ESIE13-03
|
Part 2. Troubleshooting
2. Error code based troubleshooting
13/05/15
|
Version 2.0
Page 25
Ground source heat pump
2.13. “E9” – Expansion valve abnormality
2.14. “F3” – Discharge pipe temperature control
Trigger
Effect
Reset
1. No continuity of expansion valve.
2. Minimum expansion valve opening and
suction superheat < 4 K and discharge
superheat < 5 K.
Unit will stop operating.
Via user interface (power reset might be
necessary in case no common power sup-
ply was cause).
Possible cause
Check
Corrective action
No common power supply after power on.
Check power supply.
Faulty expansion valve.
Check expansion valve (see
).
Replace expansion valve (see
Faulty thermistor R2T, R3T, R4T / refriger-
ant/brine PCB A9P.
Check thermistors R2T, R3T, R4T (see
Replace thermistors R2T, R3T, R4T (see
) or PCB A9P (see
).
Faulty high pressure sensor / refriger-
ant/brine PCB A9P.
Check high pressure sensor (see
Replace the high pressure sensor (see
) or PCB A9P (see
).
Wet operation.
Check for wet operation. (Wet operation
can be detected by checking the suction
superheat. If the suction superheat is 0°C
then liquid refrigerant is returning to the
compressor.)
In case wet operation was detected con-
firm the cause:
• Refrigerant
overcharge.
• Restricted brine flow.
• Faulty expansion valve.
External factor (e.g. electrical noise)
(cause when error is reset after power
reset, and error happens again after
awhile).
Check for source which could cause elec-
trical interference.
Trigger
Effect
Reset
1. Discharge temperature > 110°C for 15
minutes.
2. Discharge temperature > 125°C.
Unit will stop operating.
Via user interface -> only possible when
below 95°C.
Possible cause
Check
Corrective action
Refrigerant shortage (incorrect charge /
leakage).
Check for refrigerant shortage.
Perform leak test.
Repair the leak and charge the correct
amount of refrigerant (1.8 kg).
Faulty thermistor R2T / refrigerant/brine
PCB A9P.
Check thermistor R2T (see
).
Replace thermistor R2T (see
PCB A9P (see
).
Faulty compressor.
Check compressor (see
Replace compressor and also investigate
reason of breakdown.
Check expansion valve operation (liquid
back issue).
Check refrigerant shortage (overheated
issue) -> check for leak.
Faulty expansion valve.
Check expansion valve (see
).
Replace expansion valve (see