roubleshooting

MicroTech III Unit Controller LED Faults

Table 11: Low Voltage Brownout or Emergency Shutdown

Description

Type

Yellow

Green

Red

Low Voltage Brownout

Fault

OFF

Flash

OFF

Emergency Shutdown

Mode

OFF

Flash

OFF

* Same LED display for both conditions
• Verify the E terminal is not connected to common.  Remove wire, if connected, and LED should change to solid green only
•  Confirm the low voltage supply is between 19-32VAC at the H1 terminal of the main board. If the low voltage supply is out of range, verify the unit 

supply voltage matches the nameplate voltage and the correct transformer primary wire has been selected

Table 12: Compressor High Pressure

Description

Type

Yellow

Green

Red

Compressor High Pressure

Fault

OFF

OFF

Flash

• Verify high pressure switch is connected to terminal H3 on the main board

• Check for continuity of the high pressure switch
If the high pressure fault resets when power is cycled

• Check water flow (cooling operation)
• Check airflow (heating operation)
• Entering water and air temperatures should be within the operating limits

Table 13: Compressor Low Pressure

Description

Type

Yellow

Green

Red

Compressor Low Pressure

Fault

OFF

OFF

ON

• Loose wire connection on low pressure circuit
• Failed low pressure switch
• Unit is low on charge

Table 14: Compressor Suction Temp Fail, Room Temp Sensor Fail, Leaving Water Temp Sensor Fail

Description

Type

Yellow

Green

Red

Compressor Suction Temp Sensor Fail

Fault

Flash

Flash

ON

Room Temp Sensor Fail (Room Sensor Control Only)

Fault

Flash

Flash

ON

Leaving Water Temp Sensor Fail

Fault

Flash

Flash

ON

• Check connection of low suction temperature sensor on terminal H6 pins 2 and 3

• Check resistance of low suction temperature sensor, leaving water temperature sensor, and room sensor or return air sensor. All sensors are 

10kohm thermistor @77

°

F

• Return air sensor and room sensor shall not be connected simultaneously

Table 15: Compressor Low Suction Temp

Description

Type

Yellow

Green

Red

Compressor Low Suction Temp

Fault

Flash

OFF

OFF

• Check water flow (heating operation)
• Check airflow (cooling operation)
• Entering water and air temperatures should be within the operating limits

Table 16: Low Entering Water Temp

Description

Type

Yellow

Green

Red

Low Entering Water Temp

(No Display with Boilerless EH)

Fault

Flash

OFF

Flash

• Low entering water temperature (below 35

°

F standard range or 13.5

°

F extended range)

Table 17: Condensate Overflow

Description

Type

Yellow

Green

Red

Condensate Overflow (Cooling & 

Dehumidification Modes Only)

Fault

ON

OFF

OFF

• Poor condensate drain
• Check the resistance to ground on condensate wire. This should be open if there is no water in the pan

www.DaikinApplied.com 37 

IM 1049-9

Содержание Enfinity CCH

Страница 1: ...Installation and Maintenance Manual IM 1049 9 Group WSHP Part Number 910258820 Date December 2018 Daikin Enfinity Horizontal Water Source Heat Pumps R 410A Refrigerant Model CCH CCW Unit Sizes 007 070...

Страница 2: ......

Страница 3: ...rt up 23 Changing PSC Fan Motor Speed 23 Optional EC Motor 25 Start up 26 Typical Wiring Diagrams 27 Thermostats Wall Sensors 32 Typical Connections For Thermostats Temperature Sensors 32 Additional A...

Страница 4: ...ht Discharge Air 09 13 E End Discharge S Straight Discharge Blower Motor 10 14 15 01 Standard PSC 03 Low Static 04 ECM Construction Type 12 18 A Standard 1 2 inch FG insulation 1 filter rack B Standar...

Страница 5: ...spection by the carrier s agent within fifteen 15 days of the delivery date and file a claim with the carrier CAUTION The installer must determine and follow all applicable codes and regulations This...

Страница 6: ...ts 5 Each unit is furnished with a hanger kit The kit is shipped unassembled and includes hanger brackets rubber isolators washers bolts and lock washers Lay out the threaded rods per the dimension in...

Страница 7: ...personal injury or death CAUTION Sharp edges can cause personal injury Avoid contact with them Use care and wear protective clothing safety glasses and gloves when handling parts and servicing heat pu...

Страница 8: ...Fan Motor Reinstall Top Completed End Discharge Assembly IM 1049 9 8 www DaikinApplied com 6 Lift the fan assembly out rotating it 180 degrees and position it within the opening at the end of the unit...

Страница 9: ...ace a straight length of duct 5 to 10 times the duct width before the next fitting to smooth out airflow Diffusers that are located in the bottom of a trunk duct can also produce noise For this same r...

Страница 10: ...gure 9 Standard 1 25mm Filter rack return air duct collar Standard 2 51mm Figure 10 Optional 2 51mm Filter rack return air duct collar Tool less Filter Removal Ventilation Air Ventilation may require...

Страница 11: ...Volt Operation All 208 230 volt single phase and three phase units are factory wired for 208 volt operation For 230 phase operation the line voltage tap on the 24 volt transformer must be changed Dis...

Страница 12: ...tape to assure a tight seal Figure 11 Sizes 007 through 060 shown Ball Valves Supply Riser Return Riser Condensate Riser Supply Air Hanger Kits 4 Flex Hoses Electrical Access Panel Note Do not over t...

Страница 13: ...an drain water 3 Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system Short circuited supply and return runouts should now be connected to...

Страница 14: ...selection Some conditioners have built in time delays which prevent the compressor from immediately starting With most control schemes the fan will start immediately After a few minutes of compressor...

Страница 15: ...not for continuous duty Operating Mode Entering Air F Entering Water F Minimum Maximum Standard Range Extended Range DB WB DB WB Minimum Maximum Minimum Maximum Cooling 50 40 105 87 45 120 30 120 Amb...

Страница 16: ...al output to indicate an alarm condition exists Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset some lockouts There are 3 means to reset an automatic l...

Страница 17: ...larm Output TB2 3 W2 Thermostat Heat Stage 2 Input TB2 4 W1 Thermostat Heat Stage 1 Input TB2 5 Y2 Thermostat Cool Stage 2 Input TB2 6 Y1 Thermostat Cool Stage 1 Input TB2 7 G Thermostat Fan Input TB2...

Страница 18: ...s Jumper Setting Model Compressor Options JP1 JP1 Open Single Compressor Model factory default setting JP1 Shorted Dual Compressor Model Hot Gas Water Reheat HGR Dehumidification JP2 JP2 Open None def...

Страница 19: ...rned on This signal is detected by a pump restart relay providing a N O or N C set of contacts for heat pump loop circulation pump or motorized valve control When used with a system control by others...

Страница 20: ...apability of substituting the wall sensor with a duct mounted return air sensor Each unit controller orchestrates the following unit operations Enable heating and cooling to maintain setpoint based on...

Страница 21: ...ed that the MAC address dip switches on the communication module be set prior to installing the unit in the ceiling Access to the dip switches may be limited when the unit is installed Reference IM 92...

Страница 22: ...IM 1049 9 22 www DaikinApplied com Controls Figure 18 LonWorks Communication Module Placement on MicroTech III Unit Controller...

Страница 23: ...GRN RD LOW BLK HIGH Factory Wired WHT CAPACITOR LINE BRN FAN MOTOR Unit Sizes 015 and 024 all available voltages Fan motors on unit sizes 015 and 024 in all available voltages have a four position ter...

Страница 24: ...0 60 1 and 208 230 60 3 factory wired for low speed 1 YEL 2 BRN 3 BLK 4 RED LOW FACTORY WIRED LINE HIGH GR YE CAPACITOR FAN MOTOR Unit Size 048 380 50 3 460 60 3 575 60 3 The fan motor on unit size 04...

Страница 25: ...NE HIGH FACTORY WIRED GR YE CAPACITOR FAN MOTOR Unit Size 070 460 60 3 575 60 3 The fan motor on unit size 070 for voltages 460 60 3 and 575 60 3 Figure 32 have a five position terminal block and are...

Страница 26: ...g After a few minutes of operation check the discharge grilles for cool air delivery Measure the temperature difference between entering and leaving water It should be approximately 1 1 2 times greate...

Страница 27: ...sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow Sensor...

Страница 28: ...EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow Sen...

Страница 29: ...itch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board RAT Return Air Temp Sensor RV Reversing Valve Solenoid X1 Transformer _____ Standard Unit Wiring _ _ _ _...

Страница 30: ...LED Annunciator Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay Fan Motor RAT Return Air Temp Sensor RV Reversing Val...

Страница 31: ...mp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board RAT Return Air Temp Sensor RV Reversing Valve Solenoid X1 Transformer _____ Standard Unit Wiring _ _ _ _ Optional Wiring by others...

Страница 32: ...Y2 G C RH RC W2 A I O Expansion Module TB1 MicroTech III Controller Terminal TB2 Programmable Touch Screen Y1 1 Notes Includes thermostat and wall plate Refer to IO manual 910193127 Figure 41 Program...

Страница 33: ...132 910193133 910193134 P N 667720401 Sensors used with MicroTech III control Building Automated System Operation Figure 46 Digitally Adjustable Display Sensor 6 button P N 910121754 1 R 2 4 E U 6 5 3...

Страница 34: ...10121753 3 2 5 1 4 Figure 51 Adjustable Cool Warm with Occupancy Switch P N 910121753 NOTICE For 50Hz units it may be necessary to install a Ferrite Core Noise Suppresor on the thermostat cord cable w...

Страница 35: ...ssory used when up to 3 units are controlled from a single thermostat Typically the control panel and board is centrally mounted between the units and thermostat A maximum of 2 boards may be used toge...

Страница 36: ...a water source heat pump operates under a wide range of water and air temperatures the values printed below are to be taken as suggested pressure and temperatures All Daikin water source heat pumps a...

Страница 37: ...sure switch Unit is low on charge Table 14 Compressor Suction Temp Fail Room Temp Sensor Fail Leaving Water Temp Sensor Fail Description Type Yellow Green Red Compressor Suction Temp Sensor Fail Fault...

Страница 38: ...have a control signal or ready to operate when a control signal is active I O Expansion Module LED Faults For units with optional boilerless electric heat Table 22 Invalid Jumper Configuration Descrip...

Страница 39: ...Pressure Circuit 2 Description Type Yellow Green Red Low Pressure Circuit 2 Fault OFF OFF ON Loose wire connection on low pressure circuit Failed low pressure switch Unit is low on charge Table 28 Low...

Страница 40: ...Pressure Low Low Air Flow Heating High High High High Low High Low High Pressure Normal Low Air Flow Cooling Low Low Low Low High High Low Low Temp Normal Low Water Flow Heating Low Low Low Low High...

Страница 41: ...defective wiring or loose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal windings with ohm meter...

Страница 42: ...n flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle Figure 59 Heating Mode Single Circuit Only Shown Return Air Thermal Expan...

Страница 43: ...roTech III unit controller s control or thermostat inputs However only one drive terminal R or C can be connected to any individual input terminal or damage may result Some control inputs are not acce...

Страница 44: ...of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed _____...

Страница 45: ...be converted to GPM by looking in the equipment specificaton catalog Caution P GPM Note A conversion table must be used to find GPM from Delta P measurements Loop Fluid Temperature Rise Drop through...

Страница 46: ...page Model Serial H P EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cool ing Check Air Filter and Coil Comments more comments on next sheet 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23...

Страница 47: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 47 IM 1049 9...

Страница 48: ...ndard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details Refer to Form 933 430285Y To find your local Daikin Applied...

Отзывы: