2
1.
Take off the cover.
2.
Install the base. In case of wall mounting, fix the base to the wall with 2
Ø 4 mm screws and corresponding dowels based on the quality of the wall.
In case of installation on a mounting bracket, use a TS 35/7.5 bracket.
3. Make the electric connection.
4. Install the cover.
The control direction is set with jumper 1:
NO operation:
Jumper 1 = ON
NC operation:
Jumper 1 = OFF
The fixed follow-up time of 2 minutes of the pump or
the boiler can be increased by an additional 5, 10 or
15 minutes using jumper 2 and 3:
Only use a dry and solvent-free, soft cloth for cleaning.
• De-energise the complete installation.
•
Remove the wiring to all externally connected components.
•
Remove the base and dispose of it properly, if necessary.
WARNING! Electrical voltage! Danger to life!
• Always disconnect the base from the mains network and secure
against unintended activation before opening.
• Disconnect external voltages and secure against unintended activation.
WARNING! Electrical voltage! Danger to life!
• Always disconnect the base from the mains network and secure
against unintended activation before opening.
• Disconnect external voltages and secure against unintended activation.
These instructions are protected by copyright. All rights reserved. They may not be copied, reproduced, abbreviated or transmitted,
neither in whole nor in parts, in any form, neither mechanically nor electronically, without the previous consent of the manufacturer.
1
3
2
2
1
230 V
T4AH
230 V
T4AH
NC
NO
0min 5min
Nachlaufzeit
Shut-down delay
10min 15min
2 3
2 3
2 3
2 3
Time
Jumper 2
Jumper 3
0 min
OFF
OFF
5 min
OFF
ON
10 minutes
ON
OFF
15 minutes
ON
ON
Function
Colour Explanation
Pump/boiler
Green
On: Pump/boiler active
Off: Pump/boiler inactive
Flashing: Temperature limiter/dew point sensor active
Mains voltage
Green
On: Device in operation
Off: Device not in operation
Flashing: Valve prot
ection function active (Option)
Fuse
Red
On: Fuse defective
Change over
Blue
On: Cooling mode active
Off: Heating mode active
Heating zones
1 to 10
Green
On: Heating zone active
Off: Heating zone off
For the connection of the voltage supply, the cable sections must be 1.5 mm² for 230 V. Depending on the voltage version of the base, it is possible to take L1 or
L and L2 or N, as well as the protective conductor, from the base. A temperature limiter/dew point sensor can be connected to the contact TB/%H in NC operation;
this contact cannot be used in NO operation. If no temperature limiter is connected, the connection TB/%H must be bridged (provided for at the factory). The bridge
must be removed as soon as a temperature limiter is connected. The temperature limiter must be a normally closed contact.
Heating/cooling change-over
Cooling
Heating
System clock
Voltage source
Temperature limiter
Pump
Boiler
Actuator
Analogue thermostat
Digital controller
~
CO
5 Installation
5.1 Select and insert the fuse
5.2 Parametrization
6 Electric connection
7 LED signalling
8 Maintenance
8.1 Fuse change
8.2 Cleaning
9 Dismantling
The wiring of the thermostats
depends on the present ba-
sis. For wiring purposes,
please observe the instruc-
tions of the thermostat or of
the respective component.
The voltage used must
be marked on the
identification plate.
2a
1
Cable bridge in the
parametrization
NO operation
for all unused
thermostat
connections.
2b
2b
3
N/L2
CO
A
L/L1
N/L2
CO
A
L/L1
%H
N/L2
L/L1
CO
N
L
~
PE
N
L
PE
This symbol means that electrical and electronic products may NOT be mixed with unsorted household
waste. Units must be treated at a specialized treatment facility for reuse, recycling and recovery.
4P560992-1
2019.01
Copyright 2019 Daikin