ESIE13-03
|
Part 2. Troubleshooting
2. Error code based troubleshooting
Page 32
13/05/15
|
Version 2.0
Ground source heat pump
2.37. “U0” – Refrigerant shortage
2.38. “U1” – Reverse phase or open phase
Faulty inverter PCB A10P.
Check if the correct spare part PCB was
installed.
Replace inverter PCB A10P (see
).
Faulty refrigerant/brine main PCB A9P.
Check if the correct spare part PCB was
installed.
Replace refrigerant/brine main PCB A9P
(see
Faulty hydro PCB A1P.
Check if the correct spare part PCB was
installed.
Replace hydro PCB A1P when required
(see
Trigger
Effect
Reset
1. Refrigerant/brine PCB detects
maximum opening expansion valve and
discharge superheat > 50°C for 5
minutes.
2. 4 times a secondary current drop for 5
minutes (unit goes thermo off after
every drop).
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Refrigerant circuit is clogged.
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve)).
Refrigerant shortage (incorrect charge /
leakage).
Check for refrigerant shortage. Perform
leak test.
If required repair the leak and charge the
correct amount of refrigerant (1.8 kg).
Faulty expansion valve.
Check expansion valve (see
Replace expansion valve (see
) or PCB A9P (see
Faulty high pressure sensor / refriger-
ant/brine PCB A9P.
Check high pressure sensor (see
).
Replace the high pressure sensor (see
) or PCB A9P (see
Trigger
Effect
Reset
Refrigerant/brine PCB detects incorrect
power supply.
Unit will stop operating.
Via user int power reset.
Possible cause
Check
Corrective action
Power supply is not OK -> open phase.
Check power supply.
Power supply is not OK -> reverse phase.
Check power supply.
Change two phases with each other.
Faulty refrigerant/brine PCB A9P.
Check if the correct spare part PCB A9P
was installed.
Replace PCB A9P when required (see
).