D-EIMWC00804-14EN
Centrifugal Chillers
41
Table 12, Vane Speed Factory Setting
Compressor Model
Opening Time
Closing Time
CE050
2 - 2 1/2 min.
3/4 - 1 min.
CE063 - CE100
3 - 5 min.
1 - 2 min
CE126
5 - 8 min.
1 - 2 min.
Figure 21, Oil Sump and Compressor Controller Panel
NOTE: 4-way solenoid valve and vane close switches are located on the compressor
suction inlet. The mechanical high-pressure cutout is located in the discharge line.
Oil Pump
Contactor
Oil Pump
Capacitor
Compressor
MicroTech II
controller
Cooling
Water Inlet
Cooling
Water Outlet
Temperature
Control Valve
Solenoid
Valve
Oil Sump
Relief Valve
Back Seat Port