Daikin Europe NV
23
5.5
Flue gas output and air input
For the installation of the flue gas output and air input material, we
refer to the enclosed basic manual, or contact the manufacturer of
the appropriate flue gas output and air input equipment for
extensive technical information and specific assembly instructions.
Make sure that the spigot and socket joints of the flue gas
output and air input materials seal effectively and will not
come loose. Not properly attaching the flue gas output and the
air input can lead to dangerous situations or physical injury.
Check all parts which transport flue gas or air for air tightness.
5.5.1
Concentric connection 60/100
The boiler is fitted with a flue gas adapter suitable for connecting to
a concentric flue gas extractor system with a diameter of 60/100.
1.
Fit the concentric pipe for the air supply and burning gas extraction in the adapter.
The built-in gaskets ensure there is an air tight seal.
5.5.2
Concentric connection 80/125
If required, the flue gas adapter 60/100 can be replaced by a version
for a flue gas extractor system with a 80/125 diameter.
The conversion set for parallel connection can be ordered under EKHY090717.
1.
Carefully follow the instruction as provided with the adapter set 80/125.
2.
Fit the concentric pipe for the air supply and burning gas extraction in the adapter.
The built-in gaskets ensure there is an air tight seal.
5.5.3
Parallel connection 80/80
If required, the flue gas adapter 60/100 can be replaced by a version
for a parallel flue gas extraction system (2 pipes) with a 80 mm diameter.
The conversion set for parallel connection can be ordered under EKHY090707.
1.
Carefully follow the instruction as provided with the adapter set 80.
2.
Fit the pipes for the air supply and burn gas extraction in the input and output of
the unit. The built-in gaskets ensure there is an airtight seal.
5.5.4
Materials to be used:
Unit
category
Materials
Supplier/Test standard
C13
Feedthrough
Daikin
Other parts
Gastec QA or Daikin
C33
Feedthrough
Daikin
Feedthrough at the Prefab chimney
Gastec QA, Daikin or third
parties
Other parts
In accordance to applicable
national or local legislation
C43
All materials
Gastec QA or Daikin
At the CLV system
Gastec QA
C53
Inlet roster
Daikin
Other parts and exhaust hood
Gastec QA or Daikin
C63
All materials and feedthrough
Gastec QA
Main channel
Gastec QA
Other parts
Gastec QA or Daikin
C83
Inlet roster
Daikin
C93
All materials
Gastec QA or Daikin