18 English 

8-5  Wiring connections

(Remove the control box cover and connect the wiring as shown in the fi gure below.)

X1M

Transmission wiring 
from outdoor unit or BS 
unit

Transmission wiring to 
BS unit

(Upstream)

(Downstream)

Wire clip

Clamps (2)

(Accessories)

Wire clip

Clamps (2)

(Accessories)

Power supply terminal block

Wiring through hole

Earth terminal

Earth wire

Transmission 
wiring from 
indoor units

Turn so that the terminal is 
not subject to tensile force.

Turn slightly so that the 
area near the terminal 
is not subject to tensile 
force.

Bundle transmission 
wiring together.

Clamps (2) (Accessories)

• 

Transmission wiring
Remove the control box cover and connect the wires to the transmission wiring terminals (outdoor unit 
F1 and F2, BS unit F1 and F2, and each indoor unit (for example, for the BS16Q14AV1, indoor unit A 
through P) (F1 and F2)).
At this time, pass the wiring into the unit through the wiring through hole and use the included clamps (2) 
to securely hold the wires. For more information about how much insulation to strip off transmission wir-

ing, refer to the following fi gure.

Transmission wiring

10

50

CAUTION

Verify that the piping line coincides with the transmission wiring.

01_EN_3P194121-8U.indd   18

2/21/2014   3:31:15 PM

Содержание BS4Q14AV1

Страница 1: ...ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO P...

Страница 2: ...ay result in minor or moderate injury It may also be used to alert against unsafe practices WARNING Ask your local dealer or qualified personnel to carry out installation work Improper installation ma...

Страница 3: ...fter completing the installation work check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a sour...

Страница 4: ...that the following accessories have been included in the packaging Important Do not throw away any accessories that may be needed in installation work until installation is complete Name Accessory pip...

Страница 5: ...ta book Example selection In case of the BS unit with connect a FXCQ32M and a FXSQ40M Total capacity 31 25 40 71 25 2 4 Checklist Exercise particular care concerning the following items during install...

Страница 6: ...unit 450 450 70 300 or more 500 or more 1 450 2 Control box 100 or more 3 100 or more Drain pan Maintenance space Control box and motorized valve coil Maintenance space Indoor unit side pipe 1 Unit m...

Страница 7: ...ion pipe All the above parts must be supplied in the field Example installation 5 BS UNIT INSTALLATION Use only accessories and parts that conform to the designated specifications when installing the...

Страница 8: ...nd included with the outdoor unit Before beginning the work be sure to verify that the type of refrigerant used is R410A The unit will not operate correctly with a different type of refrigerant Insula...

Страница 9: ...of the pipes between the BS unit and the refrigerant branch kits and between the refrigerant branch kits and indoor units Upstream Suction gas pipe HP LP gas pipe Liquid pipe BS unit Downstream Indoo...

Страница 10: ...new units Be sure to use the stop valve kit for extension KHFP26M224 sold separately for pipe that you plan to expand in the future Do not size pipe based on anticipated future expansion Instead reex...

Страница 11: ...cut and connect as it is In case of others cut the outlet pipe and connect to the connecting pipe In accordance with the following instructions Cutting point Center of connection area Connect Local pi...

Страница 12: ...and gas piping so use insulation that can withstand more than 120 C When reinforcing the insulation material in accordance with the installation environment also reinforce the insulation on the pipin...

Страница 13: ...ulation material with the seam facing up Refer to Fig 3 7 DRAIN PIPING WORK 1 Drain piping work Install drain piping so that wastewater drains reliably Use a pipe diameter that is the same as or great...

Страница 14: ...terval of 1 to 1 5 m so that the pipe does not droop Refer to Fig 4 Metal clamp 5 Sealing material 6 Accessories Accessories Drain hoses 4 Accessories To prevent condensation do not leave any gap Fig...

Страница 15: ...nit body to wire the outdoor unit and indoor units Properly connect wire of the specified wire type and copper thickness Also use the included clamp to avoid applying excessive force to the terminal f...

Страница 16: ...se insulated wire for the power cord Select the power supply cable type and size in accordance with relevant local and national regulations Specifications for local wiring are in compliance with IEC60...

Страница 17: ...unit Note 1 Indoor unit A Indoor unit B 1 Indoor unit B 2 Note 3 Indoor unit C Note 2 Indoor unit Indoor unit OUT OUT OUT IN Never connect to power supply wiring When joining branch pipes Indoor unit...

Страница 18: ...external force Use an appropriately sized screwdriver to tighten the terminal screws Use of a screwdriver that is too small could damage the screw head and prevent proper tightening Overtightening th...

Страница 19: ...subject to tensile force Bundle transmission wiring together Clamps 2 Accessories Transmission wiring Remove the control box cover and connect the wires to the transmission wiring terminals outdoor un...

Страница 20: ...hen fastening the wire use the included clamp 2 so as not to apply tensile force to the wire connec tion and then securely fasten the wire Also after the wiring is completed organize the wiring so tha...

Страница 21: ...P Piping branch port number Terminal No to which to connect transmission wiring DIP switch Setting 1 Setting for branch ports to which no indoor unit is connected Setting Setting for branch ports to w...

Страница 22: ...ional charge of refrigerant 11 CHECK OPERATION AND TEST OPERATION 1 Verify that the control box cover is closed 2 Refer to the installation manual included with the outdoor unit and conduct a check an...

Страница 23: ...3P194121 8U EM13A025A 1402 HT 00_CV_3P194121 8U indd 2 2 15 2014 3 47 51 PM...

Отзывы: