3
|
Troubleshooting
Service manual
73
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
3.3.80 U7-00 – Outdoor unit: Transmission malfunction between main microcomputer - inverter
microcomputer
Trigger
Effect
Reset
Communication
abnormality between
main and inverter
microcomputer.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
184].
Possible cause:
Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.81 U8-02 – Connection with room thermostat lost
Trigger
Effect
Reset
Communication
abnormality between unit
and room thermostat
after connection was
already made.
Unit will NOT stop
operating.
Automatic reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the power supply is compliant with the regulations. See
Possible cause:
▪
Faulty or disturbance of the power supply (power supply MUST be within
range of nominal operating voltage ±4%),
▪
Power drop,
▪
Short circuit.
2
Check the communication wiring between the remote controller and the unit.
See
234].
Possible cause:
Faulty wiring between the remote controller and the unit.
3
Perform a check of the room thermistor:
draft – 31/05/2022 15:53