Daikin Clima-Flex CLIC STAND ALONE Series Скачать руководство пользователя страница 41

iom-clicsa-cf-eng

www.clima-flex.com

41

Index

S

ize Acronym

DataType

Min

Value

Max

Value R/W

Init

Value UoM

Description

211

2

PwrRunCircs_Perc

REAL

R

0

PERCENT

PwrRunCircs_Perc - Circuit capacity percentage by 
compressors ON

213

2

AFC2

REAL

R

0

CELSIUS

AFC2 - Cond.2 frost temp

215

2

AFE1

REAL

R

0

CELSIUS

AFE1 - Evap.1 frost temp.

217

2

AFC1

REAL

R

0

CELSIUS

AFC1 - Cond.1 frost temp

219

1

IOprbCfgWrn

UINT

R

0

IOcfgPrbWrn - I/O probe confi guration warnings

220

2

W_UsrTempRegPID

REAL

R

0

CELSIUS

W_UsrTempRegPID - Water temperature value used 
by control

226

1

DfrStatus_Circ1

UINT

Defrost status of circ 1

227

2

AIN_PwrReq_Circ1

REAL

R

0

PERCENT

Capacity request using analogue input on circuit 1

231

1

SWverEXP

UINT

R

0

Firmware B version on expansion board

232

1

SWverMAIN

UINT

R

0

Firmware B version on main board

233

1

PWRP_ErrCode_Circ1 UDINT

-

-

R

-

-

Power+ circuit 1 error code

234

1

PWRP_ErrCode_Circ2 UDINT

-

-

R

-

-

Power+ circuit 2 error code

Input 

S

tatus

Index

S

ize Acronym

DataType Min

Value

Max

Value R/W InitValue UoM Description

0

1

A01

BOOL

R

FALSE

Unit - Error in the number of retain memory writes

1

1

A02

BOOL

R

FALSE

Unit - Error in retain memory writes

2

1

A03

BOOL

R

FALSE

Unit - Remote alarm by digital input

3

1

A04

BOOL

R

FALSE

Unit - Remote set point out of range alarm

4

1

A05

BOOL

R

FALSE

Unit - User return water temperature probe broken or 
disconnected alarm

5

1

A06

BOOL

R

FALSE

Unit - User delivery water temperature probe broken or 
disconnected alarm

6

1

A07

BOOL

R

FALSE

Unit - Tank temperature probe broken or disconnected alarm

7

1

A08

BOOL

R

FALSE

Unit - User pump 1 overload

8

1

A09

BOOL

R

FALSE

Unit - User pump 2 overload

9

1

A10

BOOL

R

FALSE

Unit - Flow switch alarm, no fl ow present with user pump 1 
active

10

1

A11

BOOL

R

FALSE

Unit - Flow switch alarm, no fl ow present with user pump 2 
active

11

1

A12

BOOL

R

FALSE

Unit - User pump group alarm

12

1

A13

BOOL

R

FALSE

Unit - User 1 pump maintenance

13

1

A14

BOOL

R

FALSE

Unit - User 2 pump maintenance

14

1

A15

BOOL

R

FALSE

Unit - High chilled water temperature

15

1

A16

BOOL

R

FALSE

Unit - Source return water/air temperature probe broken or 
disconnected alarm

16

1

A17

BOOL

R

FALSE

Unit - Source 1 pump maintenance

17

1

A18

BOOL

R

FALSE

Unit - Free cooling fault

18

1

A19

BOOL

R

FALSE

Circuit 1 - Discharge pressure probe broken or disconnected 
alarm

19

1

A20

BOOL

R

FALSE

Circuit 1 - Condensing temperature probe broken or discon-
nected alarm

20

1

A21

BOOL

R

FALSE

Circuit 1 - Suction pressure probe broken or disconnected 
alarm

21

1

A22

BOOL

R

FALSE

Circuit 1 - Evaporation temperature probe broken or discon-
nected alarm

22

1

A23

BOOL

R

FALSE

Circuit 1 - Discharge temperature probe broken or discon-
nected alarm

23

1

A24

BOOL

R

FALSE

Circuit 1 - Suction temperature probe broken or disconnect-
ed alarm

24

1

A25

BOOL

R

FALSE

Circuit 1 - High pressure alarm from pressure switch

25

1

A26

BOOL

R

FALSE

Circuit 1 - High pressure alarm from transducer

26

1

A27

BOOL

R

FALSE

Circuit 1 - Low pressure alarm from transducer

27

1

A28

BOOL

R

FALSE

Circuit 1 or unit - Frost evaporation temperature alarm

28

1

A29

BOOL

R

FALSE

Circuit 1 - Low pressure alarm from pressure switch

29

1

A30

BOOL

R

FALSE

Circuit 1 - Overload compressor 1

30

1

A31

BOOL

R

FALSE

Circuit 1 - Overload compressor 2

31

1

A32

BOOL

R

FALSE

Circuit 1 - Compressor 1 maintenance

32

1

A33

BOOL

R

FALSE

Circuit 1 - Compressor 2 maintenance

33

1

A34

BOOL

R

FALSE

Circuit 1 - Source fan 1 maintenance

34

1

A35

BOOL

R

FALSE

Circuit 1 EVD - Low superheat (SH)

35

1

A36

BOOL

R

FALSE

Circuit 1 EVD - Low evaporation pressure (LOP)

36

1

A37

BOOL

R

FALSE

Circuit 1 EVD - Maximum evaporating pressure (MOP)

37

1

A38

BOOL

R

FALSE

Circuit 1 EVD - Valve motor error

38

1

A39

BOOL

R

FALSE

Circuit 1 EVD - Emergency closing

39

1

A40

BOOL

R

FALSE

Circuit 1 EVD - Incomplete valve closing

40

1

A41

BOOL

R

FALSE

Circuit 1 EVD - Offl  ine

41

1

A42

BOOL

R

FALSE

Circuit 1 Envelope - General alarm + Zone alarm

42

1

A43

BOOL

R

FALSE

Circuit 1 BLDC - Delta pressure greater than the allowable 
at startup

43

1

A44

BOOL

R

FALSE

Circuit 1 BLDC - Starting failure

44

1

A45

BOOL

R

FALSE

Circuit 1 BLDC - Low diff erential pressure

45

1

A46

BOOL

R

FALSE

Circuit 1 BLDC - High discharge gas temperature

46

1

A47

BOOL

R

FALSE

Circuit 1 Inverter - Offl  ine

47

1

A48

BOOL

R

FALSE

Circuit 1 Inverter - General alarm + Error code

48

1

A49

BOOL

R

FALSE

Unit - Secondary board is offl  ine

49

1

A50

BOOL

R

FALSE

Unit - Error in the number of retain memory writes on 
Secondary board

50

1

A51

BOOL

R

FALSE

Unit - Error in retain memory writes on Secondary board

Mapping Table 

Содержание Clima-Flex CLIC STAND ALONE Series

Страница 1: ...ion and Maintenance Manual CLIC STAND ALONE Series Air Cooled Scroll Compressor Chiller Water Generator Unit Model 25 TR Refrigerant HFC 410A 50 60 Hz IOM Group Chiller Part Number IOM CLIC STAND ALON...

Страница 2: ...facility Safety Warning 4 General Description 5 Features Benefits 6 Installation and Application Information 8 Refrigeration Schematics 14 Dimensions and Weights Packaged Units 15 Refrigerant Charge...

Страница 3: ...zed at least 12 hours before startup Chiller components EXV Sensors Transducers installed and wired properly Wiring complies with National Electrical Code and local codes See Notes Miscellaneous Yes N...

Страница 4: ...ge breaker may result in electric shock or fire WARNING If refrigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to fol...

Страница 5: ...Only H Heat Pump UNITS 1 Stand alone 2 2 units 3 3 units 4 4 units 5 5 units 6 6 units 7 7 units 8 8 units 9 units 10 10 units CONDENSER FAN A Axial Fixed ANTICORROSION C Coat in Condenser I Coat in...

Страница 6: ...ipment comes with a 1 year major warranty after start up Our units use R410A refrigerant which is harmless to the ozone layer and is non toxic and non flammable even in case of leakage Finally the eff...

Страница 7: ...water based synthetic coating with ES2 pigment applied to all areas of the coating surface with no bridging of material between fins Therefore ES2 pigments are suitable for even the most corrosive en...

Страница 8: ...unit in case of service parts or warranty questions This nameplate also contains the unit s refrigerant charge and electrical ratings The evaporator nameplate is under the insulation and contains the...

Страница 9: ...h The foundation must be strong enough to support the weight of the unit see Dimension and Weight Packaged Unit on page 15 The addition of neoprene pads customer supplied under the unit allows water t...

Страница 10: ...can be supplied and installed in the field Piping for units with brazed plate evaporators should have a drain and vent connection at the bottom of the bottom connection piping and at the top of the to...

Страница 11: ...iately after unit start up NOTE Failure to comply with these measures may result in performance and reliability problems P Vibration Eliminators Isolation Valves Thermometer Thermowell Thermowell Ther...

Страница 12: ...controlled by the chiller s microprocessor The controller will activate the pump whenever at least one chiller circuit is enabled for operation This helps ensure proper start up sequence of the unit...

Страница 13: ...y may freeze and not indicate a no flow condition HIGH TEMPERATURE OPERATION CLIC STAND ALONE series units for high temperature operation 105 F to 125 F 40 C to 52 C require the addition of the option...

Страница 14: ...iom clicsa cf eng www clima flex com 14 Refrigeration Schematics Figure 5 Refrigerant schematics...

Страница 15: ...Top View Side View Isometric View Notas 1 25TR Unit Water connections in 6 IN OUT 2101 mm 82 3 4 in 1835 mm 72 1 4 in 784 mm 30 7 8 in 1168 mm 46 in 2215 mm 87 1 4 in 827 mm 32 5 8 in 817 mm 32 1 8 i...

Страница 16: ...d pressure drop in clic stand alone unit Refrigerant Charge Pressure Drop REFRIGERANT CHARGE EVAPORATOR PRESSURE DROP FAMILY TR R410A LBS R410A KG GPM PIPE SIZE DP ft WG CLIC 25 1 X 21 1 X 9 5 60 6 34...

Страница 17: ...codes including NECA AA 10402012 for installation of aluminum wiring in buildings ANSI Wiring inside the unit is sized in accordance with the NEC Refer to the unit nameplate and unit selection report...

Страница 18: ...can cause serious damage to the chiller The procedure required to reconnect generator power to the mains is as follows 1 Set the generator to always run five minutes longer than the unit start timer w...

Страница 19: ...8 SHIELED WIRE J3 J9 WHITE WIRE J3 J9 BLACK WIRE NAKED WIRE ON GROUND COMPRESSOR PROTECTOR Located in compressor electrical connection 24vac protector INTERNAL OVERLOAD PROTECTION MC1 MC2 MC3 HPR PHAS...

Страница 20: ...S L3 MS L2 MS L1 R 2 C1 5L3 22X NC 31X NC 14X NO 43X NO CAL4 11 CAL4 11 21X NC 32X NC 13X NO 44X NO TF96 MC1 L3 MC1 L2 MC1 L1 Compressor connection EXISTING WIRES DO NOT DISCONECT FAN 1 FAN 2 COMPRESS...

Страница 21: ...ATION ONLY IN 2X18 SHIELED WIRE J3 J9 WHITE WIRE J3 J9 BLACK WIRE NAKED WIRE ON GROUND COMPRESSOR PROTECTOR Located in compressor electrical connection 24vac protector INTERNAL OVERLOAD PROTECTION MC1...

Страница 22: ...MS L2 MS L1 R 2 C1 5L3 22X NC 31X NC 14X NO 43X NO CAL4 11 CAL4 11 21X NC 32X NC 13X NO 44X NO TF96 MC1 L3 MC1 L2 MC1 L1 Compressor connection EXISTING WIRES DO NOT DISCONECT FAN 1 FAN 2 COMPRESSOR PR...

Страница 23: ...anel mounted models or sold separately on DIN rail mounted models CAREL s APPLICA app available on Google Play for the Android operating system makes it easy to configure parameters and commission the...

Страница 24: ...chiller on Microchiller On Are there any alarms Is a high pressure alarm present Is a low pressure alarm present Are there alarms for out of range probes Turn on switch ON OFF Hold on start up time Is...

Страница 25: ...apacitor approach The capacitor approximation will be calculated for each circuit The equation is as follows Capacitor approximation Capacitor saturated temperature OAT Suction reheating The suction s...

Страница 26: ...he operating or pumping state They should not operate when the circuit is in any other state Compressor start up A compressor must start if it receives a start command from the unit capacity control l...

Страница 27: ...the bulb to make sure it is properly connected to the suction line If you can move the bulb manually it is not properly secured The bulb must be perfectly insulated to protect it against the effects o...

Страница 28: ...imply has a pump configured in this case this alarm goes together with the current pump configuration A15 This alarm usually appears when the water temperature does not drop due to the current cooling...

Страница 29: ...the equipment is electrically linked to the pump start which means that when the pump is turned on the fan is turned on however this icon is currently represented on the controller as fan present Whe...

Страница 30: ...rm and save the change Press the down key again and the SEtH menu will appear this parameter is used to change the setpoint in HEAT mode only when the units have this option available otherwise it wil...

Страница 31: ...OF THE INTERFACE SCREEN OF THE CAREL APPLICATION VIA CELLULAR PHONE The following image shows the interface of the carel application through Bluetooth communication and monitoring of equipment operati...

Страница 32: ...ounters 25 1 C007 BOOL R W FALSE C007 Comp 1 circ 2 reset hour counters 26 1 C010 BOOL R W FALSE C010 Comp 2 circ 2 reset hour counters 27 1 C034 BOOL R W FALSE C034 High press switch input logic 0 N...

Страница 33: ...FALSE En_SrcRetTempPrb Connected source return temperature probe 90 1 WaitOtherDevCirc1_ SmartOpnExV BOOL R W 0 91 1 LowNoiseActive BOOL R W FALSE Low noise function active 92 1 S073 BOOL R W FALSE S0...

Страница 34: ...anual mode steps 100 1 E003 UINT 0 65535 R W 0 STEPS E003 ExV circ 2 manual mode steps 101 2 E004 REAL R W 6 DELTAKELVIN E004 ExV SH set point in cool 103 2 E005 REAL R W 15 E005 ExV SH control Kp in...

Страница 35: ...R W 0 S014 Source fan ON OFF circ 2 manual mode 0 AUTO 1 OFF 2 ON 219 1 S015 USINT 0 101 R W 0 PERCENT S015 Source fan inverter circ 2 manual mode 0 AUTO 1 0 2 1 101 100 220 2 S016 REAL R W 5 CELSIUS...

Страница 36: ...r pump 1 overload 9 LP pressure switch 10 User pump 2 overload 11 Remote cmd 1 12 Remote cmd 2 13 Source alarm 292 1 Hc07 USINT 0 6 R W 5 Hc07 Digital input 5 con g 0 Not used 1 User ow switch 2 Comp...

Страница 37: ...lve on comp starts 353 1 P012 UINT 0 999 R W 3 SECOND P012 Oil equalisation solenoid valve open time 354 1 P013 UINT 0 999 R W 1 MINUTE P013 Oil equalisation solenoid valve min o time 355 1 P014 UINT...

Страница 38: ...circ 2 3 User heater step 2 4 User pump 2 5 Source 6 Frost heater 7 4way valve 8 Oil equal valve 748 1 Hc63 USINT 0 8 R W 1 Hc63 Digital output 3 secondary con g 0 Not used 1 Comp 1 circ 2 2 Comp 2 c...

Страница 39: ...gue capacity request max value 817 1 U089 USINT 0 2 R W 0 U089 Analogue capacity request input type 0 0 5V 1 0 10V 2 4 20mA 788 1 Hc90 USINT 0 8 R W 0 HC90 Display value selection Large area 789 1 Hc9...

Страница 40: ...rce 1 pump maintenance 17 1 A18 BOOL R FALSE Unit Free cooling fault 18 1 A19 BOOL R FALSE Circuit 1 Discharge pressure probe broken or disconnected alarm 19 1 A20 BOOL R FALSE Circuit 1 Condensing te...

Страница 41: ...rce 1 pump maintenance 17 1 A18 BOOL R FALSE Unit Free cooling fault 18 1 A19 BOOL R FALSE Circuit 1 Discharge pressure probe broken or disconnected alarm 19 1 A20 BOOL R FALSE Circuit 1 Condensing te...

Страница 42: ...1Circ1_DevAlrm Comp 1 circ 1 in alarm condition 93 1 Comp1Circ1_AbleToOn BOOL R FALSE Comp 1 circ 1 enabled to start 94 1 Comp1Circ1_AbleToO BOOL R FALSE Comp 1 circ 1 enabled to stop 95 1 Comp1Circ1_...

Страница 43: ...BOOL R FALSE En_SuctTempPrb_Circ1 Connected suction temp probe for circ 1 167 1 UsrHeater2 BOOL R FALSE UsrHeater2 User heater 2 status 168 1 Al_RegulationAlrms BOOL R FALSE Al_RegulationAlrms Control...

Страница 44: ...e displayed on the control panel The control panel The power LED is activated when the frequency inverter is supplied with mains voltage Green LED on The control section is running Yellow LED Warning...

Страница 45: ...gnal via the digital inputs has higher priority than the Hand on and Auto on control keys QUICK TRANSFER OF PARAMETER SETTINGS Once the configuration of a frequency converter has been completed store...

Страница 46: ...p The following parameter groups can be accessed 0 Operation Display 1 Load Motor 3 Reference Ramps 4 Limits Warnings 5 Digital input output 6 Analog input output 7 Controls 8 Communication and option...

Страница 47: ...heck for refrigerant leaks Open the unit for hydraulic installation only Do not remove the connection guards until the hydraulic circuit is closed Check for foreign objects in the fan discharge Check...

Страница 48: ...quirements and is in automatic mode Check voltage Motor save which is set to supply the correct supply voltage for the unit The percentage of unbalance of the power supply must be calculated with the...

Страница 49: ...ence will begin by checking all pre programmed safety points on the unit If all required conditions are correct the unit will be ready to start operations UNIT CONTROL To start operations turn the ON...

Страница 50: ...e performed on a regular basis Over long periods of operation the heat exchanger will become fouled impairing efficiency and reducing the units performance Consult your local supplier about cleaning t...

Страница 51: ...mended that the unit be turned on 24 hours prior to first start up to begin warming up the compressor crankcase HYDRAULIC MAINTENANCE Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Cleaning of the hy...

Страница 52: ...Inspection of fan blades cleaning of fan blades Quarterly Plan x x x x Real Compressor power consumption check to determine refrigerant loss quarterly Plan x x x x x x Real Compressor oil inspection m...

Страница 53: ...the solenoid Check wiring Motor electrical problems Check for open shorted or bubbled motor Loose wiring Check all wire connections and tighten all terminal screws Compressor makes noise or vibrates C...

Страница 54: ...of regulating condenser temperature Excess oil used If the system has excess oil recover and adjust by observing the sight glass on the compressor Motor overload relays or circuit breakers open Volta...

Страница 55: ...e Loose fitting in oil line Correct to bring conditions within allowable limits Compressor staging intervals too short Control band not properly adjusted Check and correct Water temperature sensor fai...

Страница 56: ...iom clicsa cf eng www clima flex com...