Daikin DCS004A51 Скачать руководство пользователя страница 35

34

English

7.

ABOUT SYSTEM SETUP MENU

7-1 Overview

The System Setup menu is provided in the zone tree area displayed in the Advanced mode. This menu provides the following 
menu items.

: Granted 

: Denied

The following table explains these privileges (system setup menu items).

System Setup Privileges (Menu Item)

Permissions

Administrator

General User

System Setup

Password Setting

Registration of General Users

Deletion of General Users

Assigning Zones to General Users

Creating Schedules

System setting
Menu Name

Description

Reference

Password Setting

Each General User can change his/her own login password.

The Administrator can change not only his/her own login password but also regis-
tered General Users’ login passwords.

See page [37]

Registration of 
General Users

The Administrator can register General Users using this menu item. Registered 
General Users can operate air conditioners and other devices through the web 
interface. Up to 64 General Users can be registered.

See page [38]

Deletion of 
General Users

The Administrator can delete any of the registered General Users.

See page [39]

Assigning Zones to 
General Users

The Administrator can assign one or more zones to each General User. The 
General User can operate devices included in these zones. Zones are created in 
advance using the intelligent Touch Controller console. It is impossible to create a 
zone via the web interface.

See page [39]

Overview: Schedule 
Creation Procedure

The Schedule menu item allows you to create operation schedules and link it to 
one or more zones or groups.

You can automatically start/stop air conditioners at a point in time. The time value 
(Year, Month, Day, Day of week, Hour, Minute) is set in advance on the intelligent 
Touch Controller according to the usage of the air conditioners.

The options provided for creating schedule events are:

• Start/Stop

• Permitting/prohibiting local remote controller 

operations

• Operation mode

• Setting temperature

• Ventilation mode (

)

• Ventilation amount (

)

(

) Only for HRVs 

The following describes the steps required to make a plan to create scheduling 
patterns.

• There are two types of schedule patterns: 7 regular schedule patterns 
(applied to Sun to Sat) and 10 extra schedule patterns (Ex1 to Ex10). To get 
things started, make a plan for creating these 17 schedule patterns on the 
“calendar setting table.” Write down your plan in the “calendar setting table.”

• Do the setting of “calendar setting” : “weekly setting”, “extra schedule pat-

terns”.
Ex.: Regular schedule patterns are for normal business days and extra schedule 

patterns are for a special period such as summer holidays. 
You can create schedule programs for the next 13 months.

• Finally assign events to the above 17 schedule patterns (regular schedule 

patterns: Sun to Sat; extra schedule patterns: Ex1 to Ex10).
Ex.: Starts devices in zone 1 at 9:00 and stops at 17:00    Up to 16 
        operations can be set for each day.

Up to 8 schedule programs can be set, by concerning the schedules above as one.

See page [40]

01_EM04A057_EN.fm  Page 34  Tuesday, February 1, 2005  7:47 PM

Содержание DCS004A51

Страница 1: ...ion manual contains notes for safe use of the product Fou correct use be sure to read this manual carefully before use Store this manual close at hand so that it can be referred to as required MODEL DCS004A51 intelligent Touch Controller Web Software OPERATION MANUAL ...

Страница 2: ... SERVICE 50 1 SAFETY CONSIDERATIONS Please read these SAFETY CONSIDERATIONS carefully before installing air conditioning equipment and be sure to install it correctly After completing the installation make sure that the unit oper ates properly during the start up operation Please instruct the customer on how to operate the unit and keep it maintained Also inform customers that they should store th...

Страница 3: ...ectric leak or may damage the internal electronic parts Do not operate the air conditioner when using a room fumigation type insecticide Failure to observe could cause the chemicals to become deposited in the unit which could endanger the health of those who are hypersensitive to chemicals Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may c...

Страница 4: ... the web interface and Administrator who can setup the system and change system settings See page 5 Two Display Modes You can select the display mode from two modes during login process the Basic mode which provides a simple and easy to use interface and the Advanced mode which allows you to use advanced setting options Basic Mode See page 7 Advanced Mode See page 22 Start Stop Operation You can s...

Страница 5: ... However User 64 can operate monitor air conditioners that other General Users can also operate monitor 1 00 1 01 1 02 1 03 1 04 1 05 1 06 1 07 User 64 1 08 LAN User 1 1 00 1 01 1 02 User 1 User 1 User 2 User 3 User 3 Administrator User 2 64 User 2 1 03 1 04 1 05 User 3 1 06 1 07 1 08 User 64 1 01 1 04 1 07 Inter device communication Maximum number of the registered users Administrator 1 General U...

Страница 6: ...r is able to Operate air conditioners Monitor air conditioners Advanced Mode General Users are able to Monitor air conditioners Operate air conditioners Permit and or prohibit local remote controller operations Change his her own password The Administrator is able to Operate air conditioners Monitor air conditioners Permit and or prohibit local remote controller operations Create schedules Set his...

Страница 7: ...the figure appears The Administrator cannot log into the web interface via multiple PC at a time 4 5 Selecting Display Language To select a display language to be used for the web interface 1 Click the button 1 to display the Display language setting screen Screen 2 2 Click the or button to select a language to be used in this screen 3 Select a language to be used in the web interface by clicking ...

Страница 8: ...n the Basic mode This section describes the Main screen shown in the figure See the next page for more information on each item on this screen 1 2 3 4 The above figure shows the Main screen displayed in the Icon display mode 1 2 3 4 The figure to the left shows the Main screen displayed in the List display mode ...

Страница 9: ...ts one of the categories shown in the figures to the right Devices are grouped into these categories in advance using the intelligent Touch Controller console Icon assigned to each device cannot be changed via the web interface This section explains features of each icon Indoor Units A device registered as an indoor unit appears as an indoor unit icon see Figure 1 In the Icon display mode a temper...

Страница 10: ...tate Error Direction of air flow Air volume COOL HEAT AUTO FAN SET POINT Either of the mode icons to the left OFF ON Communication error Device error 1 2 3 4 0 In the Swing mode the direction changes in the following order and this pattern repeats permanently 0 1 2 3 4 3 2 1 High Low ...

Страница 11: ...by HRV Icons Ventilation mode Ventilation Amount Start Stop state Error Automatic ventilation All heat exchanger ventilation Normal ventilation Low High AUTO Low Fresh up High Fresh up AUTO Fresh up OFF ON Communication error Device error ...

Страница 12: ...e setting on the intelligent Touch Controller console Universal device Start Stop state Universal device Error Lighting device Start Stop state Lighting device Error Zone Start Stop state Zone Error OFF Start 1 Communication error Device error Turning off Turning on Communication error Device error OFF Start 1 Communication error Device error ...

Страница 13: ...ers is used this may not corre spond to the actual room temperature 8 Set temperature Displays the temperature setting of air conditioners You can change this value if required See page 19 9 Air flow flap Displays the direction of air flow of air conditioners You can change this setting if required See page 19 10 Fan speed Displays the air volume of air conditioners You can change this setting if ...

Страница 14: ...can change the setting if required See page 20 8 Freshen up function setting Displays Start Stop state of the Freshen up function You can turn the function on or off if required See page 20 CAUTION For some HRV models 5 7 and or 8 may not be con figured In this case unavailable buttons are grayed out 7 Ventilation amount setting 8 Freshen up function setting 5 Ventilation mode 3 Start Stop 1 Group...

Страница 15: ...the following five icons may appear CAUTION When lighting devices are connected via Dio units The Start Stop buttons 3 can be used When lighting devices are connected via Di units The Start Stop buttons 3 are not displayed 1 Group name 2 Status icon 3 Start Stop 4 Sign display area 5 System status display area CAUTION Note Indicates that the selected group is associated with one or more schedule p...

Страница 16: ... the following five icons may appear CAUTION When lighting devices are connected via Dio units The Start Stop buttons 3 can be used When lighting devices are connected via Di units The Start Stop buttons 3 are not displayed 1 Group name 2 Status icon 3 Start Stop 4 Sign display area 5 System status display area CAUTION Note Indicates that the selected group is associated with one or more schedule ...

Страница 17: ...ed zone is associated with one or more schedule programs In the air conditioner zone area information on the room temperature set temperature operation mode air volume and direction of air flow is provided In the HRV zone area information on the Ventilation mode Ventilation amount and Freshen up setting is pro vided Data of the representative unit is displayed rather than that of the entire zone R...

Страница 18: ... air conditioners and you cannot undo your oper ation Therefore be sure to click only an appropriate button especially when your operation target is a zone 5 8 Starting Stopping All the Devices in a Specific Zone Procedure for starting stopping all the devices in a specific zone Start or stop all the devices included in a specific zone This procedure supports both the Icon display and List display...

Страница 19: ...n a zone Use the group setting area Screen 3 to change the setting of all the devices in a group Click one of the following buttons according to your requirement Changes the operation mode to Cool Changes the operation mode to Heat Changes the operation mode to Fan Changes the operation mode to Set Point Changes the operation mode to Auto HRV Devices Click the tab in the zone setting area Screen 4...

Страница 20: ...Range of temperature settings inherent to the air conditioner main unit Range of temperature as a result of the restriction by tempera ture setting limit set on the intelligent Touch Controller console For more information refer to the intelligent Touch Controller Software manual 5 11 Changing the Direction of Air Flow and Air Volume Procedure for changing the direction of air flow air volume Chan...

Страница 21: ... Use the following buttons on each screen Turns the Freshen up function On Turns the Freshen up function Off Adjusts the Ventilation amount Indicates the Automatic ventilation amount setting Indicates the Strong ventilation amount setting Indicates the Weak ventilation amount setting CAUTION For some HRV models the Freshen up and or Ventilation amount settings cannot be changed In this case unavai...

Страница 22: ... the air conditioner zone area information on the room temperature set temperature operation mode air vol ume and direction of air flow is provided In the HRV zone area information on the Ventilation mode Ventilation amount and Freshen up function is provided Data of the representative unit is displayed rather than that of the entire zone For more information on the zone representative unit is fol...

Страница 23: ... mode When logging into the application in the Advanced mode you will see the following screen 1 2 3 4 5 The above figure shows the Main screen displayed in the Icon display mode 1 2 4 3 The figure to the left shows the Main screen displayed in the List display mode In the List display mode the area 5 is not provided ...

Страница 24: ... page 23 to 24 Launches a dialog box displaying detailed information on the selected zone or group See page 31 Launches a dialog box where you can set up the selected zone or group See page 24 Launches a dialog box describing detailed information on items displayed in the Icon List display modes See page 30 Returns to the screen specified by the previous zone tree setting You can return to the scr...

Страница 25: ...ration mode Switch the operation mode of the air conditioner On the Monitoring screen operation is allowed with either Icon or List as the display type In the figure Screen 1 the devices are displayed in the Icon dis play mode The operation mode can be switched by zone or by group Procedure 1 To change the setting for all the devices in a zone select the Monitoring Zone list item from the zone tre...

Страница 26: ...en 2 Operation appears 3 Select the Set checkbox 3 in the Set temperature frame and set the integral and decimal parts using the pull down menus 4 In a zone setting the pull down menus are pre populated with allowable temperature values for the air conditioners in the zone See the following example 4 Press the To cancel the setting press the Ex For the zone setting in the figure 1 the temperature ...

Страница 27: ...her Procedure 1 On Screen 1 Monitoring select a zone or a group from the pull down menu 1 Select a zone or a group of which the temperature setting is to be changed 2 To change the setting for all the devices in a group select the zone including the group from the zone tree area 1 and select the group from the main display area 2 2 Press the Screen 2 Operation appears 3 Select the Reset checkbox i...

Страница 28: ... of the radio buttons Low or High to select desired air volume When setting the direction of air flow select the Set checkbox in the Direction of air flow frame 4 and select your desired value using the pull down menu Any integer value from 0 to 7 can be selected 4 Press the To cancel the setting press the Guideline for determining the direction of air flow and air volume 6 9 Changing the HRV sett...

Страница 29: ... In this frame you can start or stop the devices Select the Set checkbox and check a desired radio button 9 Ventilation mode In this frame you can select a Ventilation mode Select the Set checkbox and check a desired radio button 10 Ventilation amount In this frame you can select a Ventilation amount setting Select the Set checkbox and check a desired radio button 11 Filter sign When the Reset ind...

Страница 30: ...ted Operation Mode Permitted or Prohibited Set Temperature Permitted or Prohibited 4 Upon completion click the button To cancel your settings click the button 6 11 Monitoring Operations of All the Devices in a Specific Zone or Group Procedures for monitoring zone or group operations Monitor operations in both the Icon and List display modes Select a display mode using the or button Operations can ...

Страница 31: ...up informa tion is displayed Start Stop state For a zone see the following section Presence absence of error For a zone see the following section Presence absence of Auto Control setting For a zone see the following section Presence absence of filter element signs For a zone see the following section Temperature setting For a zone the temperature setting of the representative unit is shown Operati...

Страница 32: ...e zone including the group from the zone tree area Then select the target zone or group in the main display area 2 2 Click the button The Information screen Screen 2 appears and provides the following data items For an air conditioner group 1 Name Group name 2 Description Group description 3 Type Air conditioner or device 4 D3 Address Address between 1 00 and 4 15 5 Schedule Enable Disabled 6 Heat...

Страница 33: ...m the zone tree area Then select the target zone or group in the main display area 2 2 Click the button to display the Setup screen Screen 2 This screen provides the following information 1 Name Description Displays the name and description of a zone or group 2 Current Condition Start Stop state Room temperature Operation Mode Presence or absence of filter signs 3 Air volume Displays current air v...

Страница 34: ...t Ventilation mode 5 Ventilation amount Displays the current Ventilation amount Upon completion click the 6 button to return to the Main screen When Monitoring a Group of HRVs When selecting an HRV group the Group setup screen Screen 4 appears You can view the following items in this screen 7 Current Condition Start Stop state Ventilation mode Ventilation amount Filter sign 8 R C Mode Start Stop D...

Страница 35: ... interface See page 39 Overview Schedule Creation Procedure The Schedule menu item allows you to create operation schedules and link it to one or more zones or groups You can automatically start stop air conditioners at a point in time The time value Year Month Day Day of week Hour Minute is set in advance on the intelligent Touch Controller according to the usage of the air conditioners The optio...

Страница 36: ...2F Zone 3F SUN Holiday Holiday Holiday MON 9 30 18 00 Duty hours 8 30 17 00 Duty hours 12 00 13 00 Lunch break 17 00 22 00 Overtime hours 22 00 Closing office 9 00 14 30 Duty hours TUE ditto ditto ditto WED 9 30 17 00 Duty hours ditto ditto THU same as Mon ditto ditto FRI same as Mon ditto ditto SAT Holiday Holiday Holiday Ex1 third Sat of every month Concerned as a working day Concerned as a work...

Страница 37: ...0 Zone 2F OFF Null Null Prohibits remote controller operations Time Target Zone Start Stop Opera tion mode Set temperature Remote Controller Code 9 00 Zone 2F Null Null Null Override 17 00 Zone 2F OFF Null Null Prohibits remote controller operations Time Target Zone Start Stop Opera tion mode Set temperature Remote Controller Code 8 30 Zone 2F ON Null Null Override 12 00 Zone 2F OFF Null Null Null...

Страница 38: ... passwords for web interface and console A new Administrator password set in this screen is also used for the system console menu and you will not be able to use the system console menu without entering the new password On the other hand setting an Administrator password on the system console not only makes the console unavailable with out entering the password but also replaces the existing Admin...

Страница 39: ...he interface as the Administrator and select the System Setup node 1 from the zone tree area to display the System setup main screen Screen 1 2 Double click the User settg icon 2 to display the User settg dialog box Screen 2 3 Click the button 3 to display the Add user dialog box Screen 3 4 Enter the user name to be registered in the User name field 4 5 Enter a new password of the User in the Pass...

Страница 40: ...splay the Deletion of user confirmation dialog box Screen 3 Click the Yes button to confirm your selection Assigning Zones to General Users 1 Log into the interface as the Administrator and select the System Setup node 1 from the zone tree area to display the System setup main screen Screen 1 2 Double click the User settg icon 2 to display the User settg dialog box Screen 2 1 2 Screen 1 System set...

Страница 41: ...reen This section describes the components of the main sched uling screen When selecting the Schedule node 1 from the zone tree area you will see the following screen the main scheduling screen 1 Schedule node in the zone tree area Selecting this node displays the main scheduling screen 2 Schedule program list Lists the name and status Enabled disabled for each schedule program 3 Enable Disable ra...

Страница 42: ...le patterns See page 42 3 Copies or deletes schedule patterns See page 46 4 Renames Ex schedule patterns See page 47 5 Renames schedule programs displayed on the main sched uling screen See page 47 6 Schedule Calendar area Renames schedule programs displayed on the main sched uling screen See page 45 7 Legends area Describes the symbols representing each schedule pattern 8 Used to assign one or mo...

Страница 43: ...le program See the following pages for the instructions Regular schedule pattern This page Ex schedule pattern See page 44 8 4 Creating Regular Schedule Patterns To create regular schedule patterns 1 To create regular schedule patterns Sun to Sat select a tar get day of the week by clicking an appropriate pattern radio button 1 2 Click the button 2 to display the Pattern change dialog box Screen 2...

Страница 44: ...it the start stop operation through remote controllers Operation Mode Permit or prohibit the modification of the operation mode through remote controllers Set Temperature Permit or prohibit the modification of the temperature setting through remote controllers Ventilation mode Set the HRV s ventilation mode using the radio buttons Ventilation amount Set the HRV s ventilation amount CAUTION When th...

Страница 45: ...le patterns Ex1 to 10 in the Schedule Setup screen Screen 1 Click an appropriate radio button 1 to select the Ex schedule pattern to be set up or changed 2 Click the button to display the Pattern change dialog box Screen 2 3 To add a new schedule event click the button 3 A new event item appears in the top row of the schedule event list 6 You can set up or change a new or existing event in this li...

Страница 46: ...lick the button 9 The Calendar change screen Screen 2 appears Click the Set checkbox 2 10 Click the appropriate radio button to select the Ex schedule pattern to be set 11 With the Ex schedule pattern radio button selected click a date on the calendar to assign that date to the Ex schedule pattern To deselect an Ex schedule pattern assigned date select the Week radio button and then click the date...

Страница 47: ... following options are provided All settings are deleted Only the calendar setting is deleted Click the button 5 Then click the button to complete the copy pro cess 8 7 Copying or Deleting Schedule Events To copy or delete schedule events 1 Click the button 1 in the Schedule Setup screen Screen 1 2 The Edit Schedule screen Screen 2 appears Copy Procedure Select a source date in the left pull down ...

Страница 48: ...ton 2 The Edit Schedule Setup screen Screen 2 appears Click the button 2 3 The Name Change dialog box Screen 3 appears Enter a name into the field of this box Up to 16 characters can be entered 4 Click the button to complete this process 5 To name an Ex schedule pattern select the Ex schedule pattern from the list 3 on the Schedule Setup screen Screen 2 and click the button 4 6 The Name Change dia...

Страница 49: ...s were started from the intelligent Touch Controller console or any centralized controller 3 A schedule program set via the web interface started the con ditioners 4 The Temperature Limit function of the intelligent Touch Con troller started the air conditioners This function prevents room temperature from becoming extremely high or low by automatically starting air condition ers when a specified ...

Страница 50: ...Controller address entered in the browser is incorrect The intelligent Touch Controller is turned off The network is congested for any reason In this case wait for a while and then access it again When accessing the intelligent Touch Controller web interface the following screen appears This message informs you that Java plugin is not installed or the version of the installed Java plugin is not su...

Страница 51: ...may be congested for any reason In this case wait for a while and then access it again The room temperature value on the intelligent Touch Controller web interface does not match the actual measurement value Since the suction temperature of air conditioners is used this may not reflect the actual measurement value especially when the indoor unit s fans are stopped This temperature value should be ...

Страница 52: ... 0502 HT EM04A057 ...

Отзывы: