3
|
Troubleshooting
Service manual
61
EBLA04~08E + EDLA04~08E
Daikin Altherma 3 M
ESIE22-09 – 2022.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the refrigerant pressure sensor. See
Possible cause:
Faulty refrigerant pressure sensor.
2
Perform a check of the hydro PCB. See
175].
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.62 JA-17 – Refrigerant pressure sensor abnormality
Trigger
Effect
Reset
Refrigerant pressure
sensor input is out of
range.
Unit will stop operating.
Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the refrigerant pressure sensor. See
Possible cause:
Faulty refrigerant pressure sensor.
2
Perform a check of the hydro PCB. See
175].
Possible cause:
Faulty hydro PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
3.3.63 L1-00 – Outdoor unit: Main PCB abnormality
Trigger
Effect
Reset
Outdoor unit main PCB
detects current/voltage
errors.
Unit will stop operating.
Manual reset via user
interface.
Power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
draft – 31/05/2022 15:53