1
EKWUFHTA1V3
These instructions must be read completely and thoroughly before commencing
any work with the base. These instructions must be kept and are to be handed
over to future users.
The following symbols show
The base serves
• the arrangement of a room-by-room temperature control system with a
maximum of 10 zones for heating and cooling systems,
• the connection of a maximum of 18 actuators and 10 room control units,
• the connection of actuators with the direction of control action NC (normally
closed) or NO (normally open), depending on the thermostat used,
• the connection of an external timer,
• depending on the type used, the connection of a pump or a boiler, a CO
signal generator, a temperature limiter or dew point sensor,
•
a fixed installation.
Every other use, modification and conversion is expressly forbidden and leads to
dangers the manufacturer cannot be held liable for.
The electrical installation must be performed according to the current national
regulations as well as according to the regulations of your local electric power
utility company. These instructions presume specialist knowledge corresponding
to an officially recognised degree in one of the following professions:
• Systems Mechanic for sanitary, heating and air condition technology
• Electrical Equipment Installer or
• Electronics Engineer
according to the profession designations officially announced in the Federal Re
-
public of Germany, and to comparable professions within the European Com-
munity Law.
All safety notes in these instructions must be observed in order to avoid acci-
dents involving personal harm and/or property damage.
WARNING
Danger to life due to the electrical voltage at the base station!
• Always disconnect from the mains network and secure against unintended
activation before opening.
• Only an authorised electrician may open the device.
• Disconnect external voltages and secure against activation.
• Only use the product if it is in perfect state.
• Do not operate the device without the device cover.
• This unit is not intended to be used by persons (including children) with restrict-
ed physical, sensory or mental skills or those who lack experience or knowl-
edge. If necessary, these persons must be supervised by a person responsible
for their safety or receive instructions from this person on how to use this unit.
• Ensure that children do not play with this device. Children must be super-
vised if necessary.
• In case of emergency, disconnect the complete room-by-room temperature
control system.
The following instructions show the full equipment. Individual positions may be
omitted depending on the present base.
This product is labelled with the CE Marking and thus is in compliance with
following regulations:
• 2014/30/EU with amendments “Council Directive on the approximation of the
laws of the Member States relating to Electromagnetic Compatibility”
•
2014/35/EU with amendments “Council for Coordination of the Regulations
of EU Member Countries regarding the electrical equipment for use within
certain voltage limits”
•
2011/65/EU “Restriction of the Use of Certain Hazardous Substances in
Electrical and Electronic Equipment”
Increased protection requirements may exist for the overall installation, the com-
pliance of which is the responsibility of the installer.
1 Boiler connection
2 Pump connection
3 Protective conductor connection
(only for 230 V)
4 Voltage supply
5
Fuse
6 Temperature limiter or dew point
sensor
7
Reduction channel, external timer
8
Heating/cooling change-over
9 Thermostat connection
10 LEDs
11 Strain relief
12 Connection of actuators
13 DIP switch
14 Contacts for casing cover with
integrated system clock
1 Scope of supply
2 About these instructions
3 Safety
3.1 Intended use
3.2 Safety notes
3.3 Personnel-related preconditions
4 Device overview
4.1 Connections and indications
4.2 Technical data
4.3 Conformity
important information.
a warning with respect to electrical voltage
1x
2x
T4AH
O
perating voltage:
230 V ±10 %, 50 Hz
Power input 230 V:
max. 50 VA
Fuse 230 V:
T4AH
Number of heating zones:
10
Connectable actuators Type
EKWCVATR1V3
10 heating zones:
max. 18
The following applies to other actuators than those mentioned above
Inrush current per actuator:
max. 500 mA (for 230 V)
Pump/boiler control
Switching power:
2 A, 200 VA inductive
Turn-on delay:
2 min
Follow-up time fixed/adjustable:
2 min / 5 - 15 min
Pump protection function:
14 days for 1 minute
Control direction:
NC or NO
Ambient temperature:
0 to +50 °C
Storage temperature:
-20 to +70 °C
Ambient humidity:
80%, not condensing
Temperature for ball pressure test
: Terminals: 100 °C
Plastic enclosures:
75 °C
Pollution degree:
2
Rated impulse voltage:
1500 V
ERP class acc. to EU 811/2013:
1=1 %
Protection class 230 V:
II
Protection type:
IP 20
Type action:
Type 1 / Type 1.C
Dimensions (H x L x D):
90 x 326.5 x 50 mm
6 7 8
9
10
2 3 4
5
11
12
13
14
1
INSTALLATION MANUAL
Multi-zoning base unit 230 V
https://qr.daikin.eu?N=EKWUFHTA1V3