This BS unit is only for systems for Models REYQ-T.
It cannot be connected to systems for Models REYQ-M+REYQ-P.

For series of applicable indoor units, refer to the catalog or other literature.

Select the BS unit to fit the total capacity (sum of unit’s capacity) and max. number of the indoor units to be 
connected downstream. About indoor unit’s capacity, refer to the Table 2.

Table 1 

Table 2 

* About indoor unit’s capacity for HRV type (VKM), refer to the Engineering data book.

<

Example

>

In case of the BS unit which connects two FXCQ

32

M and two FXSQ

40

M.

Total capacity = 

31.25

x2+

40

x2 = 142.5 

 

Select BS1Q16

2-5 CHECK ITEM

For the following items, take special care during construction and check after installation is finished.

Completion check items

Hand-over check items

3. SELECTING INSTALLATION SITE

The equipment is not intended to be installed in spaces where it is better to avoid noise, like bedrooms. (

Refer 

to Fig. A

).

The equipment is not intended for use in a potentially explosive atmosphere.
Select an installation site where the following conditions are satisfied and that meets with your customer’s 
approval.

Where is resistible against weight of BS unit.

Locations where the wall is not significantly tilted.

Where sufficient clearance for maintenance and service can be ensured. (

Refer to Fig. 1

)

Locations where an inspection hole (

Refer to Fig. 2

) can be installed to EL. COMPO. BOX side (See Note).

Where the total piping length involving indoor unit and outdoor unit is below the allowable piping length.
(See installation manual attached to outdoor unit.)

Model

Total capacity of all downstream indoor units

Max. number of all downstream indoor units

BS1Q10

 100

6

BS1Q16

100 < A 

 160

8

BS1Q25

160 

<

 A 

 250

8

Capacity expressed as indoor unit’s model No.

15

20

25

32

40

50

63

80

100

125

200

250

Indoor unit’s capacity (for use in computation)

15

20

25

31.25

40

50

62.5

80

100

125

200

250

Check items

Problems

Check

Are the BS units installed securely?

Falling, vibration, and operating noise

Have you performed a gas leak test?

Does not cool or heat

Is the insulation complete? (Refrigerant piping and pipe connection part)

Water leaking

Is the voltage the same as that listed on the unit’s nameplate?

Does not operate/burnt out

Are all the wiring and piping correct?

Does not operate/burnt out

Is the unit grounded?

Dangers during electrical leak

Is the thickness of the power cord as specified?

Does not operate/burnt out

Check items

Check

Did you close the EL. COMPO. BOX lid?

Did you hand the operating manual and warranty card to the customer?

Содержание BS1Q10ACV1B

Страница 1: ...READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE INSTALLATION MANUAL BS unit BS1Q10ACV1B BS1Q16ACV1B BS1Q25ACV1B System air conditioner...

Страница 2: ...EKBSVQLNP eg ISOVER 1000S EKBSVQLNP eg ISOVER 1000S A 1 2 3 4 5 6 7 8 9 1 0...

Страница 3: ...s The original instructions are written in English All other languages are translations of the original instructions Meaning of WARNING and CAUTION notices WARNING Failure to follow these instructions...

Страница 4: ...tric shocks fire or the terminals overheating If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant gas comes into contact with fire...

Страница 5: ...ant R410A requires that strict precautions be observed for keeping the system clean dry and tightly sealed Clean and dry Strict measures must be taken to keep impurities including SUNISO oil and other...

Страница 6: ...rt especially the refrigerant piping About installation of outdoor and indoor unit refer to the installation manual provided with the outdoor and the indoor unit This unit both indoor and outdoor is s...

Страница 7: ...nit Locations where the wall is not significantly tilted Where sufficient clearance for maintenance and service can be ensured Refer to Fig 1 Locations where an inspection hole Refer to Fig 2 can be i...

Страница 8: ...or the like Install the BS unit so that its weight can be withstood Hanging bracket For supporting the connection pipe Be sure to support the connection piping around the unit using hanging brackets...

Страница 9: ...0 3 pcs 4 locations and washers For M8 Outside diameter dimension 24 to 28mm For M10 Outside diameter 30 to 34mm 2 pcs 4 locations field supply from both the top and bottom sides of the hanging bracke...

Страница 10: ...R410A Be sure to use the special pipe cutters for R410A during installation Make sure that nothing besides the specified refrigerant such as air gets into the refrigerant piping If refrigerant gas lea...

Страница 11: ...the refrigerant pipe joints Using a chlorine flux may cause the pipes to corrode and if it contains fluoride it may cause the refrigerant lubricant to deteriorate adversely affecting the refrigerant...

Страница 12: ...indoor units Piping size outer diameter x minimum thickness Gas pipe Liquid pipe 15 20 25 32 40 50 12 7x0 80 6 4x0 80 63 80 100 125 15 9x0 99 9 5x0 80 200 19 1x0 80 250 22 2x0 80 mm BS unit Piping si...

Страница 13: ...uid pipe Site piping Gas pipe Site piping Liquid pipe Site piping BS unit Top Accessory pipes 1 2 Accessory pipes 1 1 Gas pipe Site piping Liquid pipe Site piping BS unit Top Suction gas pipe Site pip...

Страница 14: ...ulation field supply with the seams facing up See figure at right BS1Q10 16 type BS1Q25 type BS unit BS unit Clamp 2 2 Accessory Clamp 2 2 Accessory Insulation tube 3 2 Accessory Insulation tube 3 2 A...

Страница 15: ...unction Do not turn on the power supply branch switches overload interrupters until all other work is done 7 2 EXAMPLE FOR THE WHOLE SYSTEM 7 3 POWER CIRCUIT SAFETY DEVICE AND CABLE REQUIREMENTS A pow...

Страница 16: ...the EL COMPO BOX lid and connect the wires to F1 and F2 TO IN D UNIT and F1 and F2 TO OUT D UNIT transmission wiring terminals control PCB A1P At this time pass the wiring into the unit through the w...

Страница 17: ...he wire through hole to protect the wires Do not pass the transmission wiring and power supply wiring through the same locations and outside of the unit keep them separated by at least 50mm Not doing...

Страница 18: ...r to the Engineering data book Setting method The setting is made using the Local Setting Mode by the remote controller of indoor unit connected to the BS unit For information regarding the setting me...

Страница 19: ...ADAPTOR FOR OUTDOOR UNIT X38A CONNECTOR ADAPTOR FOR MULTI TENANT NOTES 1 THIS WIRING DIAGRAM APPLIES TO THE BS UNIT ONLY 2 TERMINAL STRIP CONNECTOR TERMINAL FIELD WIRING PROTECTIVE EARTH 3 WHEN USING...

Страница 20: ...4P357812 1B 2023 10 Copyright 2014 Daikin...

Отзывы: