4 Unit installation
Installation manual
6
EL23E
Daikin Altherma 3 R MT F
4P708476-1 – 2023.03
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (example: open flames, an
operating gas appliance or an operating electric heater)
and have a room size as specified below.
NOTICE
▪ Do NOT re-use joints and copper gaskets which have
been used already.
▪ Joints made in installation between parts of refrigerant
system shall be accessible for maintenance purposes.
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation and are executed ONLY by authorised persons.
NOTICE
▪ Protect pipework from physical damage.
▪ Keep the pipework installation to a minimum.
4.1.3
Installation patterns
Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type
Allowed patterns
Living room, kitchen, garage, attic, basement, storage room
1, 2, 3
Technical room (i.e. room that is NEVER occupied by persons)
1, 2, 3, 4
PATTERN 1
PATTERN 2
PATTERN 3
PATTERN 4
a
b
a
b
H
release
H
release
1a
b
A
1b
H
release
H
release
2a
b
c2
c1
A
B
2b
A
b
3a
c2
c1
A
Ventilation openings
N/A
Between room A and B
N/A
Between room A and
outside
Minimum floor area
Room A
Room A + Room B
N/A
N/A
Chimney
Might be needed
Might be needed
Connected to outside
N/A
Release in case of
refrigerant leakage
Inside room A
Inside room A
Outside
Inside room A
Restrictions
7],
8],
10], and
"Tables for PATTERN 1, 2 and 3"
See
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
a
If no chimney is installed, this is the default point of release
in case of refrigerant leakage.
If needed, you can connect a chimney here.
b
Chimney
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
release
Actual release height:
1a
2a
: Without chimney. From floor to top of the unit.
▪ For 180 l units => H
release
=1.66 m
▪ For 230 l units => H
release
=1.86 m
1b
2b
: With chimney. From floor to top of the chimney.
▪ For 180 l units => H
release
=1.66 m + Chimney height
▪ For 230 l units => H
release
=1.86 m + Chimney height
3a
Installation with chimney connected to the outside. The
release height is not relevant. There are no requirements to
the minimum floor area.
N/A
Not applicable