5 Preparation

Installer reference guide

8

07C2V3

Daikin Altherma monobloc compact outdoor unit

4P598847-1 – 2019.10

Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet
causes short circuit (suction of discharge air). This may result in:

▪ deterioration of the operational capacity;

▪ frequent frost acceleration in heating operation;

▪ disruption  of  operation  due  to  decrease  of  low  pressure  or

increase of high pressure;

▪ a  broken  fan  (if  a  strong  wind  blows  continuously  on  the  fan,  it

may start rotating very fast, until it breaks).

It  is  recommended  to  install  a  baffle  plate  when  the  air  outlet  is
exposed to wind.

It is recommended to install the outdoor unit with the air inlet facing
the wall and NOT directly exposed to the wind.

b

a

b

c

a

Baffle plate

b

Prevailing wind direction

c

Air outlet

Do NOT install the unit in the following places:

▪ Sound  sensitive  areas  (e.g.  near  a  bedroom),  so  that  the

operation noise will cause no trouble.
Note:  If  the  sound  is  measured  under  actual  installation
conditions,  the  measured  value  might  be  higher  than  the  sound
pressure level mentioned in Sound spectrum in the data book due
to environmental noise and sound reflections.

▪ In  places  where  a  mineral  oil  mist,  spray  or  vapour  may  be

present  in  the  atmosphere.  Plastic  parts  may  deteriorate  and  fall
off or cause water leakage.

It  is  NOT  recommended  to  install  the  unit  in  the  following  places
because it may shorten the life of the unit:

▪ Where the voltage fluctuates a lot

▪ In vehicles or vessels

▪ Where acidic or alkaline vapour is present

Seaside  installation.

  Make  sure  the  outdoor  unit  is  NOT  directly

exposed  to  sea  winds.  This  is  to  prevent  corrosion  caused  by  high
levels of salt in the air, which might shorten the life of the unit.

Install the outdoor unit away from direct sea winds.

Example: 

Behind the building.

b

c

a

If the outdoor unit is exposed to direct sea winds, install a
windbreaker.

▪ Height of windbreaker≥1.5×height of outdoor unit

▪ Mind  the  service  space  requirements  when  installing  the

windbreaker.

a

b

c

d

c

d

a

Sea wind

b

Building

c

Outdoor unit

d

Windbreaker

The  outdoor  unit  is  designed  for  outdoor  installation  only,  and  for
ambient temperatures ranging 10~43°C in cooling mode, –25~25°C
in  space  heating  mode,  and  –25~35°C  in  domestic  hot  water
operation mode.

5.2.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

c

a

b

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  See 

"6.3  Mounting  the

outdoor unit" 

[

4

 12] for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

Содержание EBLQ-C2V3

Страница 1: ...Installer reference guide Daikin Altherma monobloc compact outdoor unit English Installer reference guide Daikin Altherma monobloc compact outdoor unit EBLQ05C2V3 EBLQ07C2V3...

Страница 2: ...outdoor unit 14 6 3 5 To provide drainage 14 6 3 6 To prevent the outdoor unit from falling over 15 6 4 Connecting water piping 15 6 4 1 About connecting the water piping 15 6 4 2 Precautions when co...

Страница 3: ...y small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any obje...

Страница 4: ...e nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional...

Страница 5: ...arrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current...

Страница 6: ...ons Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories Abou...

Страница 7: ...remote outdoor sensor can be installed to measure the outdoor temperature on another location e g to avoid direct sunlight to have an improved system behaviour For installation instructions see the in...

Страница 8: ...of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds T...

Страница 9: ...ovide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded Water temperature All installed piping and piping accessories valve connections MUST withstand the fo...

Страница 10: ...s case it is recommended to install an extra vessel outside the unit a This is the height difference m between the highest point of the water circuit and the outdoor unit If the outdoor unit is at the...

Страница 11: ...to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates E g time of use rates seasonal rates W rmepumpentarif in Germany and Austria This e...

Страница 12: ...nstallation manual of the tank 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consis...

Страница 13: ...in accordance with the foundation drawing INFORMATION For information on the available options contact your dealer If the unit is installed directly on the floor prepare 4 sets of M8 or M10 anchor bo...

Страница 14: ...ation places where water leaking from the unit due to a blocked drain pan can cause damage to the location Make sure that condensation water can be evacuated properly Install the unit on a base to mak...

Страница 15: ...tank 3 Filling the water circuit 4 Protecting the water circuit against freezing addition of glycol 5 Filling the domestic hot water tank 6 Insulating the water piping INFORMATION For instructions re...

Страница 16: ...e outdoor unit 4 Connecting the power supply of the domestic hot water tank 5 Connecting the power supply of the optional backup heater inside the domestic hot water tank if applicable 6 Connecting th...

Страница 17: ...g b High voltage wiring main power supply 5 Make sure that the cable does NOT come in contact with sharp edges or hot gas piping 6 Install the switch box cover INFORMATION When installing field supply...

Страница 18: ...CE Only connect NO normally open valves NO X5M X3M M2S 2 1 6 6 Finishing the outdoor unit installation 6 6 1 To close the outdoor unit 1 Close the switch box cover 2 Mount the top plate and the front...

Страница 19: ...r further commissioning instructions see the installation manual of the domestic hot water tank 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure th...

Страница 20: ...or similarly qualified persons Booster heater of the domestic hot water tank See the installation manual of the domestic hot water tank 10 Troubleshooting 10 1 Overview Troubleshooting For instruction...

Страница 21: ...he gas stop valve and stop forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 11 3 To start and stop forced cooling Confirm that DIP swi...

Страница 22: ...CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor...

Страница 23: ...ensor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W C...

Страница 24: ...230 V earth Only for normal power supply installation MONOBLOC UNIT STANDARD PART POWER SUPPLY Control box 12 3 ESP curve Outdoor unit Note A flow error will occur when the minimum water flow rate is...

Страница 25: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance inst...

Страница 26: ......

Страница 27: ......

Страница 28: ...4P598847 1 2019 10 Copyright 2019 Daikin...

Отзывы: