damage to the compressor. You can also set
this value to determine when you want the
auxiliary heat (if installed) to engage to help
meet the set temperature. The temperature
range is adjustable from –10 to 65 °F (–23.3 to
18.3 °C) or disabled by default.
This feature uses the Internet to obtain the
current outdoor temperature. If no Internet is
available, the Outdoor Unit’s temperature sensor
is used instead
.
Cool Differential Temp
The minimum
difference between the current temperature
and set temperature before the system calls
for cool. A smaller difference means shorter
cycle times, whereas a larger difference results
in longer cycle times. The temperature range
is adjustable from 0.5 to 3 °F (0.3 to 1.7 °C) in
0.5°F (0.3°C) increments.
Cool Dissipation Time
The amount of time
the fan will run after the cool has been turned
off. Running the fan for a period of time allows
for any cooled air left in the ducts to circulate
throughout the home. The time is adjustable
from 0 to 900 seconds (default is 0 seconds).
AC Overcool Max
When using the AC to
dehumidify, the setting configures how
many degrees below the current set point
the thermostat will run in order to reach the
dehumidify set point. Options are Disabled
(default) and 0.5 to 3 °F (0.3 to 1.8°C) in 0.5 F
(0.3°C) increments.
Heat Differential Temp
The minimum
difference between the current temperature
and set temperature before the system calls
for heat. A smaller difference means shorter
cycle times, whereas a larger difference results
18