SYSTEM OPERATION
24
2 Stage Status Codes
Main Menu
Option Menu
Active Alarm menu
xx
( xx: code numbers )
Last 6 Faults
xx
( xx: code numbers )
Code Release Number
CR Number
Reset to Factory Default
yes, no
Blower Speed for Continous Fan Mode
xx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 1st Stage Compressor Mode
xx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 2nd Stage Compressor Mode
xx
( xx: Blower Speed Number
F01, F02.. )
Cool On Delay
Delay, Seconds
Default set at 7 Secs,
Adjustments can be made in
7 Secs increments from 0 to
35 Secs
Cool Off Delay
Delay, Seconds
Default set at 65 Secs,
Adjustments can be made in
5 Secs increments from 0 to
120 Secs
Blower Speed for 1st Stage Gas Heat Mode
xx
( xx: Blower Speed Number
F01, F02.. )
Blower Speed for 2nd Stage Gas Heat Mode
xx
( xx: Blower Speed Number
F01, F02.. )
Gas Heat On Delay
Delay, Seconds
Default set at 30 Secs,
Adjustments can be made in
5 Secs increments from 5 to
30 Secs
Gas heat Off Delay
Delay, Seconds
Default set at 90 Secs,
Adjustments can be made in
30 Secs increments from 30
to 180 Secs
Automatic Heat Staging - For Two Stage Control
no, 10, 20,
30, 60, AUt
Refer to Section
"CHANGING HEATING
MODE SETTING"