ESIE13-03
|
Part 2. Troubleshooting
3. Symptom based troubleshooting
Page 44
13/05/15
|
Version 2.0
Ground source heat pump
3.5. Inaccurate temperature control (for both domestic hot water and space
heating operation)
Deviation of brine leaving
(R6T - A9P) thermistor can
cause incorrect activation
of brine freeze up temper-
ature.
• Component
problem.
• Bad contact between
sensor and piping.
Check thermistor R6T - A9P (see
).
If required replace thermis-
tor R6T (see
PCB A9P (see
).
Hydro PCB A1P not opera-
tional.
• No power supply.
• Faulty
transformer
TR1.
• PCB
malfunction.
• Confirm if a small green led is blinking
in regular intervals.
• Confirm power supply towards PCB
A1P.
• Check good operation of transformer
TR1.
• Re-establish power to
PCB.
Replace PCB A1P (see
) in case power
supply and transformer
TR1 are OK but led is not
blinking.
Refrigerant/brine PCB A9P
not operational.
• No power supply.
• PCB
malfunction.
• Confirm if the HAP led is blinking in
regular intervals.
• Confirm power supply towards PCB
A9P.
Re-establish power to
PCBA9P or replace PCB
A9P (see
) in case
power supply is OK but led
is not blinking.
Inverter PCB [A10P] not
operational.
• No power towards INV
PCB.
• PCB
malfunction.
• Confirm if the HAP led is blinking in
regular intervals.
• Check if power is supplied towards
PCB (follow wiring back to main power
input and check all safeties and
cables).
Re-establish power to PCB
A10P or replace PCB
A10P (see
) in
case power supply is OK
but led is not blinking.
Inverter PCB [A10P] does
not give correct output to
compressor.
Inverter circuit problem.
Check inverter PCB.
Replace inverter PCB
A10P in case faulty (see
).
Reactor coil
(L1R/L2R/L3R) broken.
Component problem.
Check continuity of the reactor coil.
Replace the reactor coil in
case faulty.
Possible failures
Root cause
Check
Corrective action
Root cause category: parameter (setting)
Incorrect setting of unit control
method (setting [C-07]).
Incorrect setting of unit control
method (setting [C-07]) (leav-
ing water control, room ther-
mostat control, ext. room
thermostat control).
Check if setting [C-07] (leaving
water control, room thermostat
control, ext. room thermostat
control) is in set according to
the application.
Incorrect setting of user inter-
face location (user menu
[A.2.1.B]).
Incorrect setting of user inter-
face location (user menu
[A.2.1.B]) (at unit/in room).
Check if setting of user inter-
face location (user menu
[A.2.1.B]) (at unit/in room) is
set correctly.
Incorrect setting of pump oper-
ation mode (continuous, sam-
ple, request) (setting [F-0D]).
Incorrect setting.
Confirm setting [F-0].
Adapt setting [F-0] if required.
(Factory setting: [F-0]=1).
Root cause category: installation
User interface (A2P) - thermo-
stat sensor value not repre-
senting room temperature.
Bad location of thermostat
sensor (external influence) in
case of room thermostat con-
trol (setting [C-07 - 2]).
Check if user interface is
mounted in the correct position
to measure the correct room
temperature.
Correct the position of the user
interface for more accurate
room temperature measure-
ment.
Possible failures
Root cause
Check
Corrective action