background image

6

Direct vent (dual pipe) central forced air furnace  in 

which all combustion air supplied directly to the furnace 

burners through a special air intake system outlined 

in these instructions. Appropriate for use with natural 

or propane gas (

NOTE:

 If using propane, a propane 

conversion kit is required). 

This furnace may be used as a construction site heater only 

if  all of the following conditions are met:

•   The vent system is permanently installed per these 

installation instructions.

• 

  A room thermostat is used to control the furnace. 

Fixed jumpers that provide continuous heating 

CANNOT be used and can cause long term 

equipment damage. Bi-metal thermostats, or any 

thermostat affected by vibration, must not be used 

during construction.

•   Return air ducts are provided and sealed to the 

furnace.

• 

  A return air temperature range between 60ºF (16ºC) 

and 80ºF (27ºC) is maintained.

• 

  MERV 11 pleated minimum 4.0” thick (Example: 

P/N AMP-11-2025-45) air filter(s) are installed in 

the system and inspected daily and replaced as 

needed during construction and upon completion of 

construction.

•   The input rate and temperature rise are set per the 

furnace rating plate.

• 

  The furnace must be installed as a two pipe system, 

using 100% outside air for combustion during 

construction.

• 

  The furnace heat exchanger, components, duct 

system, air filters and evaporator coils are thoroughly 

cleaned following final construction clean up by a 

qualified person.

•   All furnace operating conditions (including ignition, 

input rate, temperature rise and venting) are verified 

according to these installation instructions.

• 

  Furnace doors must be in place on the furnace while 

the furnace is operating in any mode.

• 

  Damage or repairs due to failure to comply with these 

requirements are not covered under the warranty.

NOTE:

 The Commonwealth of Massachusetts requires that 

the following additional requirements must also be met:

• 

  Gas furnaces must be installed by a licensed plumber 

or gas fitter.

• 

  A T-handle gas cock must be used.

• 

  If the unit is to be installed in an attic, the passageway 

to and the service area around the unit must have 

flooring.

To  ensure  proper  furnace  operation,  install,  operate 

and  maintain  the  furnace  in  accordance  with  these 

installation and operation instructions, all local building 

codes and ordinances

. In their absence, follow the latest 

edition  of  the  National  Fuel  Gas  Code  (NFPA  54/ANSI 

Z223.1),  and/or  CAN/CSA  B149.1-15  Installation  Codes, 

local plumbing or waste water codes, and other applicable 

codes.

A  copy  of  the  National  Fuel  Gas  Code  (NFPA  54/ANSI 

Z223.1) can be obtained from any of the following:

American National Standards Institute

25 West 43rd Street, 4th Floor

New York, NY 10036

National Fire Protection Association

1 Batterymarch Park

Quincy, MA 02169-7471

CSA International

8501 East Pleasant Valley

Independence, OH 44131

The rated heating capacity of the furnace should be greater 

than or equal to the total heat loss of the area to be heated.  

The total heat loss should be calculated by an approved 

method or in accordance with “ASHRAE Guide” or “Manual 

J-Load Calculations” published by the Air Conditioning 

Contractors of America.

A copy of the CAN/CSA B149.1-15 Installation Codes can 

also be obtained from:

CSA International 

178 Rexdale Boulevard

 Etobicoke, Ontario, Canada M9W 1R3

LOCATION REQUIREMENTS & 

CONSIDERATIONS

Follow  the  instructions  listed  below  and  the  guidelines 

provided in the Combustion and Ventilation Air Requirements 

section when selecting a furnace location.

WARNING

To prevent possible equipment damage, property damage, 

personal injury or death, the following bullet points must 

be observed when installing this unit.

WARNING

Possible property damage, personal injury or death due to 

fire, explosion, smoke, soot, condensation, electrical shock 

or carbon monoxide may result from improper installation, 

repair operation, or maintenance of this product.

• 

  Centrally locate the furnace with respect to the 

proposed or existing air distribution system.

•   Ensure the temperature of the return air entering the 

furnace is between 55°F and 100°F when the furnace 

is heating.

•   Provide provisions for venting combustion products 

outdoors through a proper venting system. Special 

consideration should be given to vent/flue pipe routing 

and combustion air intake pipe when applicable.  

Содержание DM92SS

Страница 1: ...THIS SYMBOL AS A SAFETY PRECAUTION TABLE OF CONTENTS Safety Considerations 3 Shipping Inspection 4 Electrostatic Discharge ESD Precautions 5 To The Installer 5 Product Application 5 Location Requirem...

Страница 2: ...26 High Altitude Derate 26 Propane Gas Conversion 26 Gas Piping Connections 26 Gas Piping Checks 29 Propane Gas Tanks and Piping 29 Circulating Air Filters 29 Duct work Air Flow 29 Checking Duct Stati...

Страница 3: ...gas fired furnace for installation in a residential garage must be installed as specified in the LOCATION REQUIREMENTS AND CONSIDERATIONS section of this manual This furnace may be used as a construc...

Страница 4: ...electrical shock the furnace must be located to protect the electrical components from water Drain trap must be primed at time of installation Trap is internally partitioned add water to both inlet po...

Страница 5: ...ith static electricity i e do not move or shuffle your feet do not touch ungrounded objects etc If you come in contact with an ungrounded object repeat step 2 before touching control or wires 4 Discha...

Страница 6: ...and the service area around the unit must have flooring To ensure proper furnace operation install operate and maintain the furnace in accordance with these installation and operation instructions al...

Страница 7: ...above substances This protects the non direct vent furnace from airborne contaminants To ensure that the enclosed non direct vent furnace has an adequate supply of combustion air vent from a nearby u...

Страница 8: ...nting system may be too large to properly vent the remaining attached appliances POSITION SIDES REAR FRONT BOTTOM FLUE TOP Upflow 0 0 3 C 0 1 Horizontal 6 0 3 C 0 6 C If placed on combustible floor fl...

Страница 9: ...ant l un des essais d crits ci dessus des correctifs doivent tre apport s au syst me de ventilation conform ment au National Fuel Gas Code ANSI Z223 1 NFPA 54 et ou au Code d installation du gaz natur...

Страница 10: ...tal counterflow furnaces return ductwork must be attached to the basepan top end of the blower compartment NOTE Ductwork must never be attached to the back of the furnace Contact your distributor for...

Страница 11: ...gy content difference between natural and propane gas High Stage Low Stage Natural None 45 3 5 w c 1 9 w c None Propane LPM 07 1 1 25mm 10 0 w c 6 0 w c None Gas Altitude Kit Orifice Manifold Pressure...

Страница 12: ...aterials and Joining Methods Two three inch nominal diameter PVC Schedule 40 pipe meeting ASTM D1785 PVC primer meeting ASTM F656 and PVC solvent cement meeting ASTM D2564 specifications must be used...

Страница 13: ...es above ground level or the anticipated snow level Vent terminations non direct and direct vent must terminate at least 3 feet above any forced air inlet located within 10 feet NOTE This provision do...

Страница 14: ...pipe Secure vent flue pipe directly into the furnace fitting with the appropriate glue Alternately a small section of 2 pipe may be glued in the furnace socket and a rubber coupling installed to allow...

Страница 15: ...er outlet 5 Install cut end of the flanged section and connect to inducer with rubber coupling supplied with furnace Install screws removed in step 1 securing flange to cabinet MODEL PIPE SIZE 1 2 3 4...

Страница 16: ...per material manufacturers specifications to prevent separation and flue gas leaks Figure 11 Insert flange Cut 2 long R 000142 F Figure 9 CUT HERE Figure 10 Vent Flue Pipe Cuts Upflow Horizontal model...

Страница 17: ...secured to the combustion air intake to prevent inadvertent blockage The tee used in the vent flue termination must be included when determining the number of elbows in the piping system Vent Flue Pi...

Страница 18: ...r specific details on termination construction For details concerning connection of pipes to the furnace refer to the Vent Flue Pipe and Combustion Pipe Standard Furnace Connections or Alternate Furna...

Страница 19: ...ecifications Condensate Drain Lines Drain Trap Acondensing gas furnace achieves its high level of efficiency by extracting heat from the products of combustion to the point where condensation takes pl...

Страница 20: ...ay be added in the area shown in Figure 21 Any unused cabinet opening must be sealed Do not allow drain hose to sag or trap water Figure 21 Drain Exiting Right Side 1 Locate and Install the 45 pipe ho...

Страница 21: ...the top mounting tabs of the trap into the two predrilled holes in the side of the cabinet 9 Refer to Field Supplied Drain section for instructions on field supplied installed drain on outlet of furn...

Страница 22: ...he non grommet end Discard the section without the grommet 5 Insert the cut end of tube 5 through the lower cabinet drain hole 6 Insert 100 degree elbow in the cut end of hose 5 7 Locate hose 6 Using...

Страница 23: ...ses needed for installation and install per the following directions 1 Remove the drain trap and factory installed drain tube assemblies 2 Remove two 1 plugs from right side of cabinet 3 Draining the...

Страница 24: ...n hole 12 Insert 100 elbow in hose 5 and secure with a red clamp 13 Locate hose 4 and cut a cut off a 4 straight section and discard the radius end 14 Connect the 4 straight section of hose 4 to the 1...

Страница 25: ...low NOTE Wire routing must not to interfere with circulator blower operation filter removal or routine maintenance Junction Box Relocation WARNING HIGH VOLTAGE To avoid personal injury or death due to...

Страница 26: ...t not be exceeded to prevent unit overfiring High Altitude Derate When this furnace is installed at high altitude the appropriate High Altitude orifice kit must be applied This is required due to the...

Страница 27: ...1 8 NPT pipe plug fitting accessible for test gauge connection immediately upstream of the gas supply connection to the furnace Always use a back up wrench when making the connection to the gas valve...

Страница 28: ...ation Gas Valve Burners Manual Shut Off Valve upstream from ground joint pipe union Drip Leg Grommet in Standard Gas Line Hole Ground Joint Pipe Union Ground Joint Pipe Union NOTE Union may be inside...

Страница 29: ...de NSCNGPIC CAN CSA B149 1 15 For satisfactory operation propane gas pressure must be 10 WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on thre...

Страница 30: ...an air conditioner coil or Electronic Air Cleaner is used in conjunction with the furnace the readings must also include theses components as shown in the following drawing 4 Consult proper tables for...

Страница 31: ...e furnace The installation of a centrally installed air cleaner cabinet or a return duct filter installation may offer more practicality Clean Comfort brand MERV 11 air cleaners have 5 media filters a...

Страница 32: ...t angle 2000 CFM 20 in X 25 in x 5 AM11 2025 5RA AM11 5RA Bottom return platform 2000 CFM 20 in X 25 in x 5 AM11 2832 5PP Bottom return platform 2000 CFM 20 in X 25 in x 5 AM11 2843 5PP AM11 5 2 X 160...

Страница 33: ...ances on the same gas supply line 4 Measure furnace gas supply pressure with burners firing Supply pressure must be within the range specified in the Inlet Gas Supply Pressure table If supply pressure...

Страница 34: ...pplier if additional input rate adjustment is required 4 Turn ON gas to and relight all other appliances turned off in step 1 Be certain that all appliances are functioning properly and that all pilot...

Страница 35: ...als 4 Connect all unused blower motor leads to the PARK terminals on the integrated control module Any leads not connected to the PARK terminals must be taped 5 Turn ON power to furnace 6 Verify prope...

Страница 36: ...heat exchanger compartment temperatures It is a normally closed electrically automatic reset temperature activated sensor The limit guards against overheating as a result of insufficient conditioned...

Страница 37: ...following a one hour lockout period 2 Manual power interruption Interrupt 115 volt power to the furnace 3 Manual thermostat cycle Lower the thermostat so that there is no longer a call for heat for 1...

Страница 38: ...condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as necessary Flame Sensor Qualified Servicer Only Under some conditions the fuel or air supply c...

Страница 39: ...Loose or improperly connected wiring Pressure switch circuit not closed Induced draft blower isoperating Induced draft blower runs continuously with no further furnace operation Integrated control mo...

Страница 40: ...peration Rollout limit open Integrated control module fuse is blown Check burners for proper alignment Check flue and air inlet piping for blockage proper length elbows and termination Correct as nece...

Страница 41: ...N A 1203 N A 1158 N A 1111 1058 932 HIGH 5 0 2235 38 2166 39 2110 40 2021 42 1956 44 1855 1740 1618 MED 4 0 1955 44 1921 44 1860 46 1808 47 1746 49 1645 1572 1461 MED LO 3 5 1658 51 1634 52 1590 54 15...

Страница 42: ...OX 1 TO115 VAC 1 60HZ OR ID BLOWER PRESSURE SWITCH HEAT H GND WH RD WH GND BURNER COMPARTMENT BLOWER COMPARTMENT N O COOL H BK HI BR BR CAPACITOR YL WH CONTROL PRIMARY LIMIT AUTO RESET BL PU MANUAL RE...

Страница 43: ...nimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less...

Страница 44: ...se DB F Delta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG...

Страница 45: ...45 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 46: ...46 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 47: ...47 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 48: ...e protec on of the standard warranty registering your product is a rela vely short process and en tles you to addi onal warranty protec on except that failure by California and Quebec residents to reg...

Отзывы: