Installation manual

25

EKHBX016BB3V3S

Indoor unit for air to water heat pump system

4PW62598-1 – 10.2010

8.5.

Initial start-up at low outdoor ambient 
temperatures

During initial start-up and when water temperature is low, it is
important that the water is heated gradually. Failure to do so may
result in cracking of concrete floors due to rapid temperature change.
Please contact the responsible cast concrete building contractor for
further details.

To do so, the lowest leaving water set temperature can be decreased
to a value between 15°C and 25°C by adjusting the field setting [9-01]
(heating set point lower limit). Refer to 

"8.9. Field settings" on

page 26

.

8.6.

Pre-operation checks

Checks before initial start-up

After the installation of the unit, check the following before switching
on the circuit breaker:

1

Installation

Check that the unit is properly installed to avoid abnormal noises
and vibrations when starting the unit.

2

Field wiring

Make sure that the field wiring between local supply panel and
indoor unit, outdoor unit and indoor unit, indoor unit and valves
(when applicable), indoor unit and room thermostat (when
applicable), and indoor unit and domestic hot water tank has
been carried out according to the instructions described in the
chapter 

"7. Electrical wiring work" on page 17

, according to the

wiring diagrams and according to the applicable legislation.

3

Fuses or protection devices

Check that the fuses or the locally installed protection devices
are of the size and type specified in the chapter 

"12. Technical

specifications" on page 50

. Make sure that neither a fuse nor a

protection device has been bypassed.

4

Backup heater circuit breaker F1B/F3B

Do not forget to turn on the backup heater circuit breaker F2B in
the switch box (F1B/F3B depends on the backup heater type).
Refer to the wiring diagram.

5

Booster heater circuit breaker F2B

(1)

Do not forget to turn on the booster heater circuit breaker F2B in
the switch box (applies only to units with optional domestic hot
water tank).

6

Earth wiring

Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.

7

Internal wiring

Visually check the switch box on loose connections or damaged
electrical components.

8

Fixation

Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.

9

Damaged equipment

Check the inside of the unit on damaged components or
squeezed pipes.

10

Refrigerant leak

Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.

11

Power supply voltage

Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.

12

Pipe size and pipe insulation

Be sure that correct pipe sizes are installed and that the
insulation work is properly executed.

13

Stop valves

Make sure that the stop valves on the outdoor unit (gas and
liquid) are fully open.

14

Air purge valve

Make sure the air purge valve is open (at least 2 turns).

15

Pressure relief valve

Check if the backup heater is completely filled with water by
operating the pressure relief valve. It should purge water instead
of air.

16

Water leak

Check the inside of the unit on water leakage. in case there is a
water leakage close the water inlet and water outlet shut-off
valves and call your local dealer.

17

Shut-off valves

Make sure that the shut-off valves are correctly installed and
fully open.

8.7.

Powering up the indoor unit

When power supply to the indoor unit is turned on, "

88

" is displayed

on the user interface during its initialisation, which might take up to 30
seconds. During this process the user interface cannot be operated.

8.8.

Setting the pump speed

In case a pump with flow control is used, it shall be set at constant
flow. Refer to the technical data for the internal pressure of the
hydrobox.

INFORMATION

If leaving water temperature is set between 15°C and
25°C, heating is performed by the backup heater only.

INFORMATION

The function underfloor heating screed dry-out program
offers the possibility to execute automatically the gradual
heat up. See 

"9.4. 

Underfloor heating screed dry-out

program" on page 43

.

DANGER

Switch off all relevant power supply before making any
connections.

(1) Only applicable for tank with built-in electrical booster heater (EKHW*).

NOTICE

Operating the system with the backup heater not
completely filled with water will damage the backup
heater!

NOTICE

Operating the system with closed valves will damage
the pump!

Содержание EKHBX016BB3V3S

Страница 1: ...INSTALLATION MANUAL EKHBX016BB3V3S Indoor unit for air to water heat pump system...

Страница 2: ...35 48 142 101 502 2 3 4 5 48 39 96 361 1 1 4 1 1 4 MBSP 895 922 830 469 260 B B T T 350 300 500 2x 2x 1x 1x 1x 1 2 3 4 5 30 90 2 1 3 4 1 2 3 4...

Страница 3: ...condo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za d...

Страница 4: ...cable 20 Connection of the valve control cables 20 Connection of the bottom plate heater 21 Connection of the pump 21 Connection to a bene t kWh rate power supply 21 7 4 Relocation of the digital cont...

Страница 5: ...eration of the unit always contact your local dealer for advice and information Improper installation or attachment of equipment or accessories could result in electric shock short circuit leaks re or...

Страница 6: ...the indoor unit and allows remote alarm output heating cooling ON OFF output bivalent operation permission signal for the auxiliary boiler or additional external backup heater permission signal Refer...

Страница 7: ...oom thermostat optional Pump operation and space heating When the room thermostat T is connected to the indoor unit the pump 5 will operate when there is a heating request from the room thermostat and...

Страница 8: ...stic water heating mode 2 Only applicable for tank with built in electrical booster heater EKHW INFORMATION Details on pump con guration can be found under 8 3 Pump operation con guration on page 24 N...

Страница 9: ...application without the room thermostat connected to the indoor unit but with the heating only room thermostat set heating only controlling the oor heating and the heating cooling thermostat set heat...

Страница 10: ...ays provided by the domestic hot water tank which is connected to the Daikin indoor unit The auxiliary boiler must be integrated in the piping work and in the eld wiring according to the illustrations...

Страница 11: ...o as to achieve the target leaving water temperature as set on the user interface When weather dependent operation is active the water temperature is determined automatically depending on the outdoor...

Страница 12: ...icker inside indoor unit cover 5 Indoor unit cover xing screw INFORMATION The advantage of the dual set point control is that the heat pump will can operate at the lowest required leaving water temper...

Страница 13: ...access to the switch box components e g to connect the eld wiring the switch box service panel can be removed Thereto loosen the front screws and unhitch the switch box service panel 5 2 Main compone...

Страница 14: ...ackup heater thermal protector The backup heater is equipped with a thermal protector The thermal protector is activated when the temperature becomes too high 18 Backup heater thermal fuse The backup...

Страница 15: ...the hydrobox unit on a rm wall and not in nor close to a sound sensitive environment e g bedroom NOTICE The electrical wiring diagram can be found on the inside of the switch box cover R4T H2O t R3T t...

Страница 16: ...vessels Where acidic or alkaline vapour is present 6 2 Dimensions and service space Unit of measurement mm Dimensions of the unit see gure 3 1 Flexible drain hose 2 Water outlet connection 3 Water in...

Страница 17: ...ed with the drain pan kit 6 6 Refrigerant pipework For all guidelines instructions and speci cations regarding refrigerant pipework between the indoor unit and the outdoor unit please refer to the out...

Страница 18: ...door unit If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end...

Страница 19: ...er volume in the water circuit is 100 l In this example no action or adjustment is required INFORMATION In most applications this minimum water volume will have a satisfying result In critical process...

Страница 20: ...WORK 7 1 Precautions on electrical wiring work NOTICE Be careful not to deform the unit piping by using excessive force when connecting the piping Deformation of the piping can cause the unit to malfu...

Страница 21: ...y contact S3S Dual set point 2 contact S4S Dual set point 1 contact SS1 DIP switch TR1 Transformer 24 V for PCB V1S Spark suppression 1 V2S Spark suppression 2 X1M X9M Terminal blocks X6Y X9B Connecto...

Страница 22: ...erminal 3 Fix the cable with cable ties to the cable tie mountings to ensure strain relief Item Description Required number of conductors Maximum running current 1 Power supply cable for outdoor unit...

Страница 23: ...to ensure strain relief 3 Depending on the required pump operation set DIP switch SS2 3 and eld setting F 00 See 8 3 Pump operation con guration on page 24 and eld setting F 00 in F Option setup on pa...

Страница 24: ...ill not operate Possible types of bene t kWh rate power supply Possible connections and requirements to connect the equipment to such power supply are illustrated in the gure below 1 Bene t kWh rate p...

Страница 25: ...enabled the screed dry out function can not be enabled When connecting the equipment to a bene t kWh rate power supply change eld setting d 01 When bene t kWh rate power supply is of type 1 or indoor...

Страница 26: ...ECTRIC SHOCK See 2 General safety precautions on page 2 WARNING Switch off the power supply before opening the switch box service panel and making any changes to the DIP switch settings 1 4 3 2 1 ON O...

Страница 27: ...on the pump will then run every 5 minutes during 3 minutes to check the water temperature UI UI UI SS2 3 ON wiring on when space heating or cooling is on y UI UI UI Heating only thermostat SS2 3 ON w...

Страница 28: ...k the switch box on loose connections or damaged electrical components 8 Fixation Check that the unit is properly xed to avoid abnormal noises and vibrations when starting up the unit 9 Damaged equipm...

Страница 29: ...ppropriate eld setting second code 4 Press the pfi button and pfj button to change the set value of the select eld setting 5 Save the new value by pressing the pr button 6 Repeat step 2 through 4 to c...

Страница 30: ...point at high ambient temperature Hi2_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi2_A Note that the Hi2_Ti value should b...

Страница 31: ...eration is only allowed if heat pump is out of operation range of heat pump domestic water heating mode TA 5 03 or TA 35 C or domestic hot water temperature is 2 C lower then the heat pump OFF tempera...

Страница 32: ...ay See operation manual When setting 4 03 2 the booster heater will be allowed to operate when TA 5 03 independent of the status of 5 02 If bivalent operation is enabled and permission signal for auxi...

Страница 33: ...and the backup heater during domestic hot water operation When the space heating priority function is enabled it is assured that the full capacity of the heat pump is used as much as possible for spa...

Страница 34: ...cheduled storage 6 03 1 scheduled reheat 6 05 1 disinfection function 2 01 1 activated A Scheduled storage operation activated at 6 04 heat up domestic hot water untill domestic hot water user interfa...

Страница 35: ...t the domestic hot water set point is according to your requirements Start with a low domestic hot water storage set point and only increase if you feel that the domestic hot water supply temperature...

Страница 36: ...t set point can be a xed value or weather dependent The second set point heating 7 03 should be linked to the heat emitters which requires the highest set point in heating mode Example fan coil unit T...

Страница 37: ...y applicable in heating mode INFORMATION When heat pump is active in domestic water heating mode the delay time of booster heater is 8 03 When heat pump is not active in domestic water heating mode th...

Страница 38: ...is eld setting allows for distinction between detection of an alarm and detection of a power failure to the unit Bivalent operation Applies only to installations with an auxiliary boiler alternating o...

Страница 39: ...on 5 when bivalent operation function is enabled Daikin shall not be held liable for any damage resulting from failure to observe this rule INFORMATION In case the outdoor unit is NOT ERLQ_CA or ERHQ_...

Страница 40: ...A Outdoor temperature R Range L Local shift value 1 00 1 04 Applicable eld settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01...

Страница 41: ...mperature below which the bottom plate heater will be activated by indoor unit in order to prevent ice build up in the bottom plate of the outdoor unit at lower outdoor temperatures F 03 Bottom plate...

Страница 42: ...heater EKHTS 4 03 5 60 xed 5 C 03 Set point only in combination with domestic hot water tank with built in electrical booster heater EKHW 4 03 5 70 55 80 5 C 04 Interval only in combination with dome...

Страница 43: ...time storage start time 1 00 0 00 23 00 1 00 hour 05 Scheduled time reheat or continuous reheat 0 OFF 0 1 2 1 06 Scheduled time reheat start time 15 00 0 00 23 00 1 00 hour 07 Domestic hot water rehe...

Страница 44: ...04 Not applicable Do not change the default value 0 c Read only C Setup on EKRP1HB digital I O PCB 00 Solar priority mode setting 0 0 1 1 01 Alarm output logic 0 0 1 1 02 X1 X2 function Bivalent opera...

Страница 45: ...point of selected action number F 05 25 0 d 15 55 1 C 07 Time of selected action number F 05 0 d 0 72 12 hour 08 Under oor heating screed dry out program enabled disabled 0 OFF 0 1 1 09 Latest action...

Страница 46: ...displayed To start the test run operation press the y button To test the domestic water heating operation push the v button The test run operation will start without pressing the y button 3 The test r...

Страница 47: ...y out program as follows 1 Set in F 08 Under oor heating screed dry out program enabled disabled to 1 enabled 2 When nished press the z button to exit the FIELD SET MODE 2 Activate 1 Push the z button...

Страница 48: ...applications with domestic hot water tank only and K4M by use of an ohmmeter All contacts of these contactors must be in open position DANGER ELECTRIC SHOCK Before carrying out any maintenance or rep...

Страница 49: ...ring and immediately after operation See 2 General safety precautions on page 2 INFORMATION For problems related to the optional solar kit for domestic water heating refer to the troubleshooting in th...

Страница 50: ...he backup heater operation status eld setting 4 00 is turned on see 8 9 Field settings on page 26 Check whether or not the thermal protector of the backup heater has been activated refer to Main compo...

Страница 51: ...tlet water thermistor is giving the correct read out A1 Indoor unit PCB defective Contact your local dealer A5 Too low during cooling operation or too high during heating operation refrigerant tempera...

Страница 52: ...your local dealer U3 Under oor heating screed dry out program has been stopped by another error or by pushing operation off button or by power failure The error can only be reset in the test mode as...

Страница 53: ...ter drain hose nipple refrigerant liquid side 9 5 mm 3 8 inch refrigerant gas side 15 9 mm 5 8 inch Expansion vessel volume 10 l maximum working pressure MWP 3 bar Internal water volume 5 5 l Pressure...

Страница 54: ......

Страница 55: ......

Страница 56: ...4PW62598 1 10 2010 Copyright 2010 Daikin...

Отзывы: