General Specification

www.DaikinApplied.com 35 

CAT 258 • REBEL APPLIED ROOFTOP

2 .07 Safety Options

A. 

Unit Shall be provided with a safety shutdown 

terminal for installation of field emergency input

B. 

Unit Shall be provided with factory installed supply 

air smoke detector

C. 

Unit shall be provided with factory installed return air 

smoke detector

D. 

Unit shall be provided with factory installed supply 

and return air smoke detector

2 .08 Cooling Coil

A. 

The cooling coil section shall be installed in a  draw-

through configuration, upstream of the supply air 

fan. The coil section shall be complete with factory 

piped cooling coil and sloped drain pan. 

B. 

Direct expansion (DX) cooling coils shall be 

fabricated of seamless 1/2" diameter high efficiency 

copper tubing that is mechanically expanded into 

high efficiency aluminum plate fins. Coils shall be 

a multi-row, staggered tube design with a minimum 

of 4 rows. All units shall have two independent 

refrigerant circuits and shall use an interlaced coil 

circuiting that keeps the full coil face active at all 

load conditions.

C. 

Each refrigeration circuit shall be equipped with a 

thermostatic expansion valve for control refrigerant 

flow control.

D. 

The cooling coil casing and all coil block offs shall be 

constructed with stainless steel to prevent corrosion.

E. 

The refrigerant suction lines shall be fully insulated 

from the expansion valves to the compressors.

F. 

The distributor tubes shall be sleeved or coated to 

provide longevity and protection from leaks.

G. 

All coils shall be factory leak tested with high 

pressure air under water.

H.  The drain pan shall be stainless steel and designed 

to comply with ASHRAE- 62.1 double sloped 

requirements drain pan shall be provided with the 

cooling coil. The drain pan shall extend beyond 

the leaving side of the coil and underneath the 

cooling coil connections. The drain pan shall have 

a minimum slope of 1/8" per foot to provide positive 

draining. The drain pan shall be connected to a 

threaded drain connection extending through the 

unit base. Units with stacked cooling coils shall be 

provided with a secondary drain pan piped to the 

primary drain pan.

I. 

Insulation under the drain pan should be a closed 

cell structure to prevent moisture from wicking under 

the drain pan. Fiberglass is not allowed.

2 .09 Corrosion Protection

A. 

All Indoor Heating and Cooling coils shall be 

provided with a corrosion protection coating rated 

for a minimum of 6000 hours of salt spray resistance 

per ASTM B 117-90 salt spray performance testing., 

ASTM B 117-90 salt spray performance. 

B. 

All Outdoor condenser coils shall be provided with a 

corrosion protection coating rated for a minimum of 

6000 hours of salt spray resistance per ASTM B 11-

7-90 salt spray performance testing, ASTM B 117-90 

salt spray performance. 

C. 

All Indoor Heating and Cooling coils and the outdoor 

condenser coils shall be provided with a corrosion 

protection coating rated for a minimum of 6000 

hours of salt spray resistance per ASTM B 11-7-90 

salt spray performance testing, ASTM B 117-90 salt 

spray performance. 

2 .10 Modulating Hot Gas and Liquid Reheat

A. 

Hot gas reheat: Unit shall be equipped with a fully 

modulating hot gas reheat coil with hot gas coming 

from the unit condenser

1. 

Hot gas reheat coil shall be a Microchannel 

design. The aluminum tube shall be a micro 

channel design with high efficiency aluminum 

fins. Fins shall be brazed to the tubing for a 

direct bond. The capacity of the reheat coil shall 

allow for a 20°F temperature rise at all operating 

conditions.

2. 

The modulating hot gas reheat systems shall 

allow for independent control of the cooling 

coil leaving air temperature and the reheat coil 

leaving air temperature. The cooling coil and 

reheat coil leaving air temperature set points 

shall be adjustable through the unit controller. 

During the dehumidification cycle the unit shall 

be capable of 100% of the cooling capacity. 

The hot gas reheat coil shall provide discharge 

temperature control /- 2°F. 

3. 

Each coil shall be factory leak tested with high-

pressure air under water.

B. 

Liquid sub-cool reheat: Unit shall be equipped with 

a fully modulating liquid sub-cool reheat coil using 

hot liquid coming leaving the unit condenser to 

reheat saturated leaving evaporator air to neutral air 

temperatures leaving the unit.

1. 

Liquid sub-cool reheat coil shall be a 

Microchannel design. The aluminum tube shall 

be a micro channel design with high efficiency 

aluminum fins. Fins shall be brazed to the tubing 

for a direct bond. 

2. 

The modulating liquid sub-cool reheat system 

shall be utilized for independent control of the 

cooling coil leaving air temperature and the 

leaving/supply air temperature. 

Содержание DPSA

Страница 1: ...Catalog 258 Rebel Applied Rooftop Systems Heating and Cooling Models DPSA DFSA 30 to 52 Tons R 410A Refrigerant...

Страница 2: ...ir Quality 11 Outside Air Control 11 Filtration 11 Energy Recovery 12 Heating 13 Gas Heat 13 Electric Heat 13 Hot Water and Steam Heat 13 Fans 14 Supply Return and Exhaust Fan Array 14 EC Motor Techno...

Страница 3: ...ide EER s over 11 0 and IEER s up to 17 2 Precision heating and cooling temperature and humidity control with modulating technologies that provide superior turndown Airflow measuring Filtration UV lig...

Страница 4: ...icient thermal insulation and no exposed insulation for high indoor air quality Low Air Leakage Construction Air leakage occurs as infiltration or exfiltration Infiltration occurs when negative sectio...

Страница 5: ...d has flexible filtration options to satisfy indoor air requirements from varying space types Pleated Filter Options MERV 8 or 13 Filtration efficiencies in 2 or 4 filters exceed the AHSRAE 62 minimum...

Страница 6: ...to prevent failures and prolong equipment life Making Maintenance Easier Operating expenses go way beyond energy consumption To optimize the lifecycle cost of Rebel Applied rooftops we designed in fe...

Страница 7: ...as heat exchanger warranty Separated high and low voltage control panels for safe access to human control interfaces 208V 230V 460V 575V Single point power block connection 10 KAIC SCCR Phase voltage...

Страница 8: ...ransfer paths through the panel which prevents energy losses and exterior condensation Through metal provides a path for heat to enter the cabinet and lowers the effective R value of the insulation Fi...

Страница 9: ...al conditioning above the building loads is required meaning additional operating load and additional operating expense Figure 6 shows the average annual operating cost to building operators due to th...

Страница 10: ...o commission the equipment to provide the dehumidification each application requires No more no less The fully modulating hot gas reheat coil is controlled independent of the compressors to maintain c...

Страница 11: ...d draw through filter section and an optional final filter section with dirty filter alarm An optional electronic pressure transducer measures dirty filter status and can be monitored through the unit...

Страница 12: ...ls Defrost options for variable speed defrost control and electric preheat defrost 4 MERV 8 high capacity energy recovery filtration for high holding capacity to extend filter life in the outdoor air...

Страница 13: ...ronment even during shoulder seasons and in demanding applications such as 100 make up air and VAV systems Solves the mixed air tempering requirements of VAV systems when meeting ASHRAE 62 1 ventilati...

Страница 14: ...DC motor with an integral inverter The integral inverter eliminates variable frequency drives VFD saving energy losses and enhancing energy efficiency at part load ECM Fans provide the highest efficie...

Страница 15: ...he base of the unit Wiring complies with NEC requirements and all applicable UL standards For ease of use wiring and electrical components are number coded and labeled according to the electrical diag...

Страница 16: ...curbs Baserail curb pockets configurability makes direct replacement of multiple manufacturers legacy rooftops Daikin RoofPak and Trane IntelliPak can be replaced directly and others with minimal tra...

Страница 17: ...installed ultraviolet lights are available on the downstream side of all cooling coils and above the unit drain pan All ultraviolet lights are pre engineered and factory installed for ease of use and...

Страница 18: ...ounted BACnet or LonWorks communication module provides a network interface to the BAS Add optional field configurable I O modules to add additional sensors or points that are not standard on rooftop...

Страница 19: ...dehumidification operation Building Pressure Control Units equiped with return or exhaust fans can be configured to control building pressure directly or via several indirect methods like fan trackin...

Страница 20: ...1 kW 9 8 kW High Static Return Fans Type Direct dive ECM SWSI Plenum Fan Array Row Columns Qty 1 2 2 Diameter in 18 20 22 25 Motor Range kw hp 1 1 kW 6 0 kW Low Static Propeller Exhaust Type Direct d...

Страница 21: ...ze 9 20 24 3 20 x 20 Cartridge Filters Thickness MERV 4 15 12 11 14 16 Carbon Area sqft 38 3 ft Qty Size 9 20 24 3 20 20 Cartridge Final Filters Thickness MERV 12 14 16 Area sqft 35 6 ft Qty Size 9 20...

Страница 22: ...575V kW MBH kW MBH kW MBH kW MBH 4 stages SCR 30 102 0 20 62 4 20 62 7 25 170 6 45 153 0 40 124 7 40 125 0 45 60 204 0 55 187 1 55 188 0 75 255 0 75 249 4 75 250 2 70 255 9 90 306 0 90 311 8 90 313 4...

Страница 23: ...Efficiency Standard Efficiency Highest Efficiency Condenser Ctrl Fantrol Speedtrol Coil Rows 4 Row 6 Row Compressor Type EER IEER EER IEER 31 Standard Staged 10 8 15 0 11 5 17 1 35 Standard Staged 10...

Страница 24: ...0 100 Economizer with Propeller Fans 0 100 Economizer with High Static Exhaust Fans 0 100 Economizer with High Static Return Fans 0 100 Economizer with Energy Recovery Filter 2 Pleated Filter 8 32 2...

Страница 25: ...1 2 ECM fan array 2 Merv 8 filters Office 2 50 ton Economizer with return fan Gas heat 2 2 ECM fan array 2 Merv 8 pre filters and 12 MERV 14 cartridge filters Outside Return Air Filter DX Coil Supply...

Страница 26: ...Merv 8 filters 100 Outside Air 50 ton unit 100 Outside air damper 100 degree rise furnace 1 2 ECM fan array 2 MERV 8 filters Outside Return Air Filter DX Coil Supply Fan Gas Heat Condensing 81 0 40 0...

Страница 27: ...Service Clearance www DaikinApplied com 27 CAT 258 REBEL APPLIED ROOFTOP Service Clearance Figure 24 Rebel Applied Service Clearance Top of unit needs unobstructed clearance...

Страница 28: ...ble 9 Roof Curb Variable Dimensions 31 50 Tons A B C D Return End Configuration Out of Air Stream Vestibule AHU Length 8 Condenser Size Standard Return 2 93 48 Section 49 78 Configured 54 High Static...

Страница 29: ...ur Daikin sales representative if available clearances do not meet minimum recommendations Operating Range Daikin Rebel Applied rooftop systems are designed to operate over an extensive operating rang...

Страница 30: ...beneath the condensing section Apply for vibration isolation curb systems for sound transmission critical applications Account for low frequency duct breakout in system design Route the first 20 ft of...

Страница 31: ...cs and connection requirements B Product data 1 Provide literature that indicates dimensions weights capacities ratings and electrical characteristics and connection requirements 2 Provide data on fil...

Страница 32: ...shall be double wall with a solid stainless steel liner with a thermal break integral to the panel construction that provides a cleanable interior prevents conductive heat transfer through the panel...

Страница 33: ...be lined with a perforated acoustic liner to enhance sound attenuation 2 05 Supply Return and Exhaust Fans A All supply return and exhaust fans shall be configured in an array with a minimum number f...

Страница 34: ...re protection and prevent the motor from operation in the event of a loss of phase Motors shall be premium efficiency 3 Exhaust Fan configurations are not allowed as alternate 2 06 Electrical A Unit w...

Страница 35: ...m wicking under the drain pan Fiberglass is not allowed 2 09 Corrosion Protection A All Indoor Heating and Cooling coils shall be provided with a corrosion protection coating rated for a minimum of 60...

Страница 36: ...acterized Cv ball valves 2 12 Hot Water Heat Coils A A hot water heating coil shall be factory installed in the heat section The rooftop unit shall include a piping vestibule The coil connection shall...

Страница 37: ...aft burner The burner shall be controlled for low fire start The burner shall be capable of continuous modulation between 10 and 100 10 1 control of rated capacity G The furnace will be supplied with...

Страница 38: ...damper area at 1 differential pressure in according with testing defined in AMCA 500 Control of the dampers shall be by a factory installed direct coupled actuator D Unit shall be provided with an ou...

Страница 39: ...t or top discharge opening consult the schedule and drawings for the final orientation 2 21 Condensing Section A All Units shall provide the Energy Efficiency specified EER and IEER per the schedule e...

Страница 40: ...e a stand alone DDC controller not dependent on communications with any on site or remote PC or master control panel The microprocessor shall maintain existing set points and operate stand alone if th...

Страница 41: ......

Страница 42: ...uct Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go to www DaikinApplied com Aftermarket Services To find your local...

Отзывы: