5 Configuration
Installation manual
17
EHBH/X04+08DA
Daikin Altherma – Low temperature split
4P495266-1 – 2017.06
▪ In Weather dependent LWT setpoint mode, the scheduled actions
consist of desired shift actions, either preset or custom.
#
Code
Description
[2.1]
N/A
▪ 0: No
▪ 1: Yes
5.2.6
Configuration wizard: Additional zone
The most important settings for the additional leaving water zone
can be set here.
Emitter type
For more info about this functionality, see
"5.2.5 Configuration
wizard: Main zone" on page 16
.
#
Code
Description
[3.7]
[2‑0D]
▪ 0: Underfloor heating
▪ 1: Fancoil unit
▪ 2: Radiator
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see
"5.2.5 Configuration wizard: Main zone" on
page 16
.
#
Code
Description
[3.9]
N/A
▪ 0: Leaving water if the control type of
the main zone is Leaving water.
▪ 1: External room thermostat if the
control type of the main zone is
External room thermostat or Room
thermostat.
Setpoint mode
For more info about this functionality, see
"5.2.5 Configuration
wizard: Main zone" on page 16
.
#
Code
Description
[3.4]
N/A
▪ 0: Fixed
▪ 1: WD heating, fixed cooling
▪ 2: Weather dependent
If you choose WD heating, fixed cooling or Weather dependent, the
next screen will be the detailed screen with weather-dependent
curves. Also see
"5.2.7 Detailed screen with weather-dependent
curve" on page 17
.
Schedule
Indicates if the desired leaving water temperature is according to a
schedule. Also see
"5.2.5 Configuration wizard: Main zone" on
page 16
.
#
Code
Description
[3.1]
N/A
▪ 0: No
▪ 1: Yes
5.2.7
Detailed screen with weather-dependent
curve
When weather dependent operation is active the desired tank
temperature is determined automatically depending on the averaged
outdoor temperature. When the outdoor temperature is lower the
tank temperature will need to be higher as the water pipes will be
colder and vice versa.
The weather-dependent curves are defined by two setpoints:
▪ Setpoint (X1, Y2)
▪ Setpoint (X2, Y1)
Weather-dependent curve:
X1
Y1
Y2
X2
Y
a
X
Go through the temperatures.
Confirm changes and proceed.
Change the temperature.
Go to the next temperature.
Item
Description
a
Possible weather dependent zones:
▪
: Main zone heating
▪
: Main zone cooling
▪
: Additional zone heating
▪
: Additional zone cooling
▪
: Domestic hot water
X, X1, X2
Outdoor ambient temperature
Y, Y1, Y2
Desired tank temperature or leaving water temperature.
The symbol shown here corresponds to the heat emitter
for that zone:
▪
: Underfloor heating
▪
: Fan coil unit
▪
: Radiator
▪
: Domestic hot water tank
5.2.8
Configuration wizard: Tank
This part only applies to systems with a domestic hot water tank
installed.
▪ EHBH/X : an optional domestic hot water tank is available.
Heat up mode
The domestic hot water can be prepared in 3 different ways. They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.
#
Code
Description
[5.7]
[6-0D]
▪ 0: Reheat only: Only reheat operation
is allowed.
▪ 1: Schedule + reheat: The domestic
hot water tank is heated according to a
schedule and between the scheduled
heat up cycles, reheat operation is
allowed.
▪ 2: Schedule only: The domestic hot
water tank can ONLY be heated
according to a schedule.
See the operation manual for more details.