7.10.10  Sweeper Mode

Sweeper mode enables burner-operation independent to CH 

or DHW modes. Burner can be operated at maximum or min

-

imum capacity at sweeper mode.

Boiler operates at central heating during sweeper mode (The 

diverter valve will switch over to CH position).

Before  activating  the  sweeper  mode,  gas  analyzer  device 

should be mounted to read the flue gas values. 

To activate the sweeper mode follow the instructions below:

Press ‘Menu/Enter’ 

and ‘Cancel/Back’ but

-

tons at the same time 

for 5 seconds (in any 

mode sweeper mode 

can be activated).

‘TST’ caption and 

capacity percentage 

will appear on the 

screen.

When  first  sweeper 

mode  is  activated, 

boiler  will  operate  at 

maximum  capacity. To 

switch between maxi-

mum and minimum ca-

pacities,  press  ‘Mode/

Reset’ button.

To quit the sweeper mode, press ‘Menu/Enter’ and ‘Cancel/ 

Back’ buttons at the same time for 5 seconds.Sweeper mode 

will  be  deactivated  and  boiler  will  turn  to  normal  operation 

mode.

SAFETY OPERATION FUNCTIONS

Aim of this function is to fill the condensate trap in case con

-

densate  water  is  evaporated,  due  to  no  operation  for  long 

time. If water inside the trap is evaporated, this may cause 

gas leakage from the condensate trap.

When Low Water temp function is active;

 

1. CH set value is constant and set to 45°C.

2. Pump runs at 100% capacity.

Function  is  active  for  10  minutes  of  burner  operation. After 

function is ended, boiler operates according to central heating 

setpoint adjusted by the customer and pump modulates ac

-

cording to flow-return temperature difference, as usual.

While function is active,     icon blinks. Please note that Info 

icon blinks independent of burner operation during LWT func

-

tion.

There are two conditions for Low Water Temperature Function 

(LWT) to be active;

1. After power ON; where the boiler has been disconnected 

from mains (230 V) for at least 3 seconds.

2. After each 90 days.

LWT function is only activated if operation mode is “Winter” 

or “CH only” and room thermostat is closed, in other words, a 

central heating demand is present. This is valid for both two 

conditions defined above.

8.1 

Low Water Temperature (LWT) Function  

Sweeper Mode and DHW Mode have higher 

priority than LWT function; i.e. LWT function is 

interrupted in case water is being tapped, but 

after tapping is finished, LWT function continues 

its operation.

INFORMATION

The LWT function duration 10 minutes is the time 

that burner is active. If burner stops during LWT 

operation (i.e. 45oC + P18 ‘CH Hysteresis’ is 

exceeded), counter also stops and waits for next 

burner operation. Counter also stops during water 

tapping and sweeper mode.

INFORMATION

8.2 

Temperature Gradient Supervision 

The burner will be blocked for at least 60 seconds, if the tem

-

perature gradient of the flow-sensor exceeds the limit 5K/s.

Remark:

 Temperature gradient supervision is not active 

while sweeper mode is active.

8 Safety operation functions

Содержание D2CND024A1AA

Страница 1: ...Servicing manual Wall mounted condensing boiler D2CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA English Servicing manual Wall mounted condensing boiler...

Страница 2: ...CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA Wall mounted condensing boiler ESIE17 09 2017 11 Servicing manual 2 LOG Version Code Description Date ESIE17 09 Document release 1 11 201...

Страница 3: ...s 26 7 1 2 LCD screen 26 7 1 3 Status icons 26 7 1 4 Daikin Eye 26 7 1 5 Stand by 26 7 1 6 Flame 26 7 1 7 Error 26 7 2 Operating The Appliance 27 7 2 1 Low Water Temperature Function 27 7 2 2 Electron...

Страница 4: ...s composed of an LCD screen push buttons and two dials and which is located on the front cover of the appliance The appliance is equipped with several safety systems to pro tect it against dangerous c...

Страница 5: ...w temperature sensor which is located at the outlet of the main heat exchanger This protection ac tivates the boiler pump when the water temperature drops below depends on P03 parameter value and it a...

Страница 6: ...ostat 17 Fan 18 Return temperature sensor 19 Silencer 20 Automatic air vent pump 21 Water pressure sensor 22 By pass 23 Boiler pump 24 Domestic hot water flow sensor 25 Domestic hot water flow limiter...

Страница 7: ...56 68 56 77 Combustion products temperature min max G31 C 56 60 56 68 55 76 Maximum combustion products temp at nominal heat input C 80 82 90 CO2 Emission at nominal and minimum heat input G20 9 0 0...

Страница 8: ...14_FLOW X4 15_OWC X4 16_OWC X3 1_PwmWh X3 2_PwmB1 X3 3_ReWhSw X3 4_Gnd X3 5_5v X2 8_LP1 X2 1_SOLs X2 2_SOL X2 3_RTs X2 4_RT X2 5_NPSRT X2 6_LPSRT X2 7_NP1 X5 X4 X3 X2 X1 X1 1_NP X1 2_LP X1 3_NI X1 4_...

Страница 9: ...stable spanner Number 30 32 24 26 14 18 3 3 Spare parts To ensure long lasting operation of the appliance always use original spare parts Spare parts must be ordered from spare parts catalog by specif...

Страница 10: ...Domestic Hot Water Circuit Isolate the appliance from power supply and closedown the gas valve Close all the isolating valves on the central heating circuit Open the drain valve 1 and drain the centr...

Страница 11: ...from power supply and closedown the gas valve Undo M5 screw at the figure 1 Remove the assembly clips of front cover 2 Remove the front cover by pulling up 3 Undo 2 sheet screw holding control panel 4...

Страница 12: ...connector of flow sensor 2 and pressure sensor 3 Disconnect the wire connector of 3 way valve refer to 4 6 1 Dismantle the ignition electrode and earth cable from the power supply 4 Firstly loosen th...

Страница 13: ...socket s housing and disconnect the sensor 13 Take out cable connections of fan manually 14 Re assemble in reverse order Be careful all electrical cables during the removal of cable group wire harnes...

Страница 14: ...e gas supply pipe from the gas valve and brass nipple by using wrench 1 Unscrew the 2xM5 screws that connect gas manifold and burner hood 2 Seperate the gas manifold from the burner hood clip and take...

Страница 15: ...low return and flue NTC sensors and high limit thermostat refer to Section 4 3 Take out the syphon parts refer to Section 4 8 Unscrew the screws that connect hermetic cabinet and right cover 1 Remove...

Страница 16: ...nted condensing boiler ESIE17 09 2017 11 Servicing manual 16 4 Part replacement Remove the screw holding the hermetic cabinet with main heat exchanger M5 allen 9 Detach the main heat exchanger by push...

Страница 17: ...nti nel s products which are appropriate for cleaning of heat exchanger inside Inspect the heat exchanger from the top and bottom Take any foreign object Use the cleaning tool into the heat exchanger...

Страница 18: ...2 Undo the screws that connect to hermetic cabinet to the pump 3 Undo the 2 screws that connect to hermetic cabinet to the pump 4 for T models Loosen the union joint that provides the return pipe pump...

Страница 19: ...the DHW flow CH flow installation pipes from the boiler by using wrench refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the expansion vessel refer to Section 4 10 Remove the fast...

Страница 20: ...osedown the gas valve Drain the water from the boiler refer to Section 4 1 Open the appliance refer to Section 4 2 Take out the silencer refer to Section 4 4 Remove the syphon part from condensate sum...

Страница 21: ...efer to Section 4 2 Remove the left cover of the boiler unscrew the screws that connects hermetic cabin and left cover 1 Undo the screws which connect expansion vessel and flow hydroblock 2 Disconnect...

Страница 22: ...support s 3 screws holding the main pcb and remove the cable support 4 Unscrew the 3 screws that connect PCB and control panel 5 Isolate the appliance from power supply and closedown the gas valve Ope...

Страница 23: ...pump and heat exchanger are opened Vent the air from the installation with the manual air vent screws on the radiators Make sure screws are tightened after venting If after the purge the pressure dec...

Страница 24: ...w you can see the Cable glands placement Holes on the bottom sheet that are reserved for cable glands are covered with insulation material The insulation material must be bored if glands are to be use...

Страница 25: ...fter first power ON the boiler does not increase its capacity above a preset value for about 12 minutes even if there is demand First 0 2 minutes The electronic gas adapti ve system calibrates itself...

Страница 26: ...ashes to its maximum then constantly keeps glowing during burner operation with blue LED 7 1 7 Error The Daikin eye will go into error mode when a warning lockout or blocking error occurs During the e...

Страница 27: ...re at stand by mode 7 3 2 Selecting Operation Mode The operation mode can be changed by pushing the Mode button 7 4 Description of the Operation Modes 7 4 1 Stand by Mode In stand by mode both central...

Страница 28: ...o room ther mostat or outdoor sensor are connected The central heating water temperature setpoint is displayed The setpoint can be adjusted with the left dial The icon is shown on the screen when cent...

Страница 29: ...Note Independent of personal use pattern Comfort mode preheating function could be adjusted to operate continuously from the user settings For example When the domestic hot water DHW mode is activate...

Страница 30: ...ximum value during domestic hot water operation 100 c A10 0 Standby mode burner is not active A10 1 Start up preparation to ignition A10 2 Ignition and flame stabilisition phase A10 3 Release control...

Страница 31: ...onnected this parameter value is the central heating water tempearture setpoint when there is no a heat demand Note For this parameter value to be active Reducing mode have to be enabled by your servi...

Страница 32: ...0 20 P19 Min CH flow temp setpoint C 30 10 30 P00 In case Opentherm thermostat is switched off no heat demand boiler is either switched off 0 or operates in redu ction mode 1 P01 Weather compensation...

Страница 33: ...ble only for storage tank type models P15 Max temperature that can be adjusted by left dial when setting central heating flow temperature P16 This parameter is a read only parameter which shows the co...

Страница 34: ...0 C 10 circuits and lenght of the each circuit is 80 metres without an additional pump When the boiler is connected to an UFH system the following parameter changes must certainly be done Parameter Ma...

Страница 35: ...ir ratio will be far from average value which may also result in ignition problems delayed or loud ignition If such problems are present C02 parameter must be optimized first If C02 parameter change i...

Страница 36: ...may cause loud ignition C03 This parameter is used to increase maximum allowable flue duct length by increasing fan speed Adjust this parameter to 3 to use longer flue ducts for C13x and C33x types of...

Страница 37: ...e pass word as 043 c For 100 calibration and C12 C13 adjustment set the password as 046 Press Enter button The boiler will start calibration ac cording to above mentioned input values LED s on the scr...

Страница 38: ...set to 45 C 2 Pump runs at 100 capacity Function is active for 10 minutes of burner operation After function is ended boiler operates according to central heating setpoint adjusted by the customer an...

Страница 39: ...mall plug which contains a programmed memory With BCC set of parameters inside the PCB can be changed at field without need to change the PCB itself The BCC con tains all control parameters and safety...

Страница 40: ...or code will still be shown on display Resetting the boiler will remove the error 9 1 4 Error during Parameter transfer If an error occurs during the Parameter transfer or if parameter update is not i...

Страница 41: ...12 66 Ion base val ue exceeds lower factory limit Reset the boiler Make a manuel calibration Check the ionization elecktrode it s cable connection and it s earth cable Replace if defective ER ROR CODE...

Страница 42: ...leshooting ERROR CODE REASON ELIMINATION 81 01 Flow tem perature sensor fault Check continuity between the sen sor and PCB replace wire harness if necessary Check flue tempera ture sensor resistance u...

Страница 43: ...the building should be checked and voltage stabiliser should be used for smooth operation U4 65 Opentherm RT connection is defective Boiler operates as if Opentherm room thermostat not connected Check...

Страница 44: ...TMA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr ESIE17 09 2017 11 C...

Отзывы: