8 Technical data
Installation manual
28
C08AA
Daikin hybrid for multi heat pump – heat pump module
4P471756-1C – 2017.10
INFORMATION
▪ h=The height measured from the floor to the flare nut.
▪ H=The height measured from the floor to the bottom of
the casing.
▪ For intermediate H values (i.e., when H is between 2 H
values from the table), consider the value that
corresponds to the lower H value from the table. If
H=950 mm, consider the value that corresponds to
"H=900 mm".
▪ In cases where H≤600 mm, h is always considered to
be 600 mm, as specified in IEC 60335-2-40:2013 A1
2016, clause GG2.
▪ For intermediate A
room
values (i.e., when A
room
is
between 2 A
room
values from the table), consider the
lower A
room
value from the table. If A
room
=12.5 m
2
,
consider the value that corresponds to "A
room
=12 m
2
".