Tap water operation
The hot water supply takes precedence over the heating. If the flow switch senses a
request for more than 2 l/min of domestic hot water, any CH requests will be
interrupted. After the fan has switched on (code
3
) and there has been an ignition
(code
4
), the controller will switch to domestic water operation (code
6
). During
domestic hot water operation, the rpm of the fan, and therefore the power of the unit, is
controlled by the controller on the basis of the set tap water temperature.
The control system ensures the tap water temperature is correct. The water
temperature can be set between 40°C and 65°C (see par. 8.1). The set tap water
temperature is displayed on the operation panel. The standard setting is 60°C.
You can press the service button during tap water operation to read the actual tap water
temperature.
7
Heating up unit
In order to provide a fast supply of domestic hot water, a so-called tap comfort function
has been installed in the unit. This function keeps the heat exchanger at the right
temperature (this temperature can be set, see par. 8.2). The tap comfort function has
the following settings:
•
On:
( LED on)
The tap comfort function of the unit is continuously switched on.
The unit always immediately provides warm water.
•
Eco:
( LED on)
The tap comfort function of the unit is self-learning. The unit will
adjust to the usage pattern of the domestic hot water. This means the heat
exchanger will not be kept warm during the night or during longer absences.
•
Off:
(Both LEDs off)
The heat exchanger is not kept warm which means the supply of
domestic hot water takes a bit of time. If there is no need for fast delivery of domestic
hot water, the tap comfort function can be switched off.
3.4
PC Interface
The boiler controller is provided with an interface for a PC. A PC can be connected by
means of a special dongle, and the associated software. This facility enables you to
follow the behavior of the boiler controller, the unit and the heat installation over a long
period.
3.5
Test programs
There is an option in the boiler controller, to bring the unit into a test status.
Activating a test program, will switch on the unit with a set fan rotations per minute,
without the control functions intervening. The safety functions do remain active.
The test program is ended by pressing and simultaneously.
Test programs
Description of program
Button combination
Display reading
Burner on with minimum DHW
capacity (see parameter d par. 7.2)
and
"L"
Burner on with set maximum CH
power (see parameter 3 par. 7.2)
and (1x)
"h"
Burner on with maximum DHW power
(see parameter 3 par. 7.2)
and (2x)
"H"
Switching off test program
and
Current operation
situation
During test mode the following data can be read :
• By pressing the + button continuously in the display the CH water pressure is shown.
• By pressing the
- button continuously in the display the ionisation current is shown.
Содержание EKOMB22AAV1H
Страница 32: ...Daikin Europe NV 33...
Страница 87: ...Daikin Europe NV 31...
Страница 145: ...Daikin Europe NV 33...
Страница 200: ...Daikin Europe NV 31...
Страница 255: ...Daikin Europe NV 32...
Страница 311: ...Daikin Europe NV 32...
Страница 367: ...Daikin Europe NV 32...
Страница 394: ...Daikin Europe NV 4 Daikin EKOMB22AAV1H EKOMB28AAV1H EKOMB33AAV1H CH DHW O...
Страница 398: ...Daikin Europe NV 8 7 2 LED Eco LED LED 2 4 PC 2 5 WW d 7 2 L CH 3 7 2 1x h WW 3 7 2 2x H 2 5 1 7 10 2...
Страница 399: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Страница 403: ...Daikin Europe NV 13 4 2 1 2 cm 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Страница 404: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2 B...
Страница 405: ...Daikin Europe NV 15 4 3 3 1 2 A B C 3 4 5 6 B 7 8 9 D E 10 D F 11 5 6 12 4 3 4...
Страница 406: ...Daikin Europe NV 16 5 5 1 CH 1 CH 2 3 4 CH A B 3 bar 500 mm 5 1 1 7 4 5 1 2 CH 230 V E D 7 3 A B C D E 230 V F G H...
Страница 407: ...Daikin Europe NV 17 D CH A 55 C B X4 6 7 10 1 7 4 7 3 C o 0 3 P 5 2 3...
Страница 408: ...Daikin Europe NV 18 5 1 3 CH CH Z2 1 1 2 1 X4 6 7 3 2 X4 11 12 4 A 7 2 1 2 OpenTherm A B 230 V C T1 1 T2 2 Z1 1 Z2 2...
Страница 409: ...Daikin Europe NV 19 5 2 DHW 1 2 3 D C CH A EKOMB22AAV1H B EKOMB28AAV1H C EKOMB33AAV1H X Bar Y L min 10...
Страница 410: ...Daikin Europe NV 20 5 3 1 3 mm 1 2 A 3 1 4 2 5 6 10 2 7 8 5 3 1 X4 6 7 11 12 8 9 MIT 4 5 c 0 7 2 6 7...
Страница 412: ...Daikin Europe NV 22 5 RF 1 RF RF CH 5 RF CH 2 C rF L RF RF 1 5 4 4 10 1 7 5 5 5 1 1 2 2 3 4 50 mbar 5...
Страница 413: ...Daikin Europe NV 23 5 6 5 6 1 60 100 60 100 5 6 2 80 125 60 100 80 125 1 80 125 2 5 6 3 80 80 60 100 2 80 mm 1 80 2...
Страница 414: ...Daikin Europe NV 24 5 7 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Страница 421: ...Daikin Europe NV 31 5 10 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Страница 422: ...Daikin Europe NV 32 5 10 6 C83 O A B EKOMB22AAV1H 100 m EKOMB28AAV1H 85 m EKOMB33AAV1H 80 m...
Страница 429: ...Daikin Europe NV 39 6 3 1 2 3 4 5 6 6 3 1 10 2...
Страница 430: ...Daikin Europe NV 40 7 7 1 LED CH bar q 0 Su Et q LED Eco LED LED 8 1 LED 2 LED LED LED 30 CH LED...
Страница 431: ...Daikin Europe NV 41 30 C 90 C 80 C LED 40 C 65 C 60 C...
Страница 439: ...Daikin Europe NV 50 8 3 8 3 1 8 3 2 8 3 3 CH OpenTherm 80 1 X2 24 V X4...
Страница 441: ...Daikin Europe NV 52 DHW DHW 7 1 CH CH 8 3 8 CH OpenTherm CH 7 CH CH 8 3 9 LED A LED 8 3 10 LED A LED 20...
Страница 442: ...Daikin Europe NV 53 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 13 9 1 2 1 2 3 4 5...
Страница 447: ...Daikin Europe NV 58 11 Daikin Europe NV CH...
Страница 448: ...008 1548599_05 05 2022 88551810...