EKHBRD011~Y1
Indoor unit for air to water heat pump system
4PW54465-1C
Installation manual
22
See also
"[2] Automatic setback function" on page 20
for more
information about the setback operation.
■
[5-02] Leaving water setback temperature
■
[5-03] Room setback temperature
[6] Option setup
■
[6-00] Domestic hot water tank option
If the domestic hot water tank is installed, its operation must be
enabled by field setting. Default [6-00]=0 which means no tank is
installed. Set [6-00] to 1 if the optional domestic hot water tank is
installed.
■
[6-01] External room thermostat option
If the optional external room thermostat is installed, its operation
must be enabled by field setting. Default [6-01]=0, which means
no external room thermostat is installed. Set [6-01] to 1 if the
optional external room thermostat is installed.
The external room thermostat only gives an ON/OFF signal to
the heat pump based on the room temperature. Because it does
not give continuous feedback information to the heat pump, it is
supplementary to the remote controller room thermostat
function. To have a good control of the system and avoiding
frequent ON/OFF it is advised to use the automatic weather
dependent set point operation.
■
[6-02] Heater kit
Once installed, you can activate the heater kit by changing field
setting [6-02]=1.
From that moment on, the heat pump system will take the heater
kit into account whilst deciding operation. When the heater is
actually operating, the heater symbol
(
is shown on the remote
controller. There is no step 1-2 indication.
For more information, see installation manual of the heater kit,
especially concerning the test run for the heater kit.
■
[6-04] Benefit kWh rate power supply mode
If benefit kWh rate power supply is used, the mode must be
selected. Default [6-04]=0 which means no benefit kWh rate
power supply is used.
Set [6-04] to 1 to use benefit kWh rate power supply mode 1
(normally closed contact which will open when the power supply
is interrupted), or set [6-04] to 2 to use benefit kWh rate power
supply mode 2 (normally opened contact which will close when
the power supply is interrupted).
See
"Connection to a benefit kWh rate power supply" on page 16
more information.
[7] Option setup
■
[7-00] Bottom plate heater option
An optional bottom plate heater can be installed in your outdoor
unit. In case an ERRQ* outdoor unit (special model with
freeze-up countermeasures) is installed, the unit will have the
bottom plate heater already standard installed.
If the bottom plate heater is installed, its operation must be
enabled by field setting. Default [7-00]=0 which means no
bottom plate heater is installed. Set [7-00] to 1 if the bottom
plate heater is installed.
■
[7-02] See chapter
"Multiple set point control" on page 27
■
[7-03] See chapter
"Multiple set point control" on page 27
■
[7-04] See chapter
"Multiple set point control" on page 27
[8] Option setup
■
[8-00] Remote controller temperature control
When using the remote control delivered with the unit, 2 types of
temperature control are possible. Default [8-00]=1 which means
that the remote controller is used as room thermostat, so the
remote controller can be placed in the living room to control the
room temperature. Set [8-00] to 0 to use the unit in leaving water
temperature control.
■
[8-01] Auto restart
When a power failure occurred and the power returns to the unit,
the system will automatically restore it's settings and restart.
This is the default setting [8-01]=1. To disable this auto restart
function, set [8-01] to 0.
■
[8-02] Emergency operation
During emergency mode, heating is only done by the heater kit,
not by the heat pump.
Activation of emergency mode is done by changing field setting
[8-02]=1.
Activating the emergency mode will stop the heat pump
operation. The pump of the indoor unit will be started, but
heating itself is done by the heater kit. If there are no error
conditions in leaving or returning water thermistors, the heater
kit can start to follow emergency operation.
■
[8-03] Quiet mode
The unit has a quiet mode functionality for which 3 levels can be
selected:
■
[8-03]=1 low noise level 1 (default)
■
[8-03]=2 low noise level 2
■
[8-03]=3 low noise level 3
Activating this quiet mode is done by pushing the QUIET MODE
button on the remote controller or through the schedule timer.
■
[8-04] Freeze-up prevention
The unit has a freeze-up prevention functionality for which 3
levels can be selected:
■
[8-04]=0 prevention level 0 (default: no prevention)
■
[8-04]=1 prevention level 1
■
[8-04]=2 prevention level 2
The freeze-up prevention is only active when the unit is in
thermo OFF condition. If prevention level 1 is enabled, the
freeze-up prevention will start if the outdoor ambient
temperature <4°C and if leaving or return water temperature
<7°C. For prevention level 2, the freeze-up prevention will start
as soon as the ambient temperature <4°C.
For both cases the pump will operate and if leaving or return
water <5°C for 5 minutes the unit will start up to prevent too low
temperatures.
It is advised to enable freeze-up prevention if the indoor unit is
located in a colder ambient room (e.g. garage, ...) to prevent
water freeze-up.
NOTE
When enabling the domestic hot water tank option
be aware that the advised default settings become
active:
■
[1-00]=1=automatic night storage
■
[4-00]=1=disinfection function
NOTE
When power returns after a power supply failure, the
auto restart function reapplies the remote controller
settings at the time of the power supply failure. It is
therefore recommended to leave the auto restart
function enabled. Note that with the function disabled
the schedule timer will not be activated when power
returns to the unit after a power supply failure. Press
the
pr
button to enable the schedule timer again.
NOTE
Before activating emergency operation, be sure to
activate the heater kit. The heater will stay in
emergency mode until the field setting is set back
to default [8-02]=0.