background image

2 Specific installer safety instructions

Installation and operation manual

6

EKVDX32~100A2VEB

VRV system air conditioner

4P555815-1A – 2021.08

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

The  VAM  and  the  EKVDX  indoor  unit  MUST  share  the
same electrical safety devices and power supply.

CAUTION

▪ Each  EKVDX  unit  has  to  be  connected  to  a  separate

user interface. Only a safety system compatible remote
controller  can  be  used  as  the  user  interface.  See
technical  data  sheet  for  remote  controller  compatibility
(e.g. H-type user interface like BRC1H52/82*).

▪ R32 refrigerant: the user interface MUST be installed in

one of the rooms the EKVDX unit is discharging into.

▪ R410A  refrigerant:  the  user  interface  can  also  be

installed in e.g. the hallway.

2.1

Instructions for equipment using
R32 refrigerant

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating  gas  appliance  or  an  operating  electric  heater)
and have a room size as specified below.

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation and are executed ONLY by authorised persons.

WARNING

If  one  or  more  rooms  are  connected  to  the  unit  using  a
duct system, make sure:

▪ there are NO operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  the  room  where  the  unit  is  installed,
in  case  the  floor  area  is  less  than  the  minimum  floor
area A

min

 (m²) of the rooms that are served.

▪ NO auxiliary devices, which may be a potential ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  the  manufacturer

are used in the duct work;

▪ the  air  outlet  can  be  connected  directly  to  multiple

rooms by ducting. Do NOT use spaces such as a false
ceiling as a duct for the air outlet.

▪ the  height  of  the  air  extraction  opening  from  the  room

MUST  be  be  equal  or  below  the  refrigerant  release
point.

NOTICE

▪ Precautions shall be taken to avoid excessive vibration

or pulsation to refrigeration piping.

▪ Protection  devices,  piping  and  fittings  shall  be

protected  as  far  as  possible  against  adverse
environmental effects.

▪ Provision shall be made for expansion and contraction

of long runs of piping.

▪ Piping  in  refrigerating  systems  shall  be  designed  and

installed such as to minimise the likelihood of hydraulic
shock damaging the system.

▪ The  indoor  equipment  and  pipes  shall  be  securely

mounted  and  guarded  such  that  accidental  rupture  of
equipment  or  pipes  cannot  occur  from  events  such  as
moving furniture or reconstruction activities.

CAUTION

Do  NOT  use  potential  sources  of  ignition  in  searching  for
or detection of refrigerant leaks.

NOTICE

▪ Do  NOT  re-use  joints  and  copper  gaskets  which  have

been used already.

▪ Joints  made  in  installation  between  parts  of  refrigerant

system shall be accessible for maintenance purposes.

2.1.1

Installation space requirements

If  the  system  uses  R32  refrigerant,  extra  safety  measures  are
required  because  R32  refrigerant  is  mildly  flammable.  This  means
that  the  system  is  restricted  with  respect  to  the  total  refrigerant
charge and/or the floor area that is served.

WARNING

In  case  the  appliance  contains  R32  refrigerant,  refer  to

"2.1.2 To determine the charge limitations"

 [

4

 7].

NOTICE

▪ Pipework shall be protected from physical damage.

▪ Installation of pipework shall be kept to a minimum.

Содержание EKVDX32A2VEB

Страница 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner EKVDX32A2VEB EKVDX50A2VEB EKVDX80A2VEB EKVDX100A2VEB...

Страница 2: ...94 31 7 a 15 8 b 95 32 0 a 16 0 b 96 32 4 a 16 2 b 97 32 7 a 16 3 b 98 33 0 a 16 5 b 99 33 4 a 16 7 b 100 33 7 a 16 8 b 63 21 2 a 10 6 b 64 21 6 a 10 8 b 65 21 9 a 10 9 b 66 22 2 a 11 1 b 67 22 6 a 11...

Страница 3: ...s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputa...

Страница 4: ...omponents 20 14 2 To connect the electrical wiring to the indoor unit 20 14 3 To connect the external outputs 21 14 4 To connect the external input 21 15 Configuration 21 15 1 To set the discharge tem...

Страница 5: ...stall the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Refrigerant piping installation see 13 Piping installation 418...

Страница 6: ...ectric heater in the room where the unit is installed in case the floor area is less than the minimum floor area Amin m of the rooms that are served NO auxiliary devices which may be a potential ignit...

Страница 7: ...oor units and EKVDX units 63 84 kg Case 1 VAM EKVDX and indoor unit s combined Step 1 determine A1 the area of the smallest room in the lowest underground floor in which an indoor unit is present if a...

Страница 8: ...room with a ceiling mounted indoor unit on other floors has an area of 14 m There are multiple underground floors in the building and the smallest room with an indoor unit in the lowest underground fl...

Страница 9: ...on contact your installer or local authority Batteries are marked with the following symbol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed...

Страница 10: ...se with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand...

Страница 11: ...modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electrical shock or fire Contact your dealer In case of accidental refrigerant le...

Страница 12: ...inner chemical dust cloth etc The panel may get discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wi...

Страница 13: ...tion started The following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minutes Operation Description Hot start a The supply air fan will stop...

Страница 14: ...o the service manual for more information Contact your dealer to repair and re activate the system Refer to the service manual for more information 7 2 To clean the air outlet WARNING Do NOT let the i...

Страница 15: ...g Auxiliary pipe liquid 9 5 mm h Sealing for duct flanges EKVDX50 100A2 i Washers for hanger bracket j Drain hose k Sealing pads drain pipe gas pipe and liquid pipe l Tie wraps m Sealing strips for ca...

Страница 16: ...for maintenance and service a mm A C b c 600 B 300 809 c 600 A Side view refrigerant piping drain piping control box B Side view air outlet C Bottom view a Ceiling opening width 900 mm EKVDX32A2 950 m...

Страница 17: ...as duct use accessory screws 2 Connect the duct to the canvas duct g c b a f e d d h f a Screws for duct flanges accessory b Duct flange rectangular installed on the unit c Indoor unit d Insulation fi...

Страница 18: ...n hose 5 5 d d Sealing pad accessory 6 Connect the drain piping to the drain hose 6 e e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet onl...

Страница 19: ...surface of the insulation 13 2 Connecting the refrigerant piping DANGER RISK OF BURNING SCALDING 13 2 1 To connect the refrigerant piping to the indoor unit CAUTION Install the refrigerant piping or c...

Страница 20: ...WAYS be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the ser...

Страница 21: ...al data sheet of the user interface E g the BRC1H52 controller generates an alarm of 65 dB sound pressure measured at 1 m distance from the alarm 14 4 To connect the external input INFORMATION For det...

Страница 22: ...with VRV system Without duct With duct Without duct With duct Without duct With duct Setting for cold areas when heater thermostat is OFF c Stop Stop Low Low Stop stop Low Low Fan operation when defr...

Страница 23: ...m NO F1 F2 connection between VAM and EKVDX only P1 P2 connection allowed NO group control Power supply and electrical safety devices are shared between VAM and EKVDX Each VAM unit is connected to on...

Страница 24: ...19 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Porta...

Страница 25: ...or V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoi...

Страница 26: ......

Страница 27: ......

Страница 28: ...4P555815 1A 2021 08 Copyright 2021 Daikin 4P555815 1 A 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: