Function
2.
Basic Control
2.1
Normal Operation
Cooling Operation
Heating Operation
Heating operation is not functional at an outdoor air temperature of 30
°
CDB or more.
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, compressor
operating frequency upper limit control with
inverter protection control, dew prevention control,
and freeze-up protection control.
Outdoor unit fan
Cooling fan control
Four way valve
OFF
Main electronic expansion valve (EV1)
2000 pls
Subcooling electronic expansion valve
(EV2)
PI control
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Receiver gas discharging valve (SVG)
OFF
This valve turns on with dew prevention control.
BP unit electronic expansion valve
(operating room)
SH control
BP unit electronic expansion valve
(stopping room)
0 pls
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan
STEP8
The fan step changes to STEP1 with high pressure
> 3.2MPa.
Four way valve
ON
Main electronic expansion valve (EV1)
PI control
Subcooling electronic expansion valve
(EV2)
0 pls
The opening of this valve changes with high
pressure > 3.2MPa.
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Receiver gas discharging valve (SVG)
OFF
—
BP unit electronic expansion valve
(operating room)
SC control
BP unit electronic expansion valve
(stopping room)
80 pls
The opening of this valve changes with insufficient
gas control.
Содержание D-Series
Страница 1: ...Si18 525B Applied Models Super Multi Plus Cooling only Super Multi Plus Heat Pump D Series ...
Страница 33: ...List of Functions Si18 525B 20 List of Functions ...
Страница 34: ...Si18 525B Specifications 21 Part 2 Specifications 1 Specifications 22 1 1 Cooling Only 22 1 2 Heat Pump 42 ...
Страница 71: ...Specifications Si18 525B 58 Specifications ...
Страница 107: ...Printed Circuit Board Connector Wiring Diagram Si18 525B 94 Printed Circuit Board Connector Wiring Diagram ...
Страница 117: ...Refrigerant Flow for Each Operation Mode Si18 525B 104 Refrigerant Circuit ...
Страница 171: ...Indoor Unit SkyAir Models Si18 525B 158 Function ...
Страница 207: ...Test Operation and Field Setting for RA Indoor Unit Si18 525B 194 Test Operation ...
Страница 336: ...Si18 525B Service Check Function Troubleshooting 323 ...
Страница 443: ...BP Unit Si18 525B 430 Removal Procedure The clamps are to be kept in stock Step Procedure Points Clamps Q0529 ...
Страница 469: ...Wiring Diagrams Si18 525B 456 Appendix ...
Страница 475: ...Si18 525B vi Index ...