background image

EKHBH/XE008BA

Indoor unit for air to water heat pump system

4PW56301-1A

Installation manual

17

Piping insulation

The complete water circuit, inclusive all piping, must be insulated to
prevent condensation during cooling operation and reduction of the
cooling and heating capacity.

If the temperature is higher than 30°C and the humidity is higher than
RH 80%, then the thickness of the sealing materials should be at
least 20 mm in order to avoid condensation on the surface of the
sealing.

Field wiring

Overview

The illustration below gives an overview of the required field wiring
between several parts of the installation. Refer also to 

"Typical

application examples" on page 4

.

NOTE

During filling, it might not be possible to remove all
air in the system. Remaining air will be removed
through the automatic air purge valves during first
operating hours of the system. Additional filling
with water afterwards might be required.

The water pressure indicated on the manometer
will vary depending on the water temperature
(higher pressure at higher water temperature).
However, at all times water pressure should
remain above 0.3 bar to avoid air entering the
circuit.

The unit might dispose some excessive water
through the pressure relief valve.

Water quality must be according to EU directive
98/83 EC.

WARNING

A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local and national legislation.

Switch off the power supply before making any
connections.

Use only copper wires.

Never squeeze bundled cables and make sure that it
does not come in contact with the piping and sharp
edges.

Make sure no external pressure is applied to the
terminal connections.

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance
with the wiring diagram supplied with the unit and the
instructions given below.

Be sure to use a dedicated power supply. Never use a
power supply shared by another appliance.

Be sure to establish an earth. Do not earth the unit to
a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.

Be sure to install an earth leakage circuit breaker in
accordance with relevant local and national
regulations. Failure to do so may cause electrical
shock or fire.

Be sure to install the required fuses.

A

Single power supply for 
outdoor unit, backup 
heater and booster 
heater

G

3-way valve for domestic 
hot water tank (optional)

H

2-way valve for cooling 
mode (field supply)

B

Outdoor unit

C

Bottom plate heater 

EKBPHT

(a)

(a) Bottom plate heater is only applicable in combination with ERLQ or in case of 

optional EKBPHT kit.

I

Domestic hot water tank 
(optional)

D

Backup heater

J

Booster heater 
(optional)

E

Indoor unit

F

Room thermostat 
(optional)

K

User interface (digital 
controller)

Item

Description

Required 
number of 
conductors

Maximum 
running current

1

Power supply cable for outdoor 
unit

2+GND

(a)

(a) Refer to nameplate on outdoor unit.

2

Indoor unit power supply and 
communication cable

3+GND

(b)

(b) Cable section 2.5 mm

2

3

Power cable for bottom plate 
heater

2

(c)

(c) Minimum cable section 1.5 mm

2

4

Power supply cable for backup 
heater

2+GND or 

3+GND

(d)

(d) See table under 

"Connection of the backup heater power supply" on page 18

.

5

Room thermostat cable

3 or 4

100 mA

(e)

(e) Minimum cable section 0.75 mm

2

6

3-way valve control cable

2+GND

100 mA

(e)

7

2-way valve control cable

2+GND

100 mA

(e)

8

Booster heater power supply 
and thermal protection cable

4+GND

(b)

9

Thermistor cable

2

(f)

(f)

The thermistor and connection wire (12 m) are delivered with the domestic hot 
water tank.

10

Booster heater power supply 
cable

2+GND

13 A

11

User interface cable

2

(g)

(g) Cable section 0.75 mm

2

 till 1.25 mm

2

, maximum length: 500 m.

CAUTION

Select all cables and wire sizes in accordance with
relevant local and national regulations.

T

I

M

M

2

B

1

4

5

D

6

7

8

9

3

E

A

10

F

K

I

C

J

H

G

11

Содержание EKHBHE008BA3V3

Страница 1: ...INSTALLATION MANUAL EKHBHE008BA3V3 EKHBXE008BA3V3 Indoor unit for air to water heat pump system For installation WITH restricted power supply condition 6 kW ...

Страница 2: ...3 4 35 48 142 101 502 2 3 4 5 48 39 96 361 1 1 2 FBSP 1 MBSP 895 922 830 469 260 B B T T 2 350 300 500 1 2x 2x 1x 1x 1x 1 2 3 4 5 30 90 1 2 3 4 ...

Страница 3: ...ERLQ heat pumps These units are designed for wall mounted indoor installation See Selecting an installation location on page 12 The units can be combined with Daikin fan coil units floor heating applications low temperature radiators Daikin domestic water heating applications and Daikin solar kit for domestic hot water applications Heating cooling units and heating only units The unit range consis...

Страница 4: ...r operation Emergency backup heater operation occurs because of User request to heat up water to the space heating loops The temperature of this water is too low and is out of the operation range during initial start up for example Refer to Initial start up at low outdoor ambient temperatures on page 22 and Re start at low outdoor ambient temperatures on page 22 During heating operation the water ...

Страница 5: ...on as the refrigerant pipes may be hot or cold depending on the condition of the refrigerant flowing through the refrigerant piping compressor and other refrigerant cycle parts Your hands may suffer burns or frostbite if you touch the refrigerant pipes To avoid injury give the pipes time to return to normal temperature or if you must touch them be sure to wear proper gloves Do not touch the intern...

Страница 6: ...b the control system and cause malfunction of the equipment Where flammable gases may leak where carbon fibre or ignitable dust is suspended in the air or where volatile flammables such as thinner or gasoline are handled Such gases may cause a fire Where the air contains high levels of salt Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vap...

Страница 7: ...r tank optional 2 Indoor unit 3 Heat exchanger 11 Booster heater 4 Pump 12 Heat exchanger coil 5 Shut off valve FHL1 3 Floor heating loop 6 Collector field supply T1 3 Individual room thermostat optional 7 Shut off valve 8 Motorised 3 way valve delivered with domestic hot water tank M1 3 Individual motorised valve to control loop FHL1 field supply 9 By pass valve field supply NOTE Details on pump ...

Страница 8: ...g mode to achieve the target leaving water temperature With the unit in heating mode the 2 way valve 13 is open Hot water is provided to both the fan coil units and the floor heating loops With the unit in cooling mode the 2 way valve 13 is closed to prevent cold water running through the floor heating loops FHL The ON OFF setting of the heating cooling operation is done by the user interface on t...

Страница 9: ...tarts operating depending on the outdoor temperature status of permission signal for the auxiliary boiler When the permission is given towards the boiler the space heating operation by the EKHB unit will be automatically switched off For more details see field setting C 02 C 04 CAUTION Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant European a...

Страница 10: ...ler will operate so as to achieve the target leaving water temperature as set on the boiler controller Never set the target leaving water temperature set point on the boiler controller above 55 C Make sure to only have 1 expansion vessel in the water circuit An expansion vessel is already premounted in the Daikin indoor unit NOTE Make sure to configure the DIP switch SS2 3 on the PCB of the EKHB s...

Страница 11: ...tat Status signal active not active from the mixing station It is the installers responsibility to make sure no unwanted situations can occur e g too high water temperatures towards floor heating loops etc Daikin does not offer any type of mixing station Dual set point control only provides the possibility to use two set points When only zone A request heating zone B will be fed with water at a te...

Страница 12: ...s the installer and user to set up use and maintain the unit 8 Refrigerant liquid connection 9 Refrigerant gas connection 10 Shut off valves accessory The shut off valves on the water inlet connection and water outlet connection allow isolation of the indoor unit water circuit side from the residential water circuit side This facilitates draining and filter replacement of the indoor unit 11 Water ...

Страница 13: ...ose The actual outlet of the pressure relief valve Make sure to provide a proper drain Switch box main components 1 Backup heater contactors K1M and K5M 2 Main PCB The main PCB Printed Circuit Board controls the functioning of the unit 3 Booster heater contactor K3M only for installations with domestic hot water tank 4 Booster heater circuit breaker F2B only for installations with domestic hot wat...

Страница 14: ... not intended for use in a potentially explosive atmosphere Do not install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit must be covered Take care that in the event of a water leak water can not cause any damage to the installation space and surroundings Do not place any objects or equipment on top of the unit B...

Страница 15: ...ee packing on the wall and mark the fixation positions 2 on top T and 2 at the bottom B Make sure that the marks 2 by 2 are completely level and the dimensions of the marks are corresponding according to figure 4 When the unit is not installed level air might get trapped in the water circuit resulting in malfunctioning of the unit Pay special attention to this when installing an EKHBX model to pre...

Страница 16: ...nections and leaks NOTE The unit is only to be used in a closed water system Application in an open water circuit can lead to excessive corrosion of the water piping NOTE Before continuing the installation of the unit check the following points The maximum water pressure 3 bar static pressure of pump The maximum water temperature is 65 C safety device setting Two shut off valves are delivered with...

Страница 17: ...this case refer to Re start at low outdoor ambient temperatures on page 22 Repeated forced defrost stops can in some cases cause severe ice build up on the outdoor unit This will lead to reduced unit performance In most applications this minimum water volume will have a satisfying result In critical processes or in rooms with a high heat load though extra water volume might be required NOTE When c...

Страница 18: ...pecting the water in and outlet If air moisture or dust gets in the water circuit problems may occur Therefore always take into account the following when connecting the water circuit Use clean pipes only Hold the pipe end downwards when removing burrs Cover the pipe end when inserting it through a wall so that no dust and dirt enter Use a good thread sealant for the sealing of the connections The...

Страница 19: ...ring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Be sure to use a dedicated power supply Never use a power supply shared by another appliance Be sure to establish an earth Do not earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Be sure to install an earth leakage circ...

Страница 20: ...s are provided at the bottom of the switch box Fix all cables using cable ties field supply A dedicated power circuit is required for the backup heater Installations equipped with a domestic hot water tank optional require a dedicated power circuit for the booster heater Please refer to the domestic hot water tank installation manual Connection of the indoor unit power supply and communication cab...

Страница 21: ...field setting F 00 See Pump operation configuration on page 21 and field setting F 00 in F Option setup on page 29 Connection of the valve control cables Valve requirements Power supply 230 V AC Maximum running current 100 mA Wiring the 2 way valve 1 Using the appropriate cable connect the valve control cable to the X2M terminal as shown on the wiring diagram 2 Fix the cable s with cable ties to t...

Страница 22: ...mounted indoors NOTE Be careful not to distort the shape of the lower part of the digital controller by over tightening the mounting screws 1 Unit 2 Rear part of the digital controller 3 Front part of the digital controller 4 Wired from the rear 5 Wired from the top 6 Notch the part for the wiring to pass through with nippers etc 1 P1 P2 1 1 6 2 3 4 5 P1 P2 16a 16 16a 16 NOTE When wiring run the w...

Страница 23: ...d off i e chattering and thereby impacting the lifetime of the pump When the room thermostat is connected to the indoor unit the heating and cooling schedule timers are never available Other schedule timers are not affected For more information on the schedule timers refer to the operation manual When the room thermostat is connected to the indoor unit and the button or y button is pressed the cen...

Страница 24: ...ater circuit breaker F1B F3B Do not forget to turn on the backup heater circuit breaker F2B in the switchbox F1B F3B depends on the backup heater type Refer to the wiring diagram 4 Booster heater circuit breaker F2B Do not forget to turn on the booster heater circuit breaker F2B in the switch box applies only to units with optional domestic hot water tank installed 5 Earth wiring Make sure that th...

Страница 25: ...ue displayed to the right 1 2 Press the bgi button to select the appropriate field setting first code 3 Press the bgj button to select the appropriate field setting second code 4 Press the pfi button and pfj button to change the set value of the select field setting 5 Save the new value by pressing the pr button 6 Repeat step 2 through 4 to change other field settings as required 7 When finished p...

Страница 26: ...ion function is turned on 1 or off 0 2 02 Start time time of the day at which the domestic hot water should be heated 2 03 Set point high water temperature to be reached 2 04 Interval time period defining how long the set point temperature should be maintained Tt Target water temperature TA Ambient outdoor temperature Shift value Lo_Ti Lo_A Hi_A TA Tt 05 00 05 Hi_Ti Shift value CAUTION The disinfe...

Страница 27: ... i e the heat pump ON temperature and stopped i e the heat pump OFF temperature When the domestic hot water temperature drops below the heat pump ON temperature THP ON heating of the domestic hot water by the heat pump can be started As soon as the domestic hot water temperature reaches the heat pump OFF temperature THP OFF or the user set point temperature TU heating of the domestic hot water by ...

Страница 28: ... point for domestic hot water TU Refer to field setting 7 00 and the operation manual to select preferable set point If this high domestic hot water temperature can be a potential risk for human injuries a mixing valve field supply shall be installed at the hot water outlet connection of the domestic hot water tank This mixing valve shall secure that the hot water temperature at the hot water tap ...

Страница 29: ...ating set point lower limit minimum leaving water temperature for heating operation 9 02 Cooling set point upper limit maximum leaving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the set point before the compressor stops This function i...

Страница 30: ...eating by indoor unit will be stopped C 04 Bivalent hysteresis defines the temperature difference between bivalent ON temperature and bivalent OFF temperature Permission signal X1 X2 EKRP1HB D Restricted power supply condition mode Local shift value weather dependent D 02 is set to 1 by default The restricted power supply condition mode is enabled Do not change this value Local shift value weather...

Страница 31: ...h an outdoor unit ERLQ or in case the option bottom plate heater kit is installed F 02 Bottom plate heater ON temperature defines the outdoor temperature below which the bottom plate heater will be activated by indoor unit in order to prevent ice build up in the bottom plate of the outdoor unit at lower outdoor temperatures F 03 Bottom plate heater hysteresis defines the temperature difference bet...

Страница 32: ...ult value 0 OFF 0 1 2 02 Space heating off temperature 25 14 25 1 C 03 Booster heater operation 3 0 1 2 3 04 Not applicable 2 Read only 5 Equilibrium temperature and space heating priority temperature 00 Not applicable Do not change the default value 1 ON 0 1 01 Not applicable Do not change the default value 0 15 35 1 C 02 Not applicable Do not change the default value 0 OFF 0 1 03 Not applicable ...

Страница 33: ...t applicable Do not change the default value 0 0 1 2 3 01 Not applicable Do not change the default value 0 OFF 0 1 2 02 Not applicable Do not change the default value 1 03 Local shift value weather dependent 0 0 1 2 3 4 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet w...

Страница 34: ...indoor unit cover See Opening the indoor unit on page 9 Maintenance activities To display the last resolved error code push the z button 1 time Push the z button again 4 times to return to normal mode NOTE It is not possible to perform a test run if a forced operation from the outdoor unit is in progress Should forced operation be started during a test run the test run will be aborted DANGER ELECT...

Страница 35: ... TROUBLESHOOTING This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit This troubleshooting and related corrective actions may only be carried out by your local technician General guidelines Before starting the troubleshooting procedure carry out a thorough visual inspection of the unit and look for obvious defects such as loose connect...

Страница 36: ...BLE CAUSES CORRECTIVE ACTION There is air in the system Purge air Water pressure at pump inlet is too low Check on the manometer that there is sufficient water pressure The water pressure must be 1 bar water is cold Check that the manometer is not broken Check that the expansion vessel is not broken Check that the setting of the pre pressure of the expansion vessel is correct refer to Setting the ...

Страница 37: ... protector by pressing the reset button refer to Main components on page 10 for location of the reset button Check the reset button of the thermal protector If both the thermal protector and the controller are reset but the AA error code persists the backup heater thermal fuse has blown Contact your local dealer AC Booster heater thermal protector is open applies only to installations with a domes...

Страница 38: ... dealer PJ Failure of capacity setting Contact your local dealer U0 Refrigerant failure due to refrigerant leak Contact your local dealer U2 Main circuit voltage failure Contact your local dealer U4 Communication failure Contact your local dealer U5 Communication failure Contact your local dealer U7 Communication failure Contact your local dealer UA Communication failure Contact your local dealer ...

Страница 39: ...9 mm 5 8 inch Expansion vessel volume 10 l 10 l maximum working pressure MWP 3 bar 3 bar Pump type water cooled water cooled no of speed 3 3 Sound pressure level Refer to technical data Refer to technical data Internal water volume 5 5 l 5 5 l Pressure relief valve water circuit 3 bar 3 bar Operation range water side heating 15 50 C 15 50 C cooling 5 22 C Operation range air side heating 20 25 C 2...

Страница 40: ...4PW56301 1A Copyright 2009 Daikin ...

Отзывы: