SYSTEM WIRING
Figure 20
1 2 C R
1 2 R C
1 2 R C
Communica
�
ng Thermostat
125
�
.(*)
Air Handler BlowerIntegrated
ControlModule
250
�
.(*)
Heat Pump Integrated
ControlModule
(*) Allowable Maximum Length
1 2 C R
1 2 R C
1 2 R C
Communica
�
ng Thermostat
125
�
.(*)
Air Handler BlowerIntegrated
ControlModule
250
�
.(*)
Heat Pump Integrated
ControlModule
(*) Allowable Maximum Length
Cooling
Air Conditioner
Heating
Air Handler
Continuous Fan
Thermostat
Cooling
Heat Pump
Heat Pump Heating
Only
Heat Pump
HP+ Electric Heat
Strips
Greater than of Heat
Pump of Air Handler
Demand
Electric Heat Strips
Only
Air Handler
Continuous Fan
Thermostat
Table 10
System
System Operating
Mode
Airflow Demand
Source
Air Condi
Air Handler
Heat Pump + Air
Handler
ATTENTION INSTALLER -
IMPORTANT NOTICE!
Please read carefully before installing this unit.
• Power line terminal #C from Indoor unit must connect
to terminal #C on thermostat and power line terminal
#R from indoor unit must connect to terminal #R on
thermostat. Verify wires are not reversed. (Note:The
order of the terminals of the indoor unit and the Daikin
One+ thermostat may be different.)
• Do not attach any wires to the R & C Terminals on the
AC/HP, as they are not needed for inverter unit.
• Data line terminal #1 from AC/HP must connect to
terminal #1 on indoor unit and thermostat and data
line terminal #2 from AC/HP must connect to terminal
#2 on indoor unit and thermostat. Verify wires are not
reversed.
17.5 System Troubleshooting
NOTE:
Refer to the instructions accompanying the
Communicating compatible outdoor AC/HP unit for
unit specific troubleshooting information. Refer to the
Troubleshooting Chart
at the end of this manual for
a listing of possible air handler error codes, possible
causes and corrective actions.