6-6 PIPING INSULATION
•
After the gas leak inspection is completed, refer to the following figures and use the included insulation tube
3) and clamps 2)-2 to apply the insulation.
NOTES
•
Insulate all of the piping including the liquid pipes, HP/LP gas pipes, suction gas pipes, gas pipes, and the
pipe connections for these. Not insulting these pipes could result in water leaks or burns. In particular, suc-
tion gas flows in the HP/LP gas pipes during full cooling operation, so the same amount of insulation as
used for the suction gas pipes is required. In addition, high-pressure gas flows in the HP/LP gas pipes and
gas pipes, so use insulation that can withstand more than 250°F.
•
When reinforcing the insulation material for the installation environment, also reinforce the insulation on the
piping protruding from the unit and on the pipe connections. Locally purchase the insulation required for the
reinforcement work.
Insulation Installation Precautions
1.
Seal so that air cannot be in and out of the end.
2.
Do not over tighten the clamp so as to maintain the insulation thickness.
3.
Be sure to attach the insulation (field supply) with the seams facing up.
(See figure at right.)
BSVQ36 · 60P type
BS unit
Insulation tube 3)-2
(Accessory)
Insulation
tube 3)-2
(Accessory)
Insulation
tube 3)-1
(Accessory)
Insulation tube 3)-2
(Accessory)
Insulation tube 3)-1
(Accessory)
Suction gas pipe
(Note 1)
Gas pipe
(Note 1)
Liquid pipe
HP/LP gas pipe
(Note 1)
Liquid pipe
Insulation Attachment Instructions
Piping insulation
(Product piping side)
Pipe connection
Insulation material
(Field supply)
Piping insulation
(Site piping side)
(1) Attach the included
insulation.
(2) Seal
(3) Use the clamps (accessory)
to hold both ends.
Note 1: For suction gas pipes, HP/LP gas
pipes, and gas pipes, after
attaching the included insulation
tube, wrap more insulation (field
supply) around the connections.
Main unit
Clamp 2)-1 (Accessory)
Clamp 2)-2 (Accessory)
BSVQ96P type
BS unit
Clamp 2)-2 (Accessory)
Insulation tube 3)-2
(Accessory)
Insulation
tube 3)-2
(Accessory)
Insulation
tube 3)-1
(Accessory)
Insulation tube 3)-1
(Accessory)
Insulation tube 3)-3
(Accessory)
Gas pipe
(Note 2)
Liquid pipe
Suction gas pipe
(Note 2)
HP/LP gas pipe
(Note 1)
Liquid pipe
Clamp 2)-2 (Accessory)
Seal the connection.
Note 2: For Model Q96, wrap sealing
material (field supply) around the
insulation tube 3)-2 BS unit side
and site piping side connections
to seal them.
Main
unit
Insulation tube 3)-2
(Accessory)
Attach facing up
Seam