8 Hand-over to the user

Installer reference guide

19

07C2V3
Daikin Altherma monobloc compact outdoor unit
4P598847-1 – 2019.10

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

7.3

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.

Depending  on  the  system  layout,  not  all  components  may  be
available.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

outdoor unit

 is properly mounted.

The domestic hot water tank is properly mounted.

The following 

field wiring

 has been carried out according

to  the  available  documentation  and  the  applicable
legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between  the  local  supply  panel  and  the  domestic  hot

water tank

▪ Between  the  local  supply  panel  and  the  optional

backup  heater  inside  the  domestic  hot  water  tank  (if
applicable)

▪ Between  the  outdoor  unit  and  the  domestic  hot  water

tank

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the outdoor unit.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There are no 

water leaks

 inside the outdoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

pressure  relief  valve

  purges  water  when  opened.

Clean water must come out.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions.  See  "To  check  the  water  volume"  in

"5.3 Preparing water piping" 

[

4

 9].

INFORMATION

For further commissioning instructions, see the installation
manual of the domestic hot water tank.

8

Hand-over to the user

Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation at the URL mentioned earlier in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do for the maintenance of the unit.

9

Maintenance and service

NOTICE

General  maintenance/inspection  checklist.

  Next  to  the

maintenance  instructions  in  this  chapter,  a  general
maintenance/inspection  checklist  is  also  available  on  the
Daikin Business Portal (authentication required).

The 

general 

maintenance/inspection 

checklist 

is

complementary  to  the  instructions  in  this  chapter  and  can
be  used  as  a  guideline  and  reporting  template  during
maintenance.

NOTICE

Maintenance  MUST  be  done  by  an  authorized  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

9.1

Overview: Maintenance and
service

This chapter contains information about:

▪ Maintenance safety precautions

▪ The yearly maintenance of the outdoor unit

9.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

9.2.1

Opening the outdoor unit

See 

"6.2.2  To  open  the  outdoor  unit" 

[

4

  12]  and 

"6.2.3  To  open  the

switch box cover of the outdoor unit" 

[

4

 12].

9.3

Checklist for yearly maintenance
of the outdoor unit

Check the following at least once a year:

Содержание EBLQ-C2V3

Страница 1: ...Installer reference guide Daikin Altherma monobloc compact outdoor unit English Installer reference guide Daikin Altherma monobloc compact outdoor unit EBLQ05C2V3 EBLQ07C2V3...

Страница 2: ...outdoor unit 14 6 3 5 To provide drainage 14 6 3 6 To prevent the outdoor unit from falling over 15 6 4 Connecting water piping 15 6 4 1 About connecting the water piping 15 6 4 2 Precautions when co...

Страница 3: ...y small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire CAUTION Do NOT touch the air inlet or aluminium fins of the unit NOTICE Do NOT place any obje...

Страница 4: ...e nameplate of the unit It states the type of refrigerant and necessary amount The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional...

Страница 5: ...arrying connections must be separated before the earth connection is The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current...

Страница 6: ...ons Safety instructions that you must read before installing About the documentation What documentation exists for the installer About the box How to unpack the units and remove their accessories Abou...

Страница 7: ...remote outdoor sensor can be installed to measure the outdoor temperature on another location e g to avoid direct sunlight to have an improved system behaviour For installation instructions see the in...

Страница 8: ...of the unit Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds T...

Страница 9: ...ovide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded Water temperature All installed piping and piping accessories valve connections MUST withstand the fo...

Страница 10: ...s case it is recommended to install an extra vessel outside the unit a This is the height difference m between the highest point of the water circuit and the outdoor unit If the outdoor unit is at the...

Страница 11: ...to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates E g time of use rates seasonal rates W rmepumpentarif in Germany and Austria This e...

Страница 12: ...nstallation manual of the tank 6 Installation 6 1 Overview Installation This chapter describes what you have to do and know on site to install the system Typical workflow Installation typically consis...

Страница 13: ...in accordance with the foundation drawing INFORMATION For information on the available options contact your dealer If the unit is installed directly on the floor prepare 4 sets of M8 or M10 anchor bo...

Страница 14: ...ation places where water leaking from the unit due to a blocked drain pan can cause damage to the location Make sure that condensation water can be evacuated properly Install the unit on a base to mak...

Страница 15: ...tank 3 Filling the water circuit 4 Protecting the water circuit against freezing addition of glycol 5 Filling the domestic hot water tank 6 Insulating the water piping INFORMATION For instructions re...

Страница 16: ...e outdoor unit 4 Connecting the power supply of the domestic hot water tank 5 Connecting the power supply of the optional backup heater inside the domestic hot water tank if applicable 6 Connecting th...

Страница 17: ...g b High voltage wiring main power supply 5 Make sure that the cable does NOT come in contact with sharp edges or hot gas piping 6 Install the switch box cover INFORMATION When installing field supply...

Страница 18: ...CE Only connect NO normally open valves NO X5M X3M M2S 2 1 6 6 Finishing the outdoor unit installation 6 6 1 To close the outdoor unit 1 Close the switch box cover 2 Mount the top plate and the front...

Страница 19: ...r further commissioning instructions see the installation manual of the domestic hot water tank 8 Hand over to the user Once the test run is finished and the unit operates properly please make sure th...

Страница 20: ...or similarly qualified persons Booster heater of the domestic hot water tank See the installation manual of the domestic hot water tank 10 Troubleshooting 10 1 Overview Troubleshooting For instruction...

Страница 21: ...he gas stop valve and stop forced cooling a c b d d e a Gas stop valve b Closing direction c Hexagonal wrench d Valve cap e Liquid stop valve 11 3 To start and stop forced cooling Confirm that DIP swi...

Страница 22: ...CuT 7 9 CuT 1 4 3 2 t 12 7 CuT 12 7 CuT R4T 9 5 CuT 6 4 CuT 6 4 CuT M 6 4 CuT 6 4 CuT Discharge pipe thermistor Accumulator Compressor High pressure switch Muffler Muffler 4 way valve Pressure sensor...

Страница 23: ...ensor S1PH High pressure switch S2 S503 Connector SA1 Surge arrestor SHEET METAL Terminal strip on fixed plate SW1 SW3 Push buttons SW2 SW5 DIP switches U Connector V Connector V2 V3 V401 Varistor W C...

Страница 24: ...230 V earth Only for normal power supply installation MONOBLOC UNIT STANDARD PART POWER SUPPLY Control box 12 3 ESP curve Outdoor unit Note A flow error will occur when the minimum water flow rate is...

Страница 25: ...duct or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenance inst...

Страница 26: ......

Страница 27: ......

Страница 28: ...4P598847 1 2019 10 Copyright 2019 Daikin...

Отзывы: