
7 Installation
Installer reference guide
33
EKCB
EK2CB EKMBU EKMBUHCA9W1
Daikin Altherma low temperature monobloc
4P405544-1 – 2015.03
7.3.2
Precautions when mounting the outdoor
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
7.3.3
To provide the installation structure
Check the strength and level of the installation ground so that the
unit will not cause any operating vibration or noise.
Fix the unit securely by means of foundation bolts in accordance
with the foundation drawing.
INFORMATION
For information on the available options, contact your
dealer.
If the unit is installed directly on the floor, prepare 4 sets of M8 or
M10 anchor bolts, nuts and washers (field supply) as follows:
INFORMATION
The maximum height of the upper protruding part of the
bolts is 15 mm.
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the nuts rust easily.
a
283
740
<100
(mm)
<100
>300
In any case, provide at least 300 mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above
the maximum expected level of snow.
283
740
<150
<150
(mm)
>300
100
a
a
Maximum snowfall height
It is possible to install the unit on brackets to the wall:
>250/400
>300
>250/400
(mm)
a
a
Maximum snowfall height
Содержание EK2CB07CAV3
Страница 113: ...1 8 Field settings table Applicable units BLQ05CAV3 DLQ05CAV3 BLQ07CAV3 DLQ07CAV3 Notes 1 B 2 D 4P405542 1 2015 03 ...
Страница 121: ......
Страница 122: ...4P405544 1 2015 03 Copyright 2015 Daikin ...