16

3P583694-2E  EM18A021C

Setting addresses for each air conditioner

To control and communicate with the air conditioners, a DIII-NET address needs to be set for each air conditioner.
For detailed instructions on how to set addresses, refer to the 

“DGE601A52 Installation Manual (3P581074-2)” or 

“DGE601A72 Installation Manual (3P581074-6)”.

The installation work of DGE601A53 is complete.

Quick Operation Guide

5.1  Restarting the unit

The DGE601A53 can be restarted by pressing the 

[RESET//] button.

Operate the 

[RESET//] button using a thin rod or similar item.

Only the slot whose 

[RESET//] button has been pressed will restart.

CAUTION

Do not perform the operation with a pointed item. Doing so may result in malfunction.

15

3.2.2 

Wiring specifications

 

Cable type:  CPEV cable, FCPEV cable, CVV(S) cable

 

Core thickness:  CPEV cable, FCPEV cable: 

φ

0.65-0.9 mm, AWG 22-19 

 

CVV(S) cable:  0.75-1.25 mm², AWG 18-16

 

Cable length:  200 m (656 ft.) or less

<Pulse width>

A

B

Pulse width: 20 to 400 ms

Pulse interval: 100 ms or more

CAUTION

 

The contact connected to the contact input terminal must be capable of handling 10 mA at 16 V DC.

 

If an instantaneous contact is used for triggering an emergency stop, use one that has an energisation 
time of 200 ms or more.

NOTE

Once the emergency stop input signal is turned on, all air conditioners stop and do not restart until the emergency 
stop input is cleared.

14

3.1.4  Precautions for using multiple centralized controllers

If multiple centralised controllers are connected on the DIII-NET network, the 

“MAIN (MASTER)” and “SUB 

(SLAVE)” relationship for those controllers.

Set only one of those controllers as MAIN (MASTER), and the other controllers as SUB (SLAVE).

<DIII MASTER>

The 

[DIII MASTER]

 switch is located on the front face of the DGE601A52/

DGE601A72. The switch in the 

[ON] position sets it as “MAIN” and the 

switch in the 

[OFF] position sets it as “SUB”.

3.2  Connecting an emergency stop input device or electric energy meters

3.2.1  Terminals location and schematic connection diagram

Connect the contact input lines or pulse signal lines to the 

[i1] [i2] [i3] [i4] [CM] terminals of Di located on the upper 

part of the front face.

<Schematic drawing of Di connection>

CM

i1

CM

i2

CM

i3

CM

i4

Di

[i1] [i2] [i3] [i4] Pulse input, contact signal input
[CM]

 Common

NOTE

When using open-collector type outputs, connect 

[CM] to the negative side.

13

3.1.2 

Wiring specifications

 

Cable type: 2-core vinyl-insulated vinyl-sheathed cable/vinyl cabtyre cable or 2-core shielded cable 

 

Core thickness: 0.75-1.25 mm², AWG 18-16

WARNING

 

Do not use multicore cables with 3 or more cores.

 

When using a shielded cable, connect only one end of each shield wire to the earth.

 

The maximum wire distance must be kept to 1000 m (3280 ft.) or less, and the total wire length must be 
limited to 2000 m (6561 ft.) or less. 

 

However, when using a shielded cable, the total wire length must be kept to 1500 m (4921 ft.) or less.

3.1.3  Address setup and termination resistor

For each DGE601A53, a unique address needs to be set.

In case of connecting to the DGE601A51/DGE601A71, set a number between “3” and “8”.
In case of connecting to the iTM, set a number between “2” and “8”.

Use the 

[PORT]

 switch located on the front face of each DGE601A53 to set an address. Moreover, the termination 

resistor needs to be set for the DGE601A53 which is the furthest from the DGE601A51/DGE601A71 or iTM.

To set the termination resistor, change the position of the 

[TERM] switch located on the front panel of the DGE601A53 

to the 

[ON] position.

<DGE601A53 PORT (ADDRESS) and TERM>

PORT

ON

OFF

ON

OFF

plus

ADP

IF

D+
D–
S

F1
F2
F1
F2

plus ADP Tx

RESET//

TERM

MASTER

DIII

DIII

Rx

i1
CM
i2
CM

Di

i3

i4
CM

CM

ALARM

DIII

POWER

ALV

NOTE

If both the 

[ALV] and [ALARM] LEDs are lit when powering on the unit after installation, then probably something 

went wrong with the PORT (address) assignment:

 

You set an invalid PORT address. (In case of DGE601A51/DGE601A71, 

“0”“1”“2”, and “9” are not allowed, 

and in case of iTM, 

“0”“1”, and “9”

 are not allowed.)

 

You used the same PORT (address) twice.

Check and correct the PORT (address), then power on the DGE601A52/DGE601A72 again and restart.
Check the status of the 

[ALV] and [ALARM] LEDs.