Index
S
ize Acronym
DataType
Min
Value
Max
Value R/W
Init
Value UoM
Description
211
2
PwrRunCircs_Perc
REAL
R
0
PERCENT
PwrRunCircs_Perc - Circuit capacity percentage by
compressors ON
213
2
AFC2
REAL
R
0
CELSIUS
AFC2 - Cond.2 frost temp
215
2
AFE1
REAL
R
0
CELSIUS
AFE1 - Evap.1 frost temp.
217
2
AFC1
REAL
R
0
CELSIUS
AFC1 - Cond.1 frost temp
219
1
IOprbCfgWrn
UINT
R
0
IOcfgPrbWrn - I/O probe confi guration warnings
220
2
W_UsrTempRegPID
REAL
R
0
CELSIUS
W_UsrTempRegPID - Water temperature value used
by control
226
1
DfrStatus_Circ1
UINT
Defrost status of circ 1
227
2
AIN_PwrReq_Circ1
REAL
R
0
PERCENT
Capacity request using analogue input on circuit 1
231
1
SWverEXP
UINT
R
0
Firmware B version on expansion board
232
1
SWverMAIN
UINT
R
0
Firmware B version on main board
233
1
PWRP_ErrCode_Circ1 UDINT
-
-
R
-
-
Power+ circuit 1 error code
234
1
PWRP_ErrCode_Circ2 UDINT
-
-
R
-
-
Power+ circuit 2 error code
Input
S
tatus
Index
S
ize Acronym
DataType Min
Value
Max
Value R/W InitValue UoM Description
0
1
A01
BOOL
R
FALSE
Unit - Error in the number of retain memory writes
1
1
A02
BOOL
R
FALSE
Unit - Error in retain memory writes
2
1
A03
BOOL
R
FALSE
Unit - Remote alarm by digital input
3
1
A04
BOOL
R
FALSE
Unit - Remote set point out of range alarm
4
1
A05
BOOL
R
FALSE
Unit - User return water temperature probe broken or
disconnected alarm
5
1
A06
BOOL
R
FALSE
Unit - User delivery water temperature probe broken or
disconnected alarm
6
1
A07
BOOL
R
FALSE
Unit - Tank temperature probe broken or disconnected alarm
7
1
A08
BOOL
R
FALSE
Unit - User pump 1 overload
8
1
A09
BOOL
R
FALSE
Unit - User pump 2 overload
9
1
A10
BOOL
R
FALSE
Unit - Flow switch alarm, no fl ow present with user pump 1
active
10
1
A11
BOOL
R
FALSE
Unit - Flow switch alarm, no fl ow present with user pump 2
active
11
1
A12
BOOL
R
FALSE
Unit - User pump group alarm
12
1
A13
BOOL
R
FALSE
Unit - User 1 pump maintenance
13
1
A14
BOOL
R
FALSE
Unit - User 2 pump maintenance
14
1
A15
BOOL
R
FALSE
Unit - High chilled water temperature
15
1
A16
BOOL
R
FALSE
Unit - Source return water/air temperature probe broken or
disconnected alarm
16
1
A17
BOOL
R
FALSE
Unit - Source 1 pump maintenance
17
1
A18
BOOL
R
FALSE
Unit - Free cooling fault
18
1
A19
BOOL
R
FALSE
Circuit 1 - Discharge pressure probe broken or disconnected
alarm
19
1
A20
BOOL
R
FALSE
Circuit 1 - Condensing temperature probe broken or discon-
nected alarm
20
1
A21
BOOL
R
FALSE
Circuit 1 - Suction pressure probe broken or disconnected
alarm
21
1
A22
BOOL
R
FALSE
Circuit 1 - Evaporation temperature probe broken or discon-
nected alarm
22
1
A23
BOOL
R
FALSE
Circuit 1 - Discharge temperature probe broken or discon-
nected alarm
23
1
A24
BOOL
R
FALSE
Circuit 1 - Suction temperature probe broken or disconnect-
ed alarm
24
1
A25
BOOL
R
FALSE
Circuit 1 - High pressure alarm from pressure switch
25
1
A26
BOOL
R
FALSE
Circuit 1 - High pressure alarm from transducer
26
1
A27
BOOL
R
FALSE
Circuit 1 - Low pressure alarm from transducer
27
1
A28
BOOL
R
FALSE
Circuit 1 or unit - Frost evaporation temperature alarm
28
1
A29
BOOL
R
FALSE
Circuit 1 - Low pressure alarm from pressure switch
29
1
A30
BOOL
R
FALSE
Circuit 1 - Overload compressor 1
30
1
A31
BOOL
R
FALSE
Circuit 1 - Overload compressor 2
31
1
A32
BOOL
R
FALSE
Circuit 1 - Compressor 1 maintenance
32
1
A33
BOOL
R
FALSE
Circuit 1 - Compressor 2 maintenance
33
1
A34
BOOL
R
FALSE
Circuit 1 - Source fan 1 maintenance
34
1
A35
BOOL
R
FALSE
Circuit 1 EVD - Low superheat (SH)
35
1
A36
BOOL
R
FALSE
Circuit 1 EVD - Low evaporation pressure (LOP)
36
1
A37
BOOL
R
FALSE
Circuit 1 EVD - Maximum evaporating pressure (MOP)
37
1
A38
BOOL
R
FALSE
Circuit 1 EVD - Valve motor error
38
1
A39
BOOL
R
FALSE
Circuit 1 EVD - Emergency closing
39
1
A40
BOOL
R
FALSE
Circuit 1 EVD - Incomplete valve closing
40
1
A41
BOOL
R
FALSE
Circuit 1 EVD - Offl ine
41
1
A42
BOOL
R
FALSE
Circuit 1 Envelope - General alarm + Zone alarm
42
1
A43
BOOL
R
FALSE
Circuit 1 BLDC - Delta pressure greater than the allowable
at startup
43
1
A44
BOOL
R
FALSE
Circuit 1 BLDC - Starting failure
44
1
A45
BOOL
R
FALSE
Circuit 1 BLDC - Low diff erential pressure
45
1
A46
BOOL
R
FALSE
Circuit 1 BLDC - High discharge gas temperature
46
1
A47
BOOL
R
FALSE
Circuit 1 Inverter - Offl ine
47
1
A48
BOOL
R
FALSE
Circuit 1 Inverter - General alarm + Error code
48
1
A49
BOOL
R
FALSE
Unit - Secondary board is offl ine
49
1
A50
BOOL
R
FALSE
Unit - Error in the number of retain memory writes on
Secondary board
50
1
A51
BOOL
R
FALSE
Unit - Error in retain memory writes on Secondary board
Mapping Table