3
|
Troubleshooting
Service manual
76
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3.3.85 U8-06 – Bizone kit CANOpen communication error
Trigger
Effect
Reset
Communication
abnormality between user
interface PCB and bizone
kit box.
Unit will stop operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the user interface (main PCB). See
234].
Possible cause:
Faulty user interface (main PCB).
2
Perform a check of the bizone kit PCB. See documentation of the bizone kit.
Possible cause:
Faulty bizone kit PCB.
3
Check the communication wiring between the unit and the bizone kit box. See
Possible cause:
Faulty wiring between the unit and the bizone kit box.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.86 U8-07 – P1/P2 communication error
Trigger
Effect
Reset
Lost communication
between unit user
interface and unit.
Unit will NOT stop
operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check the communication wiring between the user interface and the unit PCB.
See
Possible cause:
Faulty wiring between the user interface and the unit PCB.
2
Check if the unit user interface functions correctly. See
234].
Possible cause:
Faulty user interface on unit.
3
Perform a check of the hydro PCB. See
Possible cause:
Faulty hydro PCB.
4
Check if the power supply is compliant with the regulations. See
254].
draft – 31/05/2022 15:53