background image

Page 5

User, Installations and Maintenance Manual

1.5  HYDRAULIC CONNECTIONS WARNINGS

It is mandatory that the installation complies with part G3 of the Building Regulations. For that the unit is factory 

equipped with a T/P safety relief valve (set = 90°C/7bar) and is supplied with a G3 kit composed by expansion 

vessel, PRSV device to be installed at the water inlet of the unit and that integrates a check-valve, a water 

pressure reducer (default set = 3,5bar), a water safety relief valve (set=6bar).
The outlet connection of both safety relief valves must be connected to a tundish. The discharge pipes from 

safety devices (tundish) must be installed to fully comply with Part G3 of the Building Regulations (latest edition).
The minimum inlet water pressure for the correct operation of the appliance is 0.15 MPa (1.5 bar).

Connect a rubber pipe to the condensate drain, taking care not to force too much so as not to break the drain 

pipe and refer to “7.6.1 Condensate drain connection" on page 20".
Use only connecting pipes (not supplied), rigid and resistant to electrolysis both at the inlet of cold water and at 

the outlet of hot water from the device.

For models that incorporate a heat exchanger (solar coil), the circuit must not exceed 1.0 MPa (10 bar) and its 

temperature must not exceed 80°C.

Refer to description and illustrations in the “7.5 Hydraulic connections" on page 17 and “7.7 Integration with 

solar thermal system (only for EKHHEU200PCV37 and EKHHEU260PCV37 models)" on page 20.

1.6  ELECTRICAL CONNECTIONS WARNINGS

The appliance shall be installed in accordance with national wiring regulations.

The electrical installation must include an all-pole disconnection with a separation of the contacts on all poles 

capable of guaranteeing complete disconnection in the overvoltage category III upstream of the appliance, 

complying with local installation rules in force .

The device must be protected by an adequate differential switch (max 30 mA). The type of differential switch 

should be selected by assessing the type of electrical devices used by the system as a whole.

Earth connection is mandatory. The manufacturer of the appliance shall not be held liable for any damage 

caused by failure to earth the system or due to anomalies in the electric power supply.

It is strictly forbidden to connect the appliance at the AC mains through extensions or by a power strip.

Before taking off the cover, make sure that the power is turned off to prevent injury or electric shock.

Refer to description and illustrations, respectively, in the “7.8 Electrical connections" on page 21 and “7.9 

Wiring diagram" on page 23.

Содержание EKHHEU200CV37

Страница 1: ...EKHHEU200CV37 EKHHEU200PCV37 EKHHEU260CV37 EKHHEU260PCV37 User Installations and Maintenance Manual UK version Domestic Hot Water Heat Pump Monobloc type...

Страница 2: ...7 4 Securing and connections of this appliance 17 7 5 Hydraulic connections 17 7 6 Connection the piping for domestic hot water 17 7 7 Integration with solar thermal system only for EKHHEU200PCV37 and...

Страница 3: ...not play with the appliance This appliance may be used by children 8 years of age or older and those with reduced physical sensory or mental capacity or lack of experience or knowledge if they are pro...

Страница 4: ...a reliable fixing means This product is designed to be used at a maximum altitude of 2000 m Refer to description and illustrations in paragraphs 7 1 Preparation of place of installation on page 14 7...

Страница 5: ...the circuit must not exceed 1 0 MPa 10 bar and its temperature must not exceed 80 C Refer to description and illustrations in the 7 5 Hydraulic connections on page 17 and 7 7 Integration with solar th...

Страница 6: ...water open the hot water taps and then operate the drain valve of the safety device The pressure relief valve must be operated regularly to remove scale deposits and to ensure that it is not blocked T...

Страница 7: ...ls for its products in compliance with EU WEEE standards 2012 19 EU RoHS 2011 65 EU This product complies with EN12897 2016 standard Water supply Specification for indirectly heated unvented closed st...

Страница 8: ...truck The packed equipment can be placed horizontally and back down to facilitate undoing the anchoring screws Unpacking must done carefully so as not to damage the equip ment casing if using knives o...

Страница 9: ...complies with part G3 of the Building Regulations For that the unit is factory equipped with a T P safety relief valve set 90 C 7bar and is supplied with a G3 kit composed by a 1x PRSV Pressure reduci...

Страница 10: ...coil Inlet 3 4 G Only for models EKHHEU200PCV37 EKHHEU260PCV37 13 Prearrangement for solar coil outlet 3 4 G Only for models EKHHEU200PCV37 EKHHEU260PCV37 14 Steel tank with vitreous enamel coating a...

Страница 11: ...80 160 160 620 628 R 310 R 3 8 8 fig 7 MODEL EKHHEU200PCV37 EKHHEU260PCV37 EKHHEU200CV37 EKHHEU260CV37 UM A 250 250 250 250 mm B 490 490 490 490 mm C 600 600 mm D 705 785 705 785 mm E 877 1162 877 116...

Страница 12: ...450 m3 h Available external static pressure 117 117 117 117 Pa Ducts diameter 160 160 160 160 mm Refrigerant circuit Compressor Rotary Refrigerant R134a Refrigerant charge 1 1 1 1 kg Evaporator Coppe...

Страница 13: ...r animals or serious dam age to property or the environment NB If the possibility of a product fault or failure can cause damage to people animals and property it is nec essary to provide for a separa...

Страница 14: ...installation The product must be installed in a suitable place i e to allow normal use and adjustment operations as well as routine and extraordinary maintenance The necessary operating space must the...

Страница 15: ...the spaces indicated in 7 1 the heat pump re quires adequate air ventilation Create a dedicated air channel as indicated in fig 13 Mandatory air inlet D 160 mm Internal compartment Exterior fig 13 Ex...

Страница 16: ...e loss To avoid the formation of condensation water insulate the air extraction pipes and the ducted air cover connections with a steam tight thermal covering of adequate thickness Install silencers i...

Страница 17: ...EKHHEU200PCV37 and EKHHEU260PCV37 mod els 11 29 9 10 20 12 13 8 fig 17 7 6 Connection the piping for domestic hot water f d b c d a 300 mm 300 mm 600 mm 600 mm 29 D1 D2 D1 D2 fig 18 29 T P safety reli...

Страница 18: ...2 tundishes supplied with the G3 kit to an appropriate drain according to the applicable legislation The following example shows discharge below fixed grat ing Building Regulation G3 section 3 61 giv...

Страница 19: ...work must have a continuous fall of 1 in 200 thereafter Maxi mum permitted equivalent length of 22 mm pipework is 9 m Each bend or elbow is equivalent to 0 8 m of pipe work The following figures fig 2...

Страница 20: ...d elec tronic controller not supplied that has a voltage free contact type output to be connected to the DIG 1 input of the equipment see 7 8 1 Remote connections To use the equipment in this configur...

Страница 21: ...conformity to the regulations in force and that the electrical system can suitably withstand the water heater s maximum power consumption val ues refer paragraph 4 2 for technical characteristics in...

Страница 22: ...k This function available only in some countries allows the equipment to be activated only when there is a signal coming from outside with prefer ential tariff If the electric contactor has a voltage...

Страница 23: ...r Probe T5AL250V Solar thermal cut out P4 P5 P3 HPS LPS fig 33 Equipment wiring diagram Description of connections available on the power board CN1 Air defrost and water NTC probes CN2 Evaporator inle...

Страница 24: ...Off button for switching on putting the product in standby mode unlocking buttons saving changes Set button to edit the parameter value confirm Increase button to increase the set point value paramet...

Страница 25: ...ly activated to prevent possible interactions with the water heater e g by children etc At the same time the backlighting level of the buttons and display decreases to reduce the unit s energy consump...

Страница 26: ...immediately 8 5 3 ELECTRIC The display shows the symbol With this mode only the heating element is used within the prod uct operating limits and is useful in situations of low inlet air temperatures...

Страница 27: ...the anti legionella temperature maintaining it for the set time If on reaching the anti legionella temperature the cycle is not performed correctly within 10 hours it is stopped and will be run again...

Страница 28: ...fault P04 P04 Evaporator inlet probe fault P05 P05 Evaporator outlet probe fault P06 P06 Compressor flow probe fault P07 P07 Solar collector probe fault P08 P08 High pressure protection E01 E01 Solar...

Страница 29: ...tons and pressing the and buttons together for 3 seconds The label of the first parameter is shown on the display with the letter A Pressing the button displays its value and pressing this button agai...

Страница 30: ...0 min 30 min Modifiable P5 Defrosting mode 0 compressor stop 1 hot gas 1 Modifiable P6 Electrical heater usage during defrosting 0 OFF 1 ON 0 Modifiable P7 Delay between two consecutive defrosting cyc...

Страница 31: ...king period in AUTO mode for heating rate calculation 10 80 min 30 min Modifiable P32 Temperature threshold for electrical heater usage in AUTO mode 0 20 C 4 C Modifiable P33 Electronic expansion valv...

Страница 32: ...ion of the air for the calculation of the setpoint 1 25 C 4 C Modifiable P61 Temperature difference 2 of evaporation of the air for the calculation of the setpoint 1 25 C 2 C Modifiable P62 Temperatur...

Страница 33: ...he equipment from the mains drain part of the water contained in the tank approx 50 then refill it and switch the equipment on again in ECO mode The heat pump remains on without ever stopping Without...

Страница 34: ...powering it fig 35 10 2 Heating element safety thermostat reset This equipment has a manual reset safety thermostat connect ed in series with the heating element immersed in water which interrupts the...

Страница 35: ...tself instead of the tank The boiler has two an odes one fitted in the lower part of the tank and one fitted in the upper part of the tank area more subject to corrosion The integrity of the Mg anodes...

Страница 36: ...tions provided for by cur rent legislation The main materials that make up the equipment in question are steel magnesium plastic copper aluminum polyurethane 13 PRODUCT SHEET Descriptions u m EKHHEU20...

Страница 37: ...0 1 2 3 4 2 3 4 5 6 7 8 9 10 P kW Q L min DTin 5K DTin 10K DTin 15K Q L min DTin 5K DTin 10K DTin 15K P kW fig 39 0 5 10 15 20 2 3 4 5 6 7 8 9 10 H mbar Q L min Q L min DH mbar fig 40 LEGEND P kW sola...

Страница 38: ...Q L min DTin 5K DTin 10K DTin 15K Q L min DTin 5K DTin 10K DTin 15K P kW fig 41 0 5 10 15 20 2 3 4 5 6 7 8 9 10 H mbar Q L min Q L min DH mbar fig 42 LEGEND P kW solar panel thermal power Tin K diffe...

Страница 39: ...Q L min DTin 5K DTin 10K DTin 15K Q L min DTin 5K DTin 10K DTin 15K P kW fig 43 0 5 10 15 20 2 3 4 5 6 7 8 9 10 H mbar Q L min Q L min DH mbar fig 44 LEGEND P kW solar panel thermal power Tin K diffe...

Страница 40: ...2023 11 Cod 3540000930 Rev 03 Copyright 2023 Daikin...

Отзывы: