background image

7 Configuration

Installation manual

5

EKRTETS
Room thermostat
4P677092-1 – 2021.10

The output relays (H and C are voltage-free contacts) can handle a
maximum  load  of  5  A  —  230  V.  For  heating  only  application,  wire
connection C is not to be installed.

WARNING

Protect the power supply with a fuse of 0.065 A (X2M) and
select a power cable that is in accordance with applicable
legislation.

WARNING

A  main  switch  or  other  means  for  disconnection,  having  a
contact  separation  in  all  poles,  MUST  be  incorporated  in
the fixed wiring in accordance with applicable legislation.

7

Put the cable bracket back in place and tighten the screws.

8

Put the receiver cover back in place and tighten the screws.

INFORMATION

To fully complete the installation of the receiver, configure
the  radio  connection  between  the  receiver  and  the  room
thermostat. 

See 

"7.3 

Receiver-thermostat 

radio

configuration"

 [

4

 6] for more information.

NOTICE

To ensure access, keep the front of the receiver clear at all
times.

6.3

To install the external temperature
sensor as floor temperature sensor

As it should be integrated into the floor, the installation of EKRTETS
should  be  planned  and  performed  in  advance.  When  EKRTETS  is
installed as a floor temperature sensor, the room thermostat must be
mounted to the wall. See 

"6.1 To install the room thermostat"

 [

4

 3] for

more information.

INFORMATION

The  following  procedure  only  serves  as  an  example.  Your
actual situation may differ from what is represented here.

Prerequisite: 

You  have  considered  the  site  requirements  for  the

room  thermostat  when  selecting  the  installation  location.  See

"5.1 Installation site requirements"

 [

4

 3] for more information.

1

Integrate  the  temperature  sensor  in  an  electrical  conduit
(Ø16 mm maximum) in the floor construction.

b

c

d

a

a

Room thermostat

b

External temperature sensor conduit

c

External temperature sensor (EKRTETS)

d

Water pipes

2

Pass  the  temperature  sensor  cable  through  the  conduit  until  it
reaches the seal.

3

Connect  the  temperature  sensor  wiring  to  the  room  thermostat
as described in 

"6.1 To install the room thermostat"

 [

4

 3].

4

On the room thermostat, set the value for parameter 20 (rEGU)
to  FLR  in  the  installer  menu.  For  more  information  about  the
installer menu, see 

"7.2 Installer menu"

 [

4

 6].

NOTICE

Properly  seal  the  temperature  sensor  electrical  conduit  in
order  to  protect  the  room  thermostat  from  hot  air  currents
and  to  allow  for  possible  future  replacement  of  the
temperature sensor.

7

Configuration

7.1

User menu

The user menu allows you to set basic room thermostat parameters.

7.1.1

To enter the user menu

1

Press and hold 

 for 5 seconds.

Result: 

The first parameter (rF INI) of the user menu appears on the

display.

To exit the user menu, use the navigation buttons to select the "End"

parameter and press 

.

7.1.2

User parameters

Parameter

Description

Possible values

(a)

#

Name

00

rF INI

Radio configuration mode

01

dEG

Temperature unit used
on display

°C

▪ °F

02

__:__

Time format used on
display

24H 

(24 

hour

display)

▪ 12H (12 hour display)

03

dst

Daylight summer time
change

yes

 (enabled)

▪ no (disabled)

04

AirC

Internal temperature
sensor calibration.

See 

"7.4 Temperature

sensor
calibration"

 [

4

 7] for

more information.

05

AMbC

External temperature
sensor calibration

06

HG

Anti-freeze temperature
in holiday mode

10°C

▪ Range: 0.5°C~10°C

07

ITCS

Intelligent Temperature
Control System

(b)

yes

 (enabled)

▪ no (disabled)

08

Clr ALL

Clear user settings: press and hold 

 for 5

seconds to reset all setpoints and user
parameters to their default settings.

09

CHAn

10

VErS

Software version

11

End

Exit the user menu. Press 

 to exit.

(a)

The default values are listed in 

bold

.

(b)

If enabled, this function will activate the installation in advance
(up to a maximum of 2 hours) to ensure that the desired setpoint
is reached at the appropriate time according to the set program.
With every program change, the room thermostat measures the
time taken by the installation to reach the setpoint to compensate
for any temperature differences that may be present at different
times. This allows you to make program changes without needing
to adjust the temperature in advance, because the room
thermostat does this automatically.

Содержание EKRTRB

Страница 1: ...Installation manual Room thermostat English Installation manual Room thermostat EKRTRB EKRTETS...

Страница 2: ...2M and select a power cable that is in accordance with applicable legislation WARNING A main switch or other means for disconnection having a contact separation in all poles MUST be incorporated in th...

Страница 3: ...pically close the indoor unit The receiver is designed to be installed in a vertical orientation only Do NOT install the receiver in metal boxes or near vertical metal pipes and electronic circuits Mo...

Страница 4: ...e the internal electronic parts Prerequisite You have considered the installation site requirements for the receiver when selecting the installation location See 5 1 Installation site requirements 43...

Страница 5: ...the temperature sensor wiring to the room thermostat as described in 6 1 To install the room thermostat 43 4 On the room thermostat set the value for parameter 20 rEGU to FLR in the installer menu For...

Страница 6: ...7 C Range 20 C 37 C Parameter Description Possible values a Name 33 Win Open window detection function yes enabled no disabled 34 rH Humidity threshold value 55 Range 0 100 35 dEv Dew prevention funct...

Страница 7: ...oling Humidity percentage threshold You can set a threshold value for the humidity percentage Whenever the room thermostat detects that the humidity percentage exceeds the set threshold cooling demand...

Страница 8: ...4P677092 1 2021 10 Copyright 2021 Daikin 4P677092 1 0000000T Verantwortung f r Energie und Umwelt...

Отзывы: