3P257556-2A        English

7

4-3/16~4-7/16  (107~112)

7-2

 (6)

Panel

Lower side 
of panel

Indoor unit

Lower part of hook of 
the indoor unit

(The ceiling is 
omitted from the 
illustration for ease 
of explanation)

Seal

Indoor unit

Lower part of 
hook of the 
indoor unit

Ceiling

Mounting bracket

Lower side of panel

Panel

Cross sections (4 points)

in. (mm)

4-3/16~4-7/16 (107~112)

Note

 

Tighten the screws securely, or otherwise a defect as shown 
below may result.

 

Readjust the height of the indoor unit if there is a space between 
the ceiling and panel with the screws tightened securely.

Air 

leakage

Air leakage 

from the 

ceiling side.

Generation 

of dirt

Drew condensation 

or dripping

Make sure that there is no space.

Height adjustments to the unit 
will be possible through the 
holes on the corners of the 
panels without removing the 
panel, provided that the 
adjustments does not affect the 
levelness or the drain piping of 
the indoor unit. Refer to the 
installation manual of the indoor 
unit to conduct the work.

7-3  Checking panel

(1) Remove sealing of panel.

1

2

1

2
3

4

Remove seal of panel

Insert the seal until the seal comes in contact with the 
clamp

Clamp 

Sealing (accessory (6))

(2) Draw the harness and lead wires (on the panel side).

Panel

Harness

Harness

Lead wire 
(on the panel side)

Lead wire 
(on the panel side)

(3) Connect the connector of the lead wires and move the glass 

tube to cover the connector part.

Lead wire 
(on the panel side)

Harness

Connector

Be sure to connect 
them securely.

Move the 
glass tube.

1

2

Glass tube

(4) Tighten and secure both ends of the glass tube with the 

clamps on the glass tube together with provided clamps 
(accessories (5)). Cut the excess portions of the clamps from 
their roots after the both ends are secured.

Tighten the clamps

Cut the roots

Clamp
(accessory (5))

(5) Return the connected lead wires to the space between the 

indoor unit and panel. 
(Accommodate the lead wires in the shaded part shown in the 
illustration.)

Note

Accommodate the lead wires carefully so that the lead wires 
do not come in contact with the air filter.

Connected 
lead wires

Connected 
lead wires

Panel

Control box of 
the indoor unit

(6) Remove the control box cover from the indoor unit.  

Refer to "6-2 Attaching harness (accessory (4))" on page 5.

Control box

Resin cover

Open the resin cover

3P257556-2A.indb   7

12/16/2013   4:28:01 PM

Содержание BYCQ125BGW1

Страница 1: ...Decoration Panel Provided with Filter Auto cleaning Function Self Cleaning Decoration Panel INSTALLATION MANUAL BYCQ125BGW1 3P257556 2A 3P257556 2A indb 1 12 16 2013 4 27 52 PM ...

Страница 2: ... carry the product Do not carry the package with the polypropylene band on the package held which will be dangerous because the polypropyl ene band may be deformed Do not touch the fin of the heat exchanger Touching the fin improperly may result in injury Do not turn the product power off immediately after the operation of the product comes to a stop Always wait for at least 5 minutes before turni...

Страница 3: ...r Panel 4 6 Preparations for Indoor Unit 5 7 Attaching Panel to Indoor Unit 6 8 Attaching Suction Grille and Decoration Corner Covers 9 9 Operation Mode Settings 11 10 Field Settings 11 11 Test Operation 12 The English text is the original instruction Other languages are translations of the original instructions 3P257556 2A indb 1 12 16 2013 4 27 52 PM ...

Страница 4: ...s Result Was the test operation of the air conditioner finished Did you explain the operation method of the air conditioner to the customer while showing the customer the operation manual Did you make mode settings for filter auto cleaning automatic control operation settings or timer operation settings with an operation time zone specified and provide information on the set mode operation of the ...

Страница 5: ...lighting applies to exposed models e g models of inverted mountain type and there are no restrictions on embedded models with no protrusion from the ceiling surface 3 If the air discharge outlet is closed or the wind direction of the swing flaps are changed to block the wind the space marked with the asterisk will be 20 in 500 mm or over The space will be 8 in 200 mm or over if the air discharge o...

Страница 6: ...tective corrugated cardboard Protective corrugated cardboard top The accessories are on the backside Protective corrugated cardboard bottom Note Do not impose force on the swing flap brush unit or air filter when handling the panel Panel Brush unit Air filter Swing flap 5 2 Removal of decoration corner covers Panel Decoration corner cover Decoration corner cover Decoration corner cover Decoration co...

Страница 7: ... after installing the indoor unit Install the indoor unit according to the installation manual provided with the indoor unit 6 1 Attaching spacer accessory 1 1 Remove the bypass hole closing cap 1 2 1 Indoor unit 2 Remove the bypass hole closing cap 2 Peel off the release paper of the double stick tape on the backside of the spacer accessory 1 3 Attach the spacer accessory 1 on the air bypass hole...

Страница 8: ... panel on the internal circumference side to the hooks of the indoor unit Note Let go your hands after confirming through the check window that the temporary latching brackets are engaged with the hooks 2 Remove from the harness opening as described in 6 Preparations for Indoor Unit on page 5 Pull out the lead wires disconnected from the decoration cover in the corner carefully so that lead wries ...

Страница 9: ...e seal of panel 2 Insert the seal until the seal comes in contact with the clamp 3 Clamp 4 Sealing accessory 6 2 Draw the harness and lead wires on the panel side Panel Harness Harness Lead wire on the panel side Lead wire on the panel side 3 Connect the connector of the lead wires and move the glass tube to cover the connector part Lead wire on the panel side Harness Connector Be sure to connect ...

Страница 10: ...illustration 1 2 3 4 5 1 Clasp 2 Hooked fall prevention cord 3 Panel 4 Fall prevention cord 5 Dust box 2 Attach the dust box in the order opposite to the procedure in 5 3 Removal of dust box on page 4 Note Make sure that the fall prevention cord is not caught by the exhaust opening on the dust box when attaching the dust box Otherwise the dust box may not function normally 3 Turn the fixing knobs ...

Страница 11: ...vention cord 3 Connect the flexible hose accessory 2 onto the panel side The flexible hose accessory 2 has no directionality constraint Flexible hose junction on the panel side Flexible hose accessory 2 Flexible hose junction on the panel side Fit the clamps into the hooks in two points securely Hooks 2 points Note Check that the clamps are engaged securely Otherwise a dust collection failure may ...

Страница 12: ...flexible hose accessory 2 has no directionality constraint Flexible hose junction on the panel side Fit the clamps into the hooks in 2 points securely Flexible hose accessory 2 Flexible hose junction on the panel side Hooks 2 points Note Check that the clamps are engaged securely Otherwise a dust collection failure may result 4 Press fit the flexible hose connected in 3 into the panel Make sure th...

Страница 13: ...owing operation modes can be selected for the filter auto cleaning of the self clean panel Operation mode Description 1 Scheduled timer operation Performs filter auto cleaning during the designated period selected from eight periods 2 00 00 to 03 00 operation Performs filter auto cleaning during the factory set period of time 00 00 to 03 00 3 Auto control operation Performs filter auto cleaning ac...

Страница 14: ...th the remote controller Test operation method with remote controller 1 Stop the operation of the panel if the panel is in air conditioning operation 2 Continue pressing the Cancel button at least 4 seconds while the backlight is lit The service settings menu will appear 3 Select Test Filter Auto Clean from the service settings menu and press the Menu Enter button 4 will appear on the basic screen...

Страница 15: ...3P257556 2A indb 13 12 16 2013 4 28 10 PM ...

Страница 16: ...3P257556 2A EM13A021 1401 FS 3P257556 2A indb 1 12 16 2013 4 28 11 PM ...

Отзывы: