4 About the units and options
Installer reference guide
7
07C2V3
Daikin Altherma monobloc compact outdoor unit
4P598847-1 – 2019.10
1×
1×
1×
1×
a
b
c
d
2×
1×
2×
f
e
g
a
General safety precautions
b
Addendum book for optional equipment
c
Outdoor unit installation manual
d
Operation manual
e
Sealing ring for shut-off valve
f
Shut-off valve
g
Unit mounting plate
4
About the units and options
4.1
Overview: About the units and
options
This chapter contains information about:
▪ Identifying the outdoor unit
▪ Combining the outdoor unit with options
4.2
Identification
NOTICE
When installing or servicing several units at the same time,
make sure NOT to switch the service panels between
different models.
4.2.1
Identification label: Outdoor unit
Location
Model identification
Example:
E B L Q 05 C2 V3
Code
Explanation
E
European monobloc outdoor heat pump
B
Reversible (cooling)
L
Low water temperature – ambient zone: −10~
−25°C
Q
Refrigerant R410A
05
Capacity class
C2
Model series
V3
Power supply
4.3
Combining units and options
4.3.1
Possible options for the outdoor unit
Remote outdoor sensor (EKRSC1)
By default the sensor inside the outdoor unit will be used to measure
the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure
the outdoor temperature on another location (e.g. to avoid direct
sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote
outdoor sensor.
5
Preparation
5.1
Overview: Preparation
This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the water piping
▪ Preparing the electrical wiring
5.2
Preparing the installation site
Do NOT install the unit in places often used as work place. In case
of construction works (e.g. grinding works) where a lot of dust is
created, the unit MUST be covered.
Choose an installation location with sufficient space for carrying the
unit in and out of the site.
5.2.1
Installation site requirements of the
outdoor unit
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
Mind the following spacing guidelines:
≤1200
>250/400
>250/400
>250
>350
>350
(mm)
(mm)
a
b
b
a
a
Air outlet
b
Air inlet
INFORMATION
If shut-off valves are installed on the unit, provide a
minimum space of 400 mm at the air inlet side. If shut‑off
valves are NOT installed on the unit, provide a minimum
space of 250 mm.
The maximum allowable distance between outdoor unit and
domestic hot water tank is 10 m.
NOTICE
▪ Do NOT stack the units on each other.
▪ Do NOT hang the unit on a ceiling.