IM 782-12 • DESTINY AIR HANDLERS 6
www.DaikinApplied.com
Installation
Service Clearances
Leave adequate space around the unit for piping, coils, and
drains. Always have access to at least one side of the unit for
regular service and maintenance. See
for servicing
space requirements. Routine maintenance examples include
filter replacement, drain pan inspection and cleaning, fan
bearing lubrication, and belt adjustment. Provide sufficient
space on the drive side of the fan and the connection side of
the coil for shaft and coil removal, if necessary (refer to the
“Coil Data” section in
for information about coil
sizes). Both the fan drive and coil can be field modified to
right or left hand to accommodate clearance restrictions. See
Reversing the Coil Handing on page 10
For routine maintenance, remove panels on either side of the
unit. See
are available for the fan and filter sections. Allow sufficient
space for service door(s) to swing completely open, or to
meet the clearance requirement of the section it accesses,
whichever is greater. Service doors are not interchangeable
with access panels on the opposite side of the unit. Determine
clearances before specifying doors.
Have at least 42" of clearance in front of electrical power
devices (starters, VFDs, disconnect switches, and combination
devices). Electrical power devices that are mounted on the side
of the unit typically are 6" deep, 12" maximum (see
Figure 2: Servicing Space Requirements
Width
Top
view
Width of
fan section
Width of
C
oil section
30.00”
Width
Height
Vertical unit
Height
Horizontal unit
For Bottom Filter Access Only
Provide 30
Filter Removal
" Vertical Clearance for
Width
Vertical unit
Electric power clearance
42"
12" (maximum)
Wall
Wall
Wall
42"
42"
Horizontal unit