Basic Control System Diagnostic
Unit controller, extension modules and communication modules are equipped with two status LED, BSP and BUS, to
indicate the operational status of the devices. The
“BUS” LED indicates the status of the communication with the controller.
The meaning of the two status LED is indicated below.
-
MAIN CONTROLLER
-
BSP LED
LED Color
Mode
Solid Green
Application running
Solid Yellow
Application loaded but not running (*) or BSP Upgrade mode active
Solid Red
Hardware Error (*)
Flashing Green
BSP startup phase. The controller needs time for starting.
Flashing Yellow
Application not loaded (*)
Flashing Yellow/Red
Fail safe mode (in case that the BSP upgrade was interrupted)
Flashing Red
BSP Error (software error*)
Flashing Red/Green
Application/BSP update or initialization
(*) Contact Service.
-
EXTENSION MODULES
-
BSP LED
LED Color
Mode
Solid Green
BSP running
Solid Red
Hardware Error (*)
Flashing Red
BSP Error (*)
Flashing Red/Green
BSP upgrade mode
-
BUS LED
LED Color
Mode
Solid Green
Communication running, I/O working
Solid Yellow
Communication running but parameter from the application wrong or missing, or
uncorrect factory calibration
Solid Red
Communication down (*)