or attachment of equipment or accessories could result in electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optio...

Страница 11: ...ation of the unit Make sure the area is well ventilated Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmos...

Страница 12: ...nt Do NOT release them directly into the environment Use a vacuum pump to evacuate the installation NOTICE After all the piping has been connected make sure there is no gas leak Use nitrogen to perfor...

Страница 13: ...stallation manual or installer reference guide of your application for more information NOTICE Make sure water quality complies with EU directive 2020 2184 2 1 5 Electrical DANGER RISK OF ELECTROCUTIO...

Страница 14: ...ing of the earth leakage protector CAUTION When connecting the power supply connect the earth cable first before making the current carrying connections When disconnecting the power supply disconnect...

Страница 15: ...ponents box is connected securely Make sure all covers are closed before starting up the unit NOTICE ONLY applicable if the power supply is three phase and the compressor has an ON OFF starting method...

Страница 16: ...tion site 466 WARNING Follow the service space dimensions in this manual for correct installation of the unit Outdoor unit See 7 1 1 Installation site requirements of the outdoor unit 466 Indoor unit...

Страница 17: ...NING SCALDING Mounting the outdoor unit see 7 3 Mounting the outdoor unit 479 WARNING Fixing method of the outdoor unit MUST be in accordance with the instructions from this manual See 7 3 Mounting th...

Страница 18: ...efrigerant circuit may be isolated from other sections caused by components with specific functions e g valves The refrigerant circuit therefore features additional service ports for vacuuming pressur...

Страница 19: ...all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth th...

Страница 20: ...ve a set maximum value This maximum allowable hot water temperature shall be selected according to the applicable legislation CAUTION The disinfection function settings MUST be configured by the insta...

Страница 21: ...default setting If you are unable to find the cause of the problem call your dealer WARNING Prevent hazards due to inadvertent resetting of the thermal cut out power to this appliance MUST NOT be supp...

Страница 22: ...move the accessories from the indoor unit 25 4 3 3 To handle the indoor unit 25 4 1 Overview About the box This chapter describes what you have to do after the boxes with the outdoor and indoor unit a...

Страница 23: ...e left and the handle to the right Pull up both sides of the sling at the same time to prevent disconnection of the sling from the unit 2 1 1 2 While handling the unit Keep both sides of the sling lev...

Страница 24: ...house gases label d Energy label e Unit mounting plate f Bolts nuts washers spring washers and wire clamp 4 3 Indoor unit At delivery the unit MUST be checked for damage Any damage MUST be reported im...

Страница 25: ...ain pan hose k Drain pan hose clamp l Cable fixation for strain relief m Cable tie n Switch box metal insert o Screw for switch box metal insert p Top cover screws q General safety precautions r WLAN...

Страница 26: ...4P678716 1 2022 01 a Screw plug b Assembly wrench c Handle 1 Open the screw plugs on the front and back of the tank 2 Attach the handles horizontally and turn by 360 3 Use the handles to carry the un...

Страница 27: ...outdoor unit 29 5 3 2 Possible options for the outdoor unit 29 5 3 3 Possible options for the indoor unit 29 5 1 Overview About the units and options This chapter contains information about Identifyi...

Страница 28: ...2 2 Identification label Indoor unit Location Model identification Example E HS H B 04 P 30 EF Code Description E European model HS Floor standing refrigerant split unit with integrated pressureless...

Страница 29: ...008D The U beams are installation brackets on which the outdoor unit can be installed It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfal...

Страница 30: ...r sensor KRCS01 1 By default the internal sensor of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat will be used as room temperature sensor As an option the remote indoor sensor...

Страница 31: ...all the optional wireless LAN module BRP069A71 For installation instructions see the installation manual of the WLAN module and the addendum book for optional equipment Universal centralised controlle...

Страница 32: ...kit BIV connector kit EKECBIVCO To make the connection of a bivalent heat source to the bivalent heat exchanger easier you can install a bivalent connector kit For installation instructions see the i...

Страница 33: ...r 56 6 4 5 DHW pump for disinfection 56 6 5 Setting up the energy metering 57 6 5 1 Produced heat 57 6 5 2 Consumed energy 57 6 5 3 Normal kWh rate power supply 58 6 5 4 Preferential kWh rate power su...

Страница 34: ...or thermostat ON OFF signal voltage free contact closed contact thermo ON open contact thermo OFF 6 2 Setting up the space heating cooling system The heat pump system supplies leaving water to heat em...

Страница 35: ...ation Setting Value Unit temperature control 2 9 Code C 07 2 Room thermostat Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface Number of water tempera...

Страница 36: ...thermostat optional equipment EKRTR1 Configuration Setting Value Unit temperature control 2 9 Code C 07 1 External room thermostat Unit operation is decided by the external thermostat Number of water...

Страница 37: ...nvectors For more information see The installation manual of the heat pump convectors The installation manual of the heat pump convector options The addendum book for optional equipment The space heat...

Страница 38: ...ing the electrical wiring to the unit see 9 2 Connections to the outdoor unit 4115 9 3 Connections to the indoor unit 4117 The heat pump convectors are directly connected to the indoor unit A shut off...

Страница 39: ...eat pump system Comfort The combination of the two heat emitter types provides The excellent heating comfort of the underfloor heating The excellent cooling comfort of the heat pump convectors 6 2 2 M...

Страница 40: ...ectly connected to the indoor unit The room temperature of the main room is controlled by the dedicated Human Comfort Interface BRC1HHDA used as room thermostat A thermostatic valve is installed befor...

Страница 41: ...liable operation provide a minimum water flow as described in table To check the water volume and flow rate in 8 5 Preparing water piping 498 The user interface integrated in the indoor unit decides t...

Страница 42: ...al of the heat pump convectors The installation manual of the heat pump convector options The addendum book for optional equipment The user interface integrated in the indoor unit decides the space op...

Страница 43: ...ting A shut off valve to prevent hot water supply when the room has no heating demand A shut off valve to prevent condensation on the floor during cooling operation of the rooms with heat pump convect...

Страница 44: ...hest design temperature in cooling Additional zone Zone with the highest design temperature in heating and the lowest design temperature in cooling CAUTION If there is more than one leaving water zone...

Страница 45: ...r for main zone B C a a f A E D b c g d e h 3 System with hydraulic separator for both zones For this system a direct pump is required for the additional zone B C a a f A E D b c g d e i h A Additiona...

Страница 46: ...request of the room The room temperature is controlled by the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Ensure water circulation is possible in main zone when shut off valves...

Страница 47: ...s 4 4 Code 7 02 1 Dual zone Main additional In case of heat pump convectors External room thermostat for the additional zone 3 A Code C 06 1 1 contact When the used external room thermostat or heat pu...

Страница 48: ...comfort for each individual installation INFORMATION For systems without indirect auxiliary boiler connected to the storage tank it is mandatory to install an electric backup heater to ensure safe ope...

Страница 49: ...determined automatically depending on the outdoor temperature During heating operation of the auxiliary boiler the auxiliary boiler operates to achieve the desired water temperature set via the auxil...

Страница 50: ...unit air thermistor install the outdoor unit in the shadow so that it is NOT influenced or turned ON OFF by direct sunlight Frequent changeover may cause corrosion of the auxiliary boiler Contact the...

Страница 51: ...auxiliary gas boiler must have a fixed setpoint 55 C or a weather dependent setpoint Tmin 0 30 25 20 15 10 5 0 5 20 30 40 50 60 10 Ta C Tmin C Ta Outdoor temperature Tmin Minimum weather dependent se...

Страница 52: ...al on the indoor unit X12M 3 and X12M 4 See 9 3 10 To connect the changeover to external heat source 4133 Configuration Via the user interface configuration wizard Set the use of an indirect bivalent...

Страница 53: ...tank temperature above which all other heat sources are stopped when solar energy is provided See Intelligent tank manager 4227 for more information on configuration 6 3 4 Setting up a solar system v...

Страница 54: ...you can set the storage tank temperature at a higher temperature example 53 C which is then mixed with cold water example 15 C The resulting domestic hot water temperature depends on this setpoint as...

Страница 55: ...e if it is installed and activated However this consumes more energy We recommend to set the desired storage tank temperature below 55 C to avoid using the electrical resistance The higher the outdoor...

Страница 56: ...ect the domestic hot water pump 4130 For installation instructions of the optional recirculation connection see the installation manual of the recirculation kit 141554 Configuration For more informati...

Страница 57: ...interface you can read out the following energy data Produced heat Consumed energy You can read out the energy data For space heating For space cooling For domestic hot water production You can read o...

Страница 58: ...energy Preferred method because of higher accuracy Requires external power meters Setup and configuration When using electrical power meters set the number of pulses kWh for each power meter via the u...

Страница 59: ...of one meter is insufficient The electrical meter cannot easily be installed in the electrical cabinet 230 V and 400 V three phase grids are combined very uncommon because of technical limitations of...

Страница 60: ...Electrical cabinet L1 L2 L3 N Normal kWh rate power supply c Power meter L1 N d Power meter L1 L2 L3 N e Fuse L1 N f Fuse L1 L2 L3 N g Outdoor unit L1 N h Indoor unit L1 N i Backup heater L1 L2 L3 N...

Страница 61: ...imiting the heat pump will reduce performance NOTICE Set a minimum power consumption of 3 6 kW to guarantee Defrost operation Otherwise if defrosting is interrupted several times the heat exchanger wi...

Страница 62: ...ower limitation level Example To limit the maximum power of the entire house lighting domestic appliances space heating a b A B C 1 2 3 4 5 A8P A Outdoor unit B Indoor unit C Energy management system...

Страница 63: ...is limited and turned OFF first The system limits power consumption in the following order 1 Turns OFF the backup heater 2 Limits the outdoor unit 3 Turns OFF the outdoor unit Example If the configur...

Страница 64: ...p an external temperature sensor You can connect one external temperature sensor It measures the indoor or outdoor ambient temperature We recommend to use an external temperature sensor in the followi...

Страница 65: ...e outdoor sensor and the addendum book for optional equipment Configuration Select outdoor sensor 9 B When the power saving functionality of the outdoor unit is active see Power saving function 4226 t...

Страница 66: ...install the outdoor unit 82 7 3 5 To provide drainage 83 7 4 Mounting the indoor unit 85 7 4 1 About mounting the indoor unit 85 7 4 2 Precautions when mounting the indoor unit 85 7 4 3 To install th...

Страница 67: ...tack the units on each other Do NOT hang the unit on a ceiling Strong winds 18 km h blowing against the outdoor unit s air outlet causes short circuit suction of discharge air This may result in deter...

Страница 68: ...ge It is NOT recommended to install the unit in the following places because it may shorten the life of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapo...

Страница 69: ...ille and dispose of it 3 Reattach the screws to the unit 2 4 1 3 a a Suction grille Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up c c d b e a...

Страница 70: ...e following measurements guidelines Maximum refrigerant piping length between indoor unit and outdoor unit 30 m Minimum refrigerant piping length between indoor unit and outdoor unit 3 m Maximum heigh...

Страница 71: ...for R32 units Additionally to the spacing guidelines Because the total refrigerant charge in the system is 1 84 kg the room where you install the indoor unit must also comply with the conditions descr...

Страница 72: ...ilation openings 1 84 kg i e if the piping length is 27 m Living room kitchen garage attic basement storage room 2 3 Technical room i e room that is NEVER occupied by persons 2 3 4 PATTERN 1 PATTERN 2...

Страница 73: ...rant charge mmax kg allowed for room A Contact your dealer Use table 3 in chapter Technical data and dm to calculate the minimum bottom opening area for natural ventilation between room A and room B A...

Страница 74: ...mm from the floor of the unoccupied room Must be Anv min minimum bottom opening area as specified in the table below 50 of the required opening area Anv min must be 200 mm from the floor of the unoccu...

Страница 75: ...closing the units 7 2 1 About opening the units At certain times you have to open the unit Example When connecting the refrigerant piping When connecting the electrical wiring When maintaining or ser...

Страница 76: ...at the tightening torque does NOT exceed 4 1 N m 7 2 4 To open the indoor unit NOTICE The top cover can only be removed if the switch box is lowered Overview a b a User interface panel b Switch box co...

Страница 77: ...To lower the switch box of the indoor unit and remove the top cover During the installation you will need access to the inside of the indoor unit To have easier front access lower the switch box of th...

Страница 78: ...Daikin Altherma 3 R ECH O 4P678716 1 2022 01 1 4 If switch box is opened Disconnect the ground connection from the top cover of the switch box 5 If necessary remove the top cover This is necessary in...

Страница 79: ...the following stages 1 Providing the installation structure 2 Installing the outdoor unit 3 Preventing the unit from falling over 4 Protecting the unit against snow and wind by installing a snow cover...

Страница 80: ...ation with the low sound cover EKLN08A1 different installation instructions apply for the U beams See the installation manual of the low sound cover a b c a Low sound cover b Bottom parts of the low s...

Страница 81: ...m Option 3 On a pedestal with the EKFT008D option kit The EKFT008D option kit is recommended in areas with heavy snowfall 300 6 0 0 1 5 0 1 5 0 mm 300 100 a b 0 mm a Maximum snowfall height b EKFT008D...

Страница 82: ...50 300 250 mm a b c 4 a Maximum snowfall height b EKFT008D option kit c Anti vibration rubber field supply 7 3 4 To install the outdoor unit CAUTION Do NOT remove the protective cardboard before the u...

Страница 83: ...tective cardboard b Instruction sheet 7 3 5 To provide drainage Make sure that condensation water can be evacuated properly Install the unit on a base to make sure that there is proper drainage in ord...

Страница 84: ...ons see the installation manual of the drain pan In short the drain pan must be installed level with a tolerance of 1 at all sides and as follows b a c a Drain pan b U beams c Drain hole insulation 35...

Страница 85: ...he indoor unit 7 4 1 About mounting the indoor unit When You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping Typical workflow Mounting the indoor unit...

Страница 86: ...ollecting in the drain pan must be drained You must connect the drain hoses to an appropriate drain according to the applicable legislation 1 Open the screw plug a a c c b 1 3 2 a Screw plug b Assembl...

Страница 87: ...in Altherma 3 R ECH O 4P678716 1 2022 01 a a Drain pan hose 7 Connect the pressure relief valve to an appropriate drain in accordance with the applicable legislation Ensure that any steam or water tha...

Страница 88: ...harging refrigerant 98 8 4 3 To fix the fluorinated greenhouse gases label 98 8 5 Preparing water piping 98 8 5 1 Water circuit requirements 98 8 5 2 To check the water volume and flow rate 101 8 6 Co...

Страница 89: ...at resistance of at least 120 C Insulation thickness Pipe outer diameter p Insulation inner diameter i Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 15 9 mm 5 8 16 20 mm 13 mm i i t p p If the tempe...

Страница 90: ...32 when adding refrigerant Only use installation tools e g manifold gauge set that are exclusively used for R32 installations to withstand the pressure and to prevent foreign materials e g mineral oil...

Страница 91: ...m 6 4 15 17 8 7 9 1 R 0 4 0 8 2 45 90 2 A 15 9 62 75 19 3 19 7 8 2 4 Pipe bending guidelines Use a pipe bender for bending All pipe bends should be as gentle as possible bending radius should be 30 40...

Страница 92: ...dversely affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure...

Страница 93: ...indicated with the arrow Do NOT damage it After handling the stop valve tighten the stem cap and check for refrigerant leaks Item Tightening torque N m Stem cap liquid side 13 5 16 5 Stem cap gas side...

Страница 94: ...piping to the indoor unit 1 Connect the liquid stop valve from the outdoor unit to the refrigerant liquid connection of the indoor unit a b a Refrigerant liquid connection b Refrigerant gas connection...

Страница 95: ...eparing refrigerant piping 488 NOTICE Use a 2 stage vacuum pump with a non return valve that can evacuate to a gauge pressure of 100 7 kPa 1 007 bar 5 Torr absolute Make sure the pump oil does not flo...

Страница 96: ...rvice port h Valve lids i Gas stop valve j Liquid stop valve 1 Vacuum the system until the pressure on the manifold indicates 0 1 MPa 1 bar 2 Leave as is for 4 5 minutes and check the pressure If the...

Страница 97: ...outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it might be necessary to connect electrical wiring...

Страница 98: ...el is delivered with the unit see accessories peel off the applicable language and stick it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total...

Страница 99: ...or connecting the water circuit Inappropriate tooling will cause damage to the pipes Closed circuit Use the indoor unit ONLY in a closed water system Using the system in an open water system will lead...

Страница 100: ...n hose to the drain 486 Air vents Provide air vents at all high points of the system which must also be easily accessible for servicing An automatic air purge is provided in the indoor unit Check that...

Страница 101: ...sy filling and draining of the storage tank we recommend to install a shut off valve See option kit Fill and drain kit 165215 Thermostatic mixing valves In accordance with the applicable legislation i...

Страница 102: ...e in the installation is guaranteed in all conditions Minimum required flow rate 12 l min NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it...

Страница 103: ...6 2 Precautions when connecting the water piping INFORMATION Also read the precautions and requirements in the following chapters 2 General safety precautions 410 8 5 Preparing water piping 498 8 6 3...

Страница 104: ...avoid damage apply the necessary countertorque with a suitable tool 2 7 mm 1 3 4 Connect the domestic hot water in and out pipes to the indoor unit Do NOT exceed the maximum tightening torque Thread s...

Страница 105: ...lves on the space heating cooling water in and out connections as well as on the domestic cold water in and domestic hot water out connections These shut off valves are field supplied NOTICE To avoid...

Страница 106: ...tc connected to the tank is subjected to this high pressure To prevent this a pressure relief valve needs to be installed The overpressure prevention depends on the correct operation of the field inst...

Страница 107: ...cording to the instructions see To purge the air out of the unit with the manual air vent valves 4243 3 Open the water tap 4 Open fill and drain valve and monitor the manometer 5 Fill the system with...

Страница 108: ...ng until no more air is vented from the taps 4 Check for water leaks The bivalent heat exchanger only for some models 5 Fill the bivalent heat exchanger with water by connecting the bivalent heating c...

Страница 109: ...led drainback solar kit option 1 Combine the fill and drain kit option with the drainback solar kit option to fill the storage tank 2 Connect the hose with non return valve to the fill and drain kit F...

Страница 110: ...37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the insulation materials should be...

Страница 111: ...t the shut off valve 128 9 3 6 To connect the electricity meters 129 9 3 7 To connect the domestic hot water pump 130 9 3 8 To connect the alarm output 131 9 3 9 To connect the space cooling heating O...

Страница 112: ...OT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause ov...

Страница 113: ...ning torque N m M4 X1M 1 2 1 5 M4 earth Indoor unit Item Tightening torque N m M4 X1M 1 2 M4 X12M X15M 0 88 10 Indoor unit BUH option Item Tightening torque N m M4 X6M 3V 6V 2 45 10 M4 X6M 9W 1 2 9 1...

Страница 114: ...nt the outdoor unit compressor will NOT operate The wiring to the unit is different depending on whether the power supply is interrupted or NOT 9 1 5 Overview of electrical connections except external...

Страница 115: ...equency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cable Minimum cable section of 1 5 mm and applicable for 230 V Recommended field fuse 20 A 25 A 16 A Earth leakage circ...

Страница 116: ...ing cover 1 1 2 3 Strip insulation 20 mm from the wires a b a Strip wire end to this point b An excessive strip length may cause electrical shock or leakage 4 Connect the interconnection cable and pow...

Страница 117: ...oor unit Item Description Power supply main See 9 3 2 To connect the main power supply 4122 Power supply backup heater See 9 3 3 To connect the backup heater power supply 4124 Backup heater See 9 3 4...

Страница 118: ...ee 9 3 15 To connect the solar input 4143 DHW output See 9 3 16 To connect the DHW output 4143 Room thermostat wired or wireless See below table Wires 0 75 mm Maximum running current 100 mA For the ma...

Страница 119: ...ernal sensor Room 1 7 Room sensor offset Human Comfort Interface See Installation and operation manual of the Human Comfort Interface Addendum book for optional equipment Wires 2 0 75 1 25 mm Maximum...

Страница 120: ...ing base unit to the outdoor unit For cooling heating operation you also need to implement a relay field supply see addendum book for optional equipment 9 3 1 To connect the electrical wiring to the i...

Страница 121: ...tion Installer reference guide 121 ERGA04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 All cables which will be connected to the switch box of the ECH2O must be f...

Страница 122: ...hile cables are connected to one of the terminals Otherwise the cables could be too short X12M 9 3 2 To connect the main power supply 1 Open the following see 7 2 4 To open the indoor unit 476 1 User...

Страница 123: ...le b Power supply indoor unit In case of preferential kWh rate power supply Interconnection cable Wires 3 GND 1 5 mm Power supply indoor unit Wires 1N GND Maximum running current 6 3 A Preferential kW...

Страница 124: ...ply contact 3 Fix the cable with cable ties to the cable tie mountings General information see 9 3 1 To connect the electrical wiring to the indoor unit 4120 9 3 3 To connect the backup heater power s...

Страница 125: ...13 A a Electrical equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage sy...

Страница 126: ...P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 X6M SWB2 3V 3V 1N 230 V 6V 6V 1N 230 V 9W 3N 400 V 1N 50 Hz 230 V AC SWB2 Q1DI N L 1 2 3 4 F1B 20A I I X6M Model power supply Connections to backu...

Страница 127: ...V AC SWB2 Q1DI L1 L2 L3 N X6M 1 2 3 4 5 6 F1B 20A I I I F1B Overcurrent fuse field supply Recommended fuse tripping class C Q1DI Earth leakage circuit breaker field supply SWB Switch box X6M Terminal...

Страница 128: ...INFORMATION Shut off valve usage example In case of one LWT zone and a combination of underfloor heating and heat pump convectors install a shut off valve before the underfloor heating to prevent cond...

Страница 129: ...electricity meters Wires 2 per meter 0 75 mm Electricity meters 12 V DC pulse detection voltage supplied by PCB 9 A Energy metering INFORMATION In case of an electricity meter with transistor output...

Страница 130: ...3 1 To connect the electrical wiring to the indoor unit 4120 9 3 7 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW...

Страница 131: ...neral information see 9 3 1 To connect the electrical wiring to the indoor unit 4120 9 3 8 To connect the alarm output Wires 2 0 75 mm Maximum load 0 3 A 230 V AC Maximum load 1 A 5 V DC 9 D Alarm out...

Страница 132: ...1 To connect the electrical wiring to the indoor unit 4120 9 3 9 To connect the space cooling heating ON OFF output INFORMATION Cooling is only applicable in case of reversible models Wires 2 0 75 mm...

Страница 133: ...he indoor unit 4120 9 3 10 To connect the changeover to external heat source INFORMATION Bivalent is only possible in case of 1 leaving water temperature zone with room thermostat control OR external...

Страница 134: ...ie mountings General information see 9 3 1 To connect the electrical wiring to the indoor unit 4120 9 3 11 To connect the power consumption digital inputs Wires 2 per input signal 0 75 mm Power limita...

Страница 135: ...2 01 1 2 3 3 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below A B B A A8P M 1 0 8 X 1 2 3 4 5 1 2 4 5 S 6 S S 7 S S 8 S S 9 S 3 a 4 Fi...

Страница 136: ...d of 15 V DC 10 mA 9 8 1 3 Benefit kWh power supply Safety thermostat 1 Open the following see 7 2 4 To open the indoor unit 476 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top co...

Страница 137: ...fety thermostat after it is installed Without configuration the unit will ignore the safety thermostat contact 9 3 13 To connect a Smart Grid This topic describes 2 possible ways to connect the indoor...

Страница 138: ...6 5 S S 10 4 3 X 5M 1 S S 4 10 9 a 2 1 a Jumper factory mounted If you also connect a safety thermostat Q4L replace the jumper with the safety thermostat wires S4S Smart Grid pulse meter 1 S10S Low vo...

Страница 139: ...6 3 4 K1A L N L N STEP 3 a b c d e f STEP 1 STEP 2 A1 A2 25 24 25 23 X1 M 2 K2A A1 A2 2 1 STEP 1 Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 Hig...

Страница 140: ...allation Installer reference guide 140 ERGA04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 X M 10 K1A X10M K2A 3 Install the components of the Smart Grid relay ki...

Страница 141: ...0 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 K1A K2A X15M X12M X 5M M X 1 12 3 4 5 6 X15M 3 X12M 23 X12M 24 X12M 25 X12M 25 X15M 5 X15M 4 X15M 6 23 24 25 4 Connect the low voltage wiring as fol...

Страница 142: ...1 24 25 X M 12 25 X M 12 24 X M 12 25 X M 12 23 1 2 23 L2 L1 N N 6 Fix the cable with cable ties to the cable tie mountings General information see 9 3 1 To connect the electrical wiring to the indoor...

Страница 143: ...ndoor unit 476 1 User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the solar input cable as shown in the illustration below A A B B 13 14 X 5M 1 13 14 Solar input 3 Fi...

Страница 144: ...User interface panel 1 3 4 2 2 Switch box 3 Switch box cover 4 Top cover 2 Connect the DHW signal cable as shown in the illustration below A B X 2M 1 11 12 A B DHW output Max load 0 3 A 230 V AC 12 1...

Страница 145: ...unit installation NOTICE It is recommended that the refrigerant piping between indoor and outdoor unit is installed in a ducting or the refrigerant piping is wrapped with finishing tape 1 Insulate and...

Страница 146: ...ent curves 164 11 5 Settings menu 166 11 5 1 Malfunctioning 166 11 5 2 Room 166 11 5 3 Main zone 170 11 5 4 Additional zone 180 11 5 5 Space heating cooling 185 11 5 6 Tank 194 11 5 7 User settings 19...

Страница 147: ...ferent methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings v...

Страница 148: ...ttings can be configured via the menu structure If for any reason it is required to change a setting using the overview settings then the overview settings can be accessed as follows 1 Set the user pe...

Страница 149: ...CCAB4 kit is required 1 Connect the USB connector of the cable to your PC 2 Connect the plug of the cable to X10A on A1P of the switch box of the indoor unit A1P X10A 3 Pay special attention to the po...

Страница 150: ...umber of zones 4 4 11 5 5 Space heating cooling 4185 Glycol Filled system overview field setting E 0D 11 5 9 Installer settings 4206 Solar 9 2 4 11 5 9 Installer settings 4206 Backup heater Voltage 9...

Страница 151: ...Heating WD curve 3 5 if applicable Cooling WD curve 3 6 if applicable Schedule 3 1 WD curve type 3 C read only Tank Heat up mode 5 6 11 5 6 Tank 4194 Hysteresis 5 9 11 3 Possible screens 11 3 1 Possib...

Страница 152: ...ough the list of the main menu Go to the main menu screen Enable disable breadcrumbs Item Description a Domestic hot water a1 Domestic hot water a2 55 Measured tank temperature a b Disinfection Powerf...

Страница 153: ...ss No room thermostat installed or set Unit operation is decided based on the leaving water temperature regardless of the actual room temperature and or heating demand of the room i2 Installed heat em...

Страница 154: ...list Enter the submenu Enable disable breadcrumbs Submenu Description 0 or Malfunctioning Restriction Only displayed if a malfunction occurs See 15 4 1 To display the help text in case of a malfunctio...

Страница 155: ...taller Perform tests and maintenance B User profile Change the active user profile C Operation Turn heating cooling functionality and domestic hot water preparation on or off D Wireless gateway Restri...

Страница 156: ...Description Minimum temperature limit a1 Fixed by the unit a2 Restricted by the installer Maximum temperature limit b1 Fixed by the unit b2 Restricted by the installer Current temperature c Measured b...

Страница 157: ...able if room thermostat control is active If leaving water temperature control is active you can program the main zone schedule instead 1 Go to the schedule 2 optional Clear the content of the whole w...

Страница 158: ...ser defined 1 2 Select Edit Delete Edit Copy 3 Use the left dial to select an entry and edit the entry with the right dial You can program up to 6 actions each day On the bar a high temperature has a...

Страница 159: ...User defined 1 2 Select Copy Delete Edit Copy Result Next to the copied day C is displayed 3 Select Tuesday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 4 Select Paste Delete Edit Copy Paste Result M...

Страница 160: ...ser defined 1 C To rename the schedule 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Rename Delete Rename Select 3 optional To delete the current schedu...

Страница 161: ...rve To be able to compensate for differences in temperature the unit relies on its weather dependent curve This curve defines how much the temperature of the tank or leaving water must be at different...

Страница 162: ...m changes and proceed 11 4 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the...

Страница 163: ...mperature at X1 is unequally higher than the preferred temperature at X2 When offset is changed the new preferred temperature at X1 is equally higher as the preferred temperature at X2 c Slope d Offse...

Страница 164: ...point mode WD heating fixed cooling OR Weather dependent Main zone Cooling 2 4 Main zone Setpoint mode Weather dependent Additional zone Heating 3 4 Additional zone Setpoint mode WD heating fixed cool...

Страница 165: ...he maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve...

Страница 166: ...eration User profile Main zone 11 5 2 Room Overview The following items are listed in the submenu 1 Room Main zone Malfunctioning Operation Additional zone 1 Room Setpoint screen 1 1 Schedule 1 2 Heat...

Страница 167: ...al room thermostat and C 2 Space heating cooling Off or if 2 9 Control Leaving water In the above cases Antifrost will heat the space heating water to a reduced setpoint when the outdoor temperature i...

Страница 168: ...on mode Heating The unit will supply leaving water to the heat emitters to heat up the room according to normal logic Space heating cooling On and Operation mode Cooling There is no room frost protect...

Страница 169: ...nit will supply leaving water to the heat emitters to heat up the room again Code Description 1 4 1 2 06 Activation 0 No Antifrost functionality is OFF 1 Yes Antifrost functionality is on 1 4 2 2 05 R...

Страница 170: ...et Human Comfort Interface BRC1HHDA used as room thermostat Offset on the actual room temperature measured by the Human Comfort Interface 5 C 5 C step 0 5 C 1 7 2 09 Room sensor offset external room s...

Страница 171: ...nt screen 2 Main zone See 11 3 5 Setpoint screen 4155 Schedule Indicate if the temperature of the leaving water is defined according to a schedule or not Influence of the LWT setpoint mode 2 4 is as f...

Страница 172: ...perature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient temperature Code Desc...

Страница 173: ...mperature 40 C 5 C 1 01 High outdoor ambient temperature 10 C 25 C 1 02 Desired leaving water temperature when the outdoor temperature equals or drops below the low ambient temperature 9 01 C 9 00 C N...

Страница 174: ...d water is required 1 09 Desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature 9 03 C 9 02 C Note This value should be lower than 1 08 as fo...

Страница 175: ...ant that in heating the zone with the lowest water temperature is configured as the main zone and the zone with the highest water temperature is configured as the additional zone NOTICE If there are 2...

Страница 176: ...esign and selection of the heat emitters The desired leaving water temperature is the result of several settings preset values shift values weather dependent curves modulation As a result too high or...

Страница 177: ...om thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 E...

Страница 178: ...tween leaving water temperature setpoint and inlet temperature at startup INFORMATION If the main zone or the additional zone has a heating demand and this zone is equipped with radiators then the tar...

Страница 179: ...can only be read out on the user interface 2 C 2 8 06 Max modulation 0 C 10 C This is the temperature value by which the desired leaving water temperature is increased or decreased INFORMATION When l...

Страница 180: ...or cooling demand INFORMATION The setting F 0B is only valid when there is a thermostat or external room thermostat request setting NOT in case of leaving water temperature setting During cooling If F...

Страница 181: ...mperature for the additional zone via setpoint screen 3 Additional zone See 11 3 5 Setpoint screen 4155 Schedule Indicates if the desired leaving water temperature is according to a schedule See 11 5...

Страница 182: ...tdoor temperature 0 03 Low outdoor ambient temperature 40 C 5 C 0 02 High outdoor ambient temperature 10 C 25 C 0 01 Desired leaving water temperature when the outdoor temperature equals or drops belo...

Страница 183: ...mperatures less cold water is required 0 04 Desired leaving water temperature when the outdoor temperature equals or rises above the high ambient temperature 9 07 C 9 08 C Note This value should be lo...

Страница 184: ...55 C 3 8 3 9 07 Cooling minimum 5 C 18 C 3 8 4 9 08 Cooling maximum 18 C 22 C Control The control type for the additional zone is read only It is determined by the control type of the main zone See 1...

Страница 185: ...set see 11 4 3 Slope offset curve 4162 In 2 E WD curve type you can choose which method you want to use In 3 C WD curve type the chosen method is shown read only same value as in 2 E Code Description...

Страница 186: ...the unit is in heating mode the icon is shown When the unit is in cooling mode the icon is shown The status indicator shows if the unit is currently in operation When the unit is not in operation the...

Страница 187: ...veraged If the outdoor temperature drops the operation mode will switch to heating and vice versa If the outdoor temperature is between the Space heating off temperature and the Space cooling off temp...

Страница 188: ...subtracted by the offset value thus 24 4 20 C Guard timer to prevent too frequent changing from heating to cooling and vice versa Code Description Changeover settings related to the indoor temperatur...

Страница 189: ...ixing station NOTICE NOT configuring the system in the following way can cause damage to the heat emitters If there are 2 zones it is important that in heating the zone with the lowest water temperatu...

Страница 190: ...ion Remark Continuous pump operation requires more energy than sample or request pump operation a b c d b c a Space heating cooling control b Off c On d Pump operation 4 5 F 0D 1 Sample The pump is ON...

Страница 191: ...ing only Pump limitation The pump speed limitation defines the maximum pump speed In normal conditions the default setting should NOT be modified The pump speed limitation will be overruled when the f...

Страница 192: ...pump speed limitation is applicable When there is heating output the pump speed is only determined by delta T in relation to the required capacity With this limitation range delta T is possible and t...

Страница 193: ...p operation 0 Disabled if outdoor temperature is higher than 4 02 or lower than F 01 depending on heating cooling operation mode 1 Possible at all outdoor temperatures Increase around 0 C Use this set...

Страница 194: ...e heating cooling Additional zone Information 5 Tank Setpoint screen 5 1 Powerful operation 5 5 Schedule 5 6 Heat up mode 5 7 Disinfection 5 8 Maximum 5 9 Hysteresis 5 B Setpoint mode 5 C WD curve 5 D...

Страница 195: ...ting cooling interruptions will happen Schedule You can set the tank temperature schedule using the schedule screen For more information about this screen see 11 3 7 Schedule screen Example 4157 Heat...

Страница 196: ...in field setting 2 03 after a disinfection operation When the high domestic hot water temperature can be a potential risk for human injuries a mixing valve field supply shall be installed at the dome...

Страница 197: ...mit the temperatures at the hot water taps INFORMATION During disinfection of the water inside the domestic hot water heat exchanger coil by periodically heating the storage tank to a specific tempera...

Страница 198: ...the high ambient temperature 35 C 6 0E C Margin In domestic hot water operation the following hysteresis value can be set for the heat pump operation Code Description 5 D 6 01 The temperature differen...

Страница 199: ...set on the user interface t Time INFORMATION The maximum heat pump temperature depends on the ambient temperature For more information see the operation range WD curve When weather dependent operation...

Страница 200: ...settings Time date once the unit is initialised Holiday About holiday mode During your holiday you can use the holiday mode to deviate from your normal schedules without having to change them While ho...

Страница 201: ...level until the next scheduled action Use and program a quiet mode schedule INFORMATION If the outdoor temperature is below zero we recommend to NOT use the most quiet level To check if quiet mode is...

Страница 202: ...alent 4222 Code Description 7 5 1 N A Electricity price High 7 5 2 N A Electricity price Medium 7 5 3 N A Electricity price Low 7 6 N A Gas price INFORMATION Electricity price can only be set when biv...

Страница 203: ...hough the running cost can increase the total operation cost taking into account the reimbursement will be optimized NOTICE Make sure to modify the setting of the energy prices at the end of the incen...

Страница 204: ...Reset 8 B Piping diagram Energy data Read out information about energy flows to check and optimize your energy consumption You can read out electricity input and produced heat divided into space heati...

Страница 205: ...us real time sensor and actuator information within the piping layout This allows a check of the system at one glance R3T 3 R4T 3 3 3 P 3 V 3 R1T 3 R2T 3 R7T 3 R5T 3 R6T 3 a1 a3 a4 b1 2 a 3 b b5 b4 c1...

Страница 206: ...ed electricity and consumed gas energy flow diagram 8 2 Malfunction history Malfunction history 8 3 Dealer information Contact helpdesk number 8 4 Sensors Room tank or domestic hot water outside and l...

Страница 207: ...defrost 9 I Overview field settings 9 N Export MMI settings 9 O Intelligent tank management 9 P Bizone kit Configuration wizard After first power ON of the system the user interface will guide you us...

Страница 208: ...schedule to determine when to turn on and off the pump When turned on the pump runs and makes sure hot water is instantly available at the tap To save energy only turn on the pump during periods of th...

Страница 209: ...acity of the second step in emergency Code Description 9 3 3 4 0A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked...

Страница 210: ...ater configuration Maximum capacity Code Description 9 3 9 4 07 Maximum capacity that should be delivered by the backup heater Range 1 kW 3 kW Step 1 kW Equilibrium Code Description 9 3 6 5 00 Equilib...

Страница 211: ...nual interaction When Emergency is set to Automatic and a heat pump failure occurs the backup heater or boiler automatically takes over the domestic hot water production and space heating When Emergen...

Страница 212: ...es NOT confirm emergency operation INFORMATION If the boiler is connected as auxiliary heat source to the tank via bivalent coil or via drain back connection the boiler and NOT the backup heater opera...

Страница 213: ...heated with the backup heater If an auxiliary boiler is connected to the tank At ambient temperatures below 5 03 only the boiler is used for domestic hot water heating 9 6 2 5 03 Priority temperature...

Страница 214: ...stops even when the target domestic hot water temperature is NOT reached The actual maximum running time also depends on setting 8 04 When Control Room thermostat This preset value is only taken into...

Страница 215: ...ed on In case the space heating cooling request is OFF and the tank temperature setpoint is reached the unit can choose to buffer energy from the photovoltaic panels in the room only in case of room t...

Страница 216: ...T set to Smart grid Allow pump 0 No Pump is forced off 1 Yes No limitation 9 8 4 D 01 Connection to a Benefit kWh power supply or a Smart grid 0 No The outdoor unit is connected to a normal power supp...

Страница 217: ...mart Grid operation modes 9 8 6 N A Restriction Only applicable if 9 8 4 Smart grid To set if electrical heaters are allowed Allow electrical heaters No Yes 9 8 7 N A Restriction Only applicable in ca...

Страница 218: ...tting Limit setting kW This prevents overconsumption and thus requiring the use of power from the grid Power consumption control Power consumption control See 6 Application guidelines 4 33 for detaile...

Страница 219: ...LED 4 08 0 0 None Backup heater and booster heater can operate simultaneously 1 Booster heater The booster heater is prioritised 2 Backup heater The backup heater is prioritised Power consumption cont...

Страница 220: ...rent from the permanent power limitation which is always changeable BBR16 activation Code Description 9 9 F 7 07 BBR16 activation 0 disabled 1 enabled BBR16 power limit Code Description 9 9 G N A BBR1...

Страница 221: ...of the indoor unit measuring the indoor temperature The temperature sensor in the dedicated Human Comfort Interface is NOT used anymore Remark This value has only meaning in room thermostat control Ex...

Страница 222: ...liary boiler is installed directly in the space heating circuit 2 Indirect DHW Set this value in case that the auxiliary boiler is connected to the storage tank and the heat generated by the auxiliary...

Страница 223: ...ng and the boiler is activated to support in case of capacity shortage The switch over between the heat pump system parallel bivalent operation if applicable and the auxiliary boiler is based on the f...

Страница 224: ...3 and LWT 55 C NOTICE Make sure to set the value of 5 01 at least 1 C higher than the value of C 03 For DHW heating switch over The heat pump system calculates a value Tlim based on outdoor temperatur...

Страница 225: ...Very high 1 High 2 Medium 3 Low 4 Very low Alarm output Alarm output Code Description 9 D C 09 Alarm output Indicates the logic of the alarm output during malfunctioning 0 Abnormal The alarm output w...

Страница 226: ...ll depends on the ambient temperature compressor conditions and minimum internal timers To enable the power saving function setting E 08 needs to be enabled on the user interface Code Description 9 F...

Страница 227: ...ng 4148 Export MMI settings About exporting the configuration settings Export the configuration settings of the unit to a USB memory stick via the MMI the user interface of the indoor unit When troubl...

Страница 228: ...ort while boiler may or may not operate This applies only when tank energy is allowed to be used for space heating C 02 3 and the auxiliary boiler is deemed more efficient by the efficiency calculatio...

Страница 229: ...HPSH Space heating by heat pump operation Ttank Storage tank temperature TankSH Space heating by tank heating support Tset In this example Tank setpoint may differ depending on space heating setpoint...

Страница 230: ...demand Enabling the function for a too small boiler may lead to undesirable and potentially damaging on off switching behavior of the heat pump Continuous heating The continuous heating function allo...

Страница 231: ...lar energy is provided and storage tank temperature is above limit temperature heat pump and boiler are switched off 1 No Heat pump and boiler can operate also while solar energy is provided Bizone ki...

Страница 232: ...aulic separator with direct pump d c b a a Indoor unit b Mixing station c Hydraulic separator d Direct pump Additional zone pump fixed PWM The speed of the additional zone pump can be fixed with this...

Страница 233: ...0 300 sec default 125 11 5 10 Commissioning Overview The following items are listed in the submenu A Commissioning User profile Installer settings Information Operation A Commissioning A 1 Operation t...

Страница 234: ...of the two needed connects the system to the internet The user you can then control the system via the Daikin Residential Controller app This needs the following components in case of WLAN cartridge b...

Страница 235: ...scription D 1 N A Enable AP mode No Yes Reboot Reboot the WLAN cartridge module Code Description D 2 N A Reboot the gateway Back OK WPS Connect the WLAN cartridge module to the router Code Description...

Страница 236: ...1 Configuration Installer reference guide 236 ERGA04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 Code Description D 6 N A Cloud connection Not connected Connecte...

Страница 237: ...Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule Level 7 5 Electricity price High Medium Low Schedule 5 Tank Powerful operation...

Страница 238: ...ly Smart grid operation mode Allow electrical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2...

Страница 239: ...tions such as room antifrost The unit automatically runs these functions when necessary During installation or service this behaviour is undesired Therefore the protective functions can be disabled At...

Страница 240: ...the result NOTICE ALWAYS complete the refrigerant piping of the unit before operating If NOT the compressor will break 12 3 Checklist before commissioning 1 After the installation of the unit check th...

Страница 241: ...relief valve purges water when opened Clean water MUST come out The minimum water volume is guaranteed in all conditions See To check the water volume and flow rate in 8 5 Preparing water piping 498 T...

Страница 242: ...t you can start the air purge procedure NOTICE For safety reasons the air purge function does not work for very high storage tank temperatures Manual or automatic There are 2 modes for purging air Man...

Страница 243: ...on automatically stops after 30 minutes INFORMATION For best results air purge each loop separately To purge the air out of the unit with the manual air vent valves c a b a b c Manual air vent valve 1...

Страница 244: ...aller See To change the user permission level 4147 2 Go to A 3 Commissioning Air purge 3 In the menu set Type Automatic 4 Select Start air purge 5 Select OK to confirm Result The air purge starts It s...

Страница 245: ...re information 12 4 4 Actuator test run Purpose Perform an actuator test run to confirm the operation of the different actuators For example when you select Pump a test run of the pump will start To p...

Страница 246: ...f the building NOTICE The installer is responsible for contacting the screed manufacturer for the maximum allowed water temperature to avoid cracking the screed programming the underfloor heating scre...

Страница 247: ...he left dial to save the schedule To perform an underfloor heating screed dryout INFORMATION If Emergency is set to Manual 9 5 0 and the unit is triggered to start emergency operation the user interfa...

Страница 248: ...matically when done 5 To stop the underfloor heating screed dryout manually 1 Open the menu and go to Stop UFH screed dryout 2 Select OK to confirm To read out the status of an underfloor heating scre...

Страница 249: ...is stopped Read out UFH screed dryout status When the program is stopped due to an error an operation switch off or a power failure you can read out the underfloor heating screed dryout status 1 Go to...

Страница 250: ...taller setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can...

Страница 251: ...performing maintenance at least once a year However applicable legislation might require shorter maintenance intervals In this chapter 14 1 Overview Maintenance and service 251 14 2 Maintenance safety...

Страница 252: ...re Space heating cooling circuit Keep water pressure above 1 bar If it is lower add water Magnetic filter dirt separator NOTICE The optional magnetic filter dirt separator requires yearly maintenance...

Страница 253: ...o be replaced by the manufacturer its service agent or similarly qualified persons Storage tank water level Carry out a visual check of the water level inside the storage tank 1 Open the following see...

Страница 254: ...e relief valve leaks 258 15 3 9 Symptom The space is NOT sufficiently heated at low outdoor temperatures 259 15 3 10 Symptom Tank disinfection function is NOT completed correctly AH error 260 15 4 Sol...

Страница 255: ...that All shut off valves of the water circuit are completely open The water filter is clean Clean if necessary There is no air in the system Purge air if necessary You can purge air manually see To p...

Страница 256: ...or can start If the backup heater doesn t start either check and make sure that The power supply to the backup heater is correctly wired The backup heater thermal protector is NOT activated The backup...

Страница 257: ...from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is s...

Страница 258: ...expansion vessel is closed Open the valve The water circuit head is too high The water circuit head is the difference in height between the indoor unit and the highest point of the water circuit If t...

Страница 259: ...cted directly to the tank and space heating support is activated make sure that the boiler is operating correctly the boiler capacity is sufficient The backup heater equilibrium temperature has not be...

Страница 260: ...d off during disinfection Do NOT stop tank operation during disinfection 15 4 Solving problems based on error codes If the unit runs into a problem the user interface displays an error code It is impo...

Страница 261: ...ality indoor unit 81 07 Mixed leaving water temperature after the tank thermistor abnormality DLWA2 89 01 Heat exchanger freeze up protection activated during defrost error 89 02 Heat exchanger freeze...

Страница 262: ...Compressor startup defect E7 00 OU Malfunction of outdoor unit fan motor E8 00 OU Power input overvoltage E9 00 Malfunction of electronic expansion valve EA 00 OU Cool heat switchover problem EC 00 Ab...

Страница 263: ...re rise problem L4 00 OU Malfunction of inverter radiating fin temperature rise L5 00 OU Inverter instantaneous overcurrent DC L8 00 Malfunction triggered by a thermal protection in the inverter PCB L...

Страница 264: ...to domestic hot water tapping following actions are recommended It is recommended to program the start up of the disinfection function at least 4 hours later than the last expected large hot water tap...

Страница 265: ...n the storage tank with a connected pressureless solar system 267 16 1 To drain the storage tank DANGER RISK OF BURNING SCALDING The water in the storage tank and all the connected piping can be very...

Страница 266: ...ltherma 3 R ECH O 4P678716 1 2022 01 a b 2 1 a Connection cover b Screw plug 3 Insert the screw plug into the fill and drain kit and secure with the clip contained in the option kit b 1 2 a b a b a Fi...

Страница 267: ...ew plug with drain connection a b 1 2 3 c d a Screw plug b Sealing plug c Screw plug with drain connection optional fill and drain kit d Screw plug with drain connection spillover connector 16 1 2 To...

Страница 268: ...04 08EAV3 V3A V37 EHSH X B 04 08P30 50EF Daikin Altherma 3 R ECH O 4P678716 1 2022 01 1 a a b c 3 4 2 5 a Clip b Sealing plug c Fill and drain kit 5 Open the valve of the fill and drain kit 6 Switch t...

Страница 269: ...natural ventilation indoor unit 280 17 8 ESP curve Indoor unit 282 17 9 Name plate Indoor unit 282 17 1 Piping diagram Outdoor unit R2T 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 12 7 CuT 12 7 C...

Страница 270: ...quid refrigerant IN cooling mode evaporator c3 Gas refrigerant OUT cooling mode evaporator c4 Liquid refrigerant OUT heating mode condenser d1 Water IN from bivalent heat source screw connection 1 d2...

Страница 271: ...lation Notes Notes Connection X1M Main terminal Earth wiring Field supply Option Switch box PCB Wiring depending on model Protective earth Field wire NOTES 1 When operating do not short circuit protec...

Страница 272: ...ing power supply Q1L Thermal protector Q1DI Earth leakage circuit breaker Q Insulated gate bipolar transistor IGBT R1T Thermistor air R2T Thermistor heat exchanger R3T Thermistor discharge RTH2 Resist...

Страница 273: ...Not mounted in switch box Wiring depending on model PCB Backup heater power supply Backup heater power supply 3V 1N 230 V 3 kW 3V 1N 230 V 3 kW 6V 1N 230 V 6 kW 6V 1N 230 V 6 kW 6WN 9WN 3N 400 V 6 9...

Страница 274: ...A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A8P Demand PCB A11P MMI user interface of the indoor unit Main PCB A14P PCB of the dedicated Human Comfort Interface BRC1HHD...

Страница 275: ...supply Translation of text on wiring diagram English Translation 1 Main power connection 1 Main power connection Outdoor unit Outdoor unit SWB1 Switch box 2 User interface 2 User interface Only for re...

Страница 276: ...Gas meter Gas meter Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Note outputs can be taken from terminal positions X12M 17 L 18 N and X12M 17...

Страница 277: ...s and heat pump convector 5 External On OFF thermostats and heat pump convector Additional LWT zone Additional leaving water temperature zone Main LWT zone Main leaving water temperature zone Only for...

Страница 278: ...4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2 core OPTIONAL PART External room thermostat Heat pump convector main and or additional zone main X12M...

Страница 279: ...charge allowed in a room indoor unit Aroom m2 Maximum refrigerant charge in a room mmax kg H 600 mm 1 0 138 2 0 276 3 0 414 4 0 553 5 0 691 6 0 829 7 0 907 8 0 970 9 1 028 10 1 084 11 1 137 12 1 187...

Страница 280: ...RMATION For HPSU models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate mc values i e when mc is between two values from th...

Страница 281: ...For floorstanding models the value of Installation height H is considered 600 mm to comply to IEC 60335 2 40 2013 A1 2016 Clause GG2 For intermediate dm values i e when dm is between two dm values fr...

Страница 282: ...Notes Selecting a flow outside the operating area can damage the unit or cause the unit to malfunction See also the minimum and maximum allowed water flow range in the technical specifications Make su...

Страница 283: ...ECH O 4P678716 1 2022 01 q Refrigerant circuit r Max operating pressure refrigerant circuit s Total refrigerant charge for information see installation instructions for the outdoor heat pump unit t At...

Страница 284: ...in product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenanc...

Страница 285: ...EF EHSX04P30EF EHSXB04P30EF EHSX04P50EF EHSXB04P50EF EHSH08P30EF EHSHB08P30EF EHSX08P30EF EHSXB08P30EF EHSH08P50EF EHSHB08P50EF EHSX08P50EF EHSXB08P50EF Notes 1 300 Tank 2 500 Tank 3 X 4 H 5 B 6 EKECB...

Страница 286: ...ving water 1 External room thermostat 2 Room thermostat 2 A C 05 R W 1 1 contact 2 2 contacts Delta T 2 B 1 1 0B R W 2 0C 2 R O 2 0C 2 3 10 C step 1 C 2 0C 2 Radiator 5 C 2 0C 2 Radiator 10 C 2 B 2 1...

Страница 287: ...C Space heating cooling 4 4 7 02 R W 0 Single zone 1 Dual zone 4 5 F 0D R W 0 Continuous 1 Sample 2 Request 4 6 E 02 R W 1 R O 2 0 Reversible 1 1 Heating only 2 4 7 9 0D R W 0 8 step 1 0 No limitation...

Страница 288: ...00 990 kWh 1 kWh 7 5 3 R W 0 00 990 kWh 1 kWh User settings 7 6 R W 0 00 990 kWh 0 00 290 MBtu 1 0 kWh Installer settings Configuration wizard System 9 1 3 2 E 03 R O 4 5 6 R W 7 0 no heater 7 2 3V 4...

Страница 289: ...R W 25 43 C step 1 C 35 C 9 1 A 0 07 R W 10 25 C step 1 C 20 C Tank 9 1 B 1 6 0D R W 0 Reheat only 3 scheduled reheat 9 1 B 2 6 0A R W 30 6 0E C step 1 C 60 C 9 1 B 3 6 0B R W 30 min 50 6 0E C step 1...

Страница 290: ...C 9 6 4 8 02 R W 0 10 hour step 0 5 hour 0 5 hour 9 6 5 8 00 R W 0 20 min step 1 min 1 min 9 6 6 8 01 R W 5 95 min step 5 min 30 min 9 6 7 8 04 R W 0 95 min step 5 min 95 min Installer settings 9 7 4...

Страница 291: ...ormal 1 Normal 9 E 3 00 R W 0 manual 1 automatic 9 F E 08 R W 0 No 1 Yes 9 G R W 0 No 1 Yes Overview field settings 9 I 0 00 R W 9 05 min 45 9 06 C step 1 C 25 C 9 I 0 01 R W 9 05 9 06 C step 1 C 2 0C...

Страница 292: ...one cooling WD curve Leaving water value for high ambient temp for DHW WD curve Leaving water value for low ambient temp for DHW WD curve High ambient temp for DHW WD curve Low ambient temp for DHW WD...

Страница 293: ...kW 0kW 4 3kW 7 4kW 5 6kW 6 9 I 6 07 0 9 I 6 08 R W 2 20 C step 1 C 10 C 9 I 6 09 0 9 I 6 0A R W 30 6 0E C step 1 C 60 C What is the maximum desired room temperature in heating What is the mimimum desi...

Страница 294: ...visible when the language of the user interface is set to Swedish Minimum running time for domestic hot water operation How much is the minimum pump PWM value Additional zone fixed pump PWM in case a...

Страница 295: ...0 pulse kWh PV meter 7 1000 pulse kWh PV meter 9 I D 0A 0 9 I D 0B 2 9 I D 0C 0 9 I D 0D 0 9 I D 0E 0 9 I E 00 R O 0 5 0 LT split 9 I E 01 R O 0 9 I E 02 R W 1 R O 2 0 Reversible 1 1 Heating only 2 9...

Страница 296: ...0 Continuous 1 Sample 2 Request 9 I F 0E R W 10 35 kW step 1kW 20 kW Bi zone kit settings 9 P 1 E 0B R W 0 not installed 1 2 Bizone kit installed 9 P 2 E 0C R W 0 Without hydraulic separator no direc...

Страница 297: ......

Страница 298: ......

Страница 299: ......

Страница 300: ...4P678716 1 2022 01 Copyright 2021 Daikin 4P678716 1 0000000X Verantwortung f r Energie und Umwelt...

Отзывы: