D2CND024A1/4AA + D2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-3E – 2017.07
Flue length determination
Flue duct length (L) is measured from lip of the elbow to end of the
flue terminal.
L
a
L
Flue duct length
a
Distance of outer lip of terminal to outer wall,
a≤50 mm
Note:
Flue ducts are inserted 45 mm into elbows and extensions.
Type C33x (concentric flue system)
The boiler draws combustion air from the outside and expels flue
gas to the outside through a concentric coaxial pipe via the roof.
The terminal outlets from separate combustion and air supply
circuits shall fit inside a square of 50 cm and the distance between
the planes of the two orifices shall be less than 50 cm.
a
b
e
c
c
d
d
f
g
h
L
i
a
Roof terminal 60/100
b
Tile roof outlet kit
Optional:
c
45° elbow 60/100
d
Extension 60/100 mm
e
Flat roof outlet kit
f
90° elbow 60/100
g
45° elbow 60/100
h
30° elbow 60/100
i
Extension 60/100
L = 500-1000 mm
Allowable flue length for C33x
D2TND*
D2CND*
Concentric 60/100 mm
12.5 m
7.6 m
Concentric 80/125 mm
42.8 m
25.6 m
Equivalent length of options
90° elbow 60/100 mm
1.5 m
45° elbow 60/100 mm
1.0 m
30° elbow 60/100 mm
1.0 m
90° elbow 80/125 mm
1.5 m
45° elbow 80/125 mm
1.0 m
30° elbow 80/125 mm
1.0 m
60/100 Vertical flue length can be increased up to 19.2 metres
(for
D2TND*
) / 13.6 metres (for
D2CND*
)by adjusting the
parameter C3 to 3 from the user interface. Refer to servicing
instructions for this operation.
Subtract equivalent length value of bends from the allowable flue
length value.
80/125 mm flue system
To increase the maximum allowable flue duct length, 80/125 mm
concentric flue ducts can be used instead of 60/100 mm. In this
case, C13x and C33x flue systems should start with a 60/100 to
80/125 adapter coupled to the flue outlet.