31
Installation Manual
Rev. 2.00
Date 01-2019
Note:
in case of system reset, it will
return to default values.
Note:
the Remote Assistance
parameter enables a qualified
technician the remote access to
your installation in order to
perform a diagnose of it.
Autochange.
This option allows the user to configure the three
values that define the auto-changeover operation that sets the
mode of the indoor unit.
-
Setpoint Differential.
Defines the minimum differential
between heating and cooling set points. For example, if set
to 2˚F, the system will force the cooling set point at least two
degrees higher than the heating set point. Values: 0 to 7˚F /
0 to 3.5˚C in increments of 1˚F / 0.5˚C, by default 2˚F / 1˚C.
-
Mode Switching Protection (min).
Defines the minimum
run time before allowing a mode change. Possible values are
15, 30, 60 and 90 minutes. By default, 30 minutes.
-
Heat OVR Temp.
If a zone has a higher heating demand than
this temperature, the system reverts heating operation even
if the cooling global demand exceeds the global heat
demand. Possible values are: Off, 3 to 8˚F / 1.5 to 4˚C in
increments of 1˚F / 0.5˚C. Default value: Off.
BACnet.
This parameter displays the Device ID, the uplink port, the
IP address, the subnet mask and the Gateway IP and allows you to
modify them. Press on the value you want to change, modify it and
then press to confirm. The values by default are:
-
Port: 47808
-
IP Address: 192.168.0.100
-
Subnet Mask: 255.255.255.0
-
Gateway IP: 192.168.0.1
Room Temperature.
This option allows the room temperature and
relative humidity to be shown/hidden. By default, the room
temperature is shown.
Lite Step.
This option configures the temperature increments
(2˚F/1˚C or 1˚F/ 0.5˚C) of the base set-point for the Wireless Lite
Thermostat. By default, 1˚F/0.5˚C.
Remote Assistance.
This option enables/disables remote
assistance. By default, remote assistance is disabled.
Reset System
(only available for the Main thermostat)
.
This option
resets the system and returns to factory settings.
Содержание DZK Series
Страница 1: ...Installation Manual Zoning Kit ...
Страница 26: ...26 Installation Manual Rev 2 00 Date 01 2019 Wired Thermostat Wireless Thermostat ...
Страница 45: ...45 Installation Manual Rev 2 00 Date 01 2019 NAVIGATION GUIDE WIRED THERMOSTAT NAVIGATION GUIDE ...
Страница 46: ...46 Installation Manual Rev 2 00 Date 01 2019 WIRELESS THERMOSTAT NAVIGATION GUIDE ...
Страница 54: ...54 Installation Manual Rev 2 00 Date 01 2019 WIRING DIAGRAM ...
Страница 55: ......
Страница 56: ...Phone 855 770 5678 http www daikinac com 400886 ...