background image

3

Connections of the Gateway to the configuration
computer

The connection of the configuration computer to the Gateway is
made to the 9-pole male connector at the back of the Gateway
labelled ‘config.’. This connection can be made by two different
cables:

a cable with a 9-pole female connector at both ends

a cable with one 9-pole female connector (to Gateway) and one
25-pole female connector (to the computer)

A program on a diskette delivered with the Kit can start the initial
configuration once the cable connects the Gateway to the
computer.

Remove the cable after configuration.

Connections to make for a cable with a 25-pole female

connector

Make the connections as listed:

Computer

Gateway (connector labelled 'config.')

25-pole female

9-pole female

2 TX

RX 2

3 RX

TX 3

7 GND

GND 5

Connections to make for a cable with two 9-pole female

connectors

Make the connections as listed:

Computer

Gateway (connector labelled 'config.')

9-pole female

9-pole female

3 TX

RX 2

2 RX

TX 3

5 GND

GND 5

Connections of the Gateway to the BMS

There are two possibilities to connect the BMS to the gateway:

using an RS-232 standard

using an RS-485 standard

RS-232 connection diagrams (Modbus-Jbus and BACnet)

The RS-232 connection to the supervisory system is standard in
Modbus-Jbus and BACnet. The BACnet Gateway has no other
options to make a connection.

Make the connection at the gateway side to the 9 pin male
connector labelled ‘modem’.

The connections you have to make depend on which cable you
use. The possible connections are listed:

Connections to make for a cable with a 25-pole female connector.
Make the connections as listed:

Supervisory system

Gateway (connector labelled 'modem')

25-pole female

9-pole female

2 TX

RX 2

3 RX

RX 3

7 GND

GND 5

Connections to make for a cable with two 9-pole female connectors.
Make the connections as listed:

Supervisory system

Gateway (connector labelled 'modem')

9-pole female

9-pole female

3 TX

RX 2

2 RX

TX 3

5 GND

GND 5

In any case, refer to the specifications of the supervisory system
for other possible connection types. However, the gateway only
manages the signals TX and RX.

RS-485 connection diagrams (only for Modbus-Jbus)

The RS-485 connection diagrams can only be used by Modbus-
Jbus.

The possible connections are listed:

Supervisory system

Gateway (connector labelled RS-422/RS-485)

GND 1
TX+/RX+ 4
TX-/RX- 5

The pinning from the supervisory system side is omitted because
it changes depending on the particular supervisory system being
utilised.

H

ARDWARE

 

CONFIGURATION

Opening the cover of the Gateway gives you access to the four
jumpers present on the card. The hardware configuration is made
by placing the jumpers in a specific way to enable different ports
and their options. The A, B, C, D jumpers are shown in the figure.
Read the instructions to enable a port or an option of a port.

How to enable the RS-232 serial port (‘modem’)
towards the supervisory system

This way the ‘RS-422/485’ modes and respective port are
disabled.

The table shows the position of the jumper and the possibility in
BACnet and Modbus-Jbus.

Jumper

Modbus

BACnet

A in 1-2

Yes

Yes

How to enable the ‘RS-422/485’ serial port towards
the supervisor

This way the RS-232 modes and the respective ‘modem’ port are
disabled.

The table shows the position of the jumper and the possibility in
BACnet and Modbus-Jbus.

Jumper

Modbus

BACnet

A in 2-3

Yes

No

Содержание EKBMSMBA

Страница 1: ...INSTALLATION MANUAL Gateway EKBMSMBA EKBMSBNA ...

Страница 2: ...1 Serial module µchiller compact line print out ala rm 1 ala rm 2 rx tx re set Gateway BMS ...

Страница 3: ...communication devices The Gateway a separate device that functions as a translator between the Modbus BACnet signals of the BMS or supervisory system and the protocol used by the chiller s address card The address card a card placed on each PCB of the chiller or a module placed inside the switchbox depending on the range of the chiller It identifies the chiller The Gateway can communicate with up ...

Страница 4: ...ire system could be damaged by the erroneous connection of a single wire Preferably insert the cables into the connectors with the Gateway switched off During the configuration phase strictly follow the instructions on the use of the relevant program Before installing the Gateway make sure you have installed the address cards correctly Follow the instructions in the installation manuals of the add...

Страница 5: ...emale connector Make the connections as listed Supervisory system Gateway connector labelled modem 25 pole female 9 pole female 2 TX RX 2 3 RX RX 3 7 GND GND 5 Connections to make for a cable with two 9 pole female connectors Make the connections as listed Supervisory system Gateway connector labelled modem 9 pole female 9 pole female 3 TX RX 2 2 RX TX 3 5 GND GND 5 In any case refer to the specif...

Страница 6: ...le shows the position of the jumper and the possibility in BACnet and Modbus Jbus Jumper Modbus BACnet C in 1 2 Yes Yes SOFTWARE CONFIGURATION MS DOS PROGRAM Installation of the configuration software for the Gateway System requirements for the PC to configure the Gateway 3 0 or higher DOS operating system RS 232 serial port Cable requirements for the PC to configure the Gateway cable termination ...

Страница 7: ...a rdbaccnf enter digitise for Modbus Jbus a readmb0 enter The PC screen will display the configuration present in the Gateway with the parameter relevant to the software version If the Gateway is not connected or does not answer following message will be displayed ERROR READING GATEWAY CONFIGURATION If so check the cable connection the Gateway power supply yellow LED ON signalling LED state com ne...

Страница 8: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE08535 1 ...

Отзывы: