4 Start-up
Installation and operating manual
16
EKHW(D/C/P)(300/500)(P)B
Daikin Altherma ST (Hot water storage tank)
008.1633099_00 – 06/2020
3‒4 Filling the buffer storage tank (1)
a
Hot water storage tank
b
Drain-back solar – flow connection
c
Safety overflow connection
d
Drain-back solar – return flow connection
All EKHWD hot water storage tanks:
1
Mount the KFE filling connection (accessory KFE BA) to the
filling and draining connection on the EKHWD (
16], item d).
2
Connect the filling hose with backflow prevention (1/2") to the
previously installed KFE filling connection.
3
Fill the storage tank on the EKHWD until water comes out of the
safety overflow (
3‒4 Filling the buffer storage
EKHWC/EKHWP hot water storage tank with solar system:
1
Install KFE filling connection (accessory KFE BA)
▪ (a) With
solar system: on the filling and draining connection
of the EKHWC/EKHWP.
▪ (b) With
solar system: on the connection bracket of the
control and pump unit (EKSRPS4A).
2
Connect the filling hose with backflow prevention (1/2") to the
previously installed KFE filling connection.
3
Only with
solar system: Adjust the valve insert X1 on the
connecting angle so that the path to the filling hose is opened
(
3‒5 Filling the buffer storage tank (2)"
16]).
4
Open the valve on the KFE filling connection and the cold water
inlet and fill the storage tank on the EKHWC/EKHWP until water
comes out of the safety overflow (
16]).
3‒5 Filling the buffer storage tank (2)
4
Start-up
WARNING
▪ Units which have been set-up and installed incorrectly
can be a health and safety risk endangering human life
and may not operate properly.
▪ Installation commissioning may only be carried out by
authorised and trained heating technicians following
the provided installation and maintenance manual.
▪ Only original replacement parts may be used.
CAUTION
A hot water storage tank commissioned improperly can
lead to property damage.
▪ Observe the regulations in VDI 2035 in order to avoid
corrosion and deposits.
▪
If the filling and top-up water has a high degree of
hardness
, measures must be taken to
stabilise this
hardness or soften the water
.
▪ Set the pressure reducer on the cold water connection
to a
maximum
of
6 bar
.
CAUTION
If the electric immersion heater is started with the storage
tank empty or not completely full, it can lead to a reduction
in performance of the electric heating (tripping of the safety
temperature limiter).
▪ Operate the electric immersion heater only with the
storage tank completely full.
Incorrect start-up makes the manufacturer's guarantee for the unit
void. If you have questions, please contact our Technical Customer
Service.
▪ Check all the points on the enclosed checklist. Make a record of
the test results and sign it, together with the operator.
▪ If an electric immersion heater is fitted, set the desired storage
tank water temperature.